| 2015-06-25 09:27:52 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | |
| | 1) PROVIDE AC LOAD CALCULATIONS FOR THE AC SYSTEMS IN |
| | ACCORDANCE WITH ACCA MANUAL J- SECTION 403.6.1 FBC-10 |
| | ENERGY CONSERVATION. |
| | 2) THE SUBMITTED ENERGY CALCULATION FORM 405-10 IS |
| | INCOMPLETE: A) DOCUMENT MUST BE SIGNED AND DATED BY THE |
| | PREPARER AND THE OWNER- SEE PAGE 1. B) CODE COMPLIANCE |
| | CHECKLIST ON PAGE 6 MUST BE CHECKED OFF. C) THE INPUT |
| | DATA REPORT INDICATING THE THERMAL ENVELOPE |
| | CONSTRUCTION AND INSULATION MATERIALS AND VALUES MUST |
| | BE SUBMITTED. PLEASE NOTE THE PLAN DOES NOT CLEARLY |
| | INDICATE INDICATE WALL, CEILING, AND ATTIC INSULATIONS |
| | AND R-VALUES TO CORRELATE WITH THE CALCS- REFERENCE |
| | SECTION 103.22. FBC-10 ENERGY CONSERVATION. |
| | 3) SHEET M-1, AIR HANDLER CLOSET: A) PROVIDE THE |
| | DIMENSIONS OF THE RETURN AIR GRILL D1400 AT CLOSET. B) |
| | PROVIDE THE DIMENSIONS OF THE AIR HANDLER CLOSET AND |
| | AIR HANDLER CLEARANCE MEASUREMENTS IN COMPLIANCE WITH |
| | SECTION M1305.1.1 FBC-10 RESIDENTIAL. C) INDICATE THE |
| | THE TYPE OF AIR BARRIER TO BE INSTALLED ON THE WALLS |
| | AND CEILING OF THE CLOSET AND HOW IT WILL BE SEALED. D) |
| | PROVIDE DETAILS FOR THE DOUBLE DOORS- PLEASE NOTE RATED |
| | DOORS WITH THRESHOLD AND WEATHER STRIPPING ARE |
| | REQUIRED- SECTIONS R302.5.1 & M1601.4.1 |
| | 4) M-2 AIR HANDLER CLOSET: A) REFERENCE COMMENTS 3B, & |
| | C ABOVE, AND ALSO INDICATE THE DIMENSIONS OF THE RETURN |
| | DUCT AND GRILL MAKING CONNECTION INTO THE CLOSET |
| | 5) M-3: PLEASE REMOVE THE DUCT SMOKE DETECTOR NOTES |
| | FROM THE CONTROLS DIAGRAM UNLESS THEY ARE ACTUALLY |
| | BEING INSTALLED- NOTE THEY ARE NOT REQUIRED FOR SINGLE |
| | FAMILY HOMES. |
| | |