| 2015-06-25 13:13:52 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE |
| | REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH |
| | RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN |
| | CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE |
| | DIGITAL PLANS. |
| | |
| | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | |
| | SHEET E-0 |
| | 1. AMEND THIS NOTE TO ALSO INCLUDE: THE TIP OF A |
| | CEILING (PADDLE) FAN BLADE, PER NFPA 29.8.3.4(8) |
| | 2. CORRECT THIS TO READ: NFPA 101, 2012 EDITION |
| | 3. CORRECT THIS TO READ: NFPA 72, 2010 EDITION |
| | 4. THOUGH THE INDIVIDUAL PANEL CALCS WILL COMPLY WITH |
| | THE PROPOSED CONDUCTORS AND THE SERVICE CONDUCTORS AS A |
| | WHOLE. THE NUMBERS AS REFLECTED HEREIN SHALL BE |
| | CORRECTED. |
| | SHEET E-1 |
| | 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL |
| | 2. AN ADDITIONAL OUTLET WILL BE REQUIRED IN THIS AREA |
| | TO COMPLY WITH MINIMUM OUTLET SPACING REQUIREMENTS |
| | 3. THESE OUTLETS CAN'T BE BEHIND OR OBSTRUCTED BY THE |
| | POOL EQUIPMENT. |
| | 4. AN ADDITIONAL OUTLET WILL BE REQUIRED IN THIS AREA |
| | TO COMPLY WITH MINIMUM OUTLET SPACING REQUIREMENTS |
| | 5. PER NFPA 29.8.3.4(9), A SMOKE DETECTOR IS REQUIRED |
| | IN THIS AREA |
| | 6. ACCORDING TO THE CIRCUIT SCHEDULE OF PANEL "A", |
| | CIRCUIT 23 IS FOR THE REFRIGERATOR. INDICATE IF AN |
| | ADDITIONAL CIRCUIT WILL BE DRAWN FOR THE MICROWAVE. |
| | 7. CORRECT THIS MISQUOTED CODE SECTION. THE APPLICABLE |
| | FBC IS 2010 SECTION 907.2.11.4 |
| | 8. THE FOLLOWING NOTES WERE ADDED TO THE DRAWING: |
| | A) NEC 240.24 LOCATION IN OR ON PREMISES. (A) & (B) |
| | PANELS SHALL BE LOCATED SUCH THAT OVER CURRENT DEVICES |
| | ARE ACCESSIBLE AND THAT OCCUPANTS SHALL HAVE ACCESS TO |
| | OCP DEVICES. |
| | B) NEC 250.94 BONDING FOR OTHER SYSTEMS. THE |
| | INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| | INSTALLED. |
| | C) NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | D) NEC 406.8(B) RECEPTACLES IN WET LOCATIONS. 15- AND |
| | 20-AMPERE, 125- AND 250-VOLT RECEPTACLES INSTALLED IN A |
| | WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS |
| | WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS |
| | INSERTED. ALL 15- AND 20-AMPERE, 125- AND 250-VOLT |
| | NONLOCKING RECEPTACLES SHALL BE LISTED |
| | WEATHER-RESISTANT TYPE. |
| | SHEET E-2 |
| | 1. PER NFPA 29.8.3.4(9), A SMOKE DETECTOR IS REQUIRED |
| | IN THIS AREA & PER FBC-R 315 IT SHALL BE COMBINATION |
| | SMOKE & CARBON MONOXIDE DETECTOR. |
| | 2. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN |
| | 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET |
| | INSTALLED WITHIN THE PERIMETER OF THE BALCONY. |
| | 3. THIS DETECTOR ALONE DOES NOT MEET THE LOCATION |
| | REQUIREMENTS OF NFPA 29.5.1(2) WITH RELATION TO BEDROOM |
| | 3 OR THE FUTURE BONUS ROOM. |
| | 4. THIS AHU SHALL HAVE A DISCONNECT AS REQUIRED BY NEC |
| | 440.14 |
| | 5. REARRANGE THE BEDROOM OUTLETS TO COMPLY WITH NEC |
| | 210.52 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | |