| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15050419 |
| | ADD: 1009 BANYAN BLVD. |
| | CONT: T. B. D. |
| | TEL: ( ?????? |
| | E-MAIL:????? |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. MAY 16/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET GS-1 MISSING THE GEOTECHNICAL REPORT PREPARED |
| | BY RESOURCENET INTERNATIONAL, INC PROJECT NUMBER : |
| | 1409. REVIEW 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | |
| | 2) SHEET GS-1 WIND DESIGN CRITERIA: THE EXPOSURE IS |
| | INDICATED AS A EXPOSURE B. TO THE WEST IS LAKE |
| | MANGONIA. 2010 FBC-B SURFACE ROUGHNESS C. OPEN TERRAIN |
| | WITH SCATTERED OBSTRUCTIONS HAVING HEIGHTS GENERALLY |
| | LESS THAN 30 FEET (9144 MM). THIS CATEGORY INCLUDES |
| | FLAT OPEN COUNTRY AND GRASSLANDS.THIS SURFACE ROUGHNESS |
| | SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN SURFACE |
| | ROUGHNESS B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN |
| | 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF |
| | SURFACE ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE |
| | THAN 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET |
| | IN THE UPWIND DIRECTION. SHORT-TERM (LESS THAN TWO |
| | YEAR) CHANGES IN THE PRE-EXISTING TERRAIN EXPOSURE, FOR |
| | THE PURPOSES OF DEVELOPMENT, SHALL NOT BE CONSIDERED |
| | SURFACE ROUGHNESS C. WHERE DEVELOPMENT BUILDOUT WILL |
| | OCCUR WITHIN THREE YEARS AND THE RESULTANT CONDITION |
| | WILL MEET THE DEFINITION OF SURFACE ROUGHNESS B, |
| | SURFACE ROUGHNESS B SHALL BE REGULATING FOR THE PURPOSE |
| | OF PERMITTING. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY |
| | AND GRASSLANDS AND SHALL EXTEND DOWNWIND FOR A DISTANCE |
| | OF 1500 FEET. |
| | |
| | 3A) SHEET GS-5 & 16S-8 BOTH SHOW GUARDRAIL SYSTEMS |
| | PLEASE SHOW COMPLIANCE WITH: 2010 FBC-B 1013.2 REQUIRED |
| | GUARDS SHALL BE NOT LESS THAN 42 INCHES (1067 MM) HIGH, |
| | MEASURED VERTICALLY ABOVE THE ADJACENT WALKING |
| | SURFACES, ADJACENT FIXED SEATING OR THE LINE CONNECTING |
| | THE LEADING EDGES OF THE TREADS. |
| | |
| | 3B) PROVIDE COMPLIANCE WITH: 2010 FBC-B 1013.3 OPENING |
| | LIMITATIONS. EXCEPTION (3). AT ELEVATED WALKING |
| | SURFACES FOR ACCESS TO AND USE OF ELECTRICAL, |
| | MECHANICAL OR PLUMBING SYSTEMS OR EQUIPMENT, GUARDS |
| | SHALL NOT HAVE OPENINGS WHICH ALLOW PASSAGE OF A SPHERE |
| | 21 INCHES (533 MM) IN DIAMETER. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |