 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050419
 ADD: 1009 BANYAN BLVD.
 CONT: T. B. D.
 TEL: ( ??????
 E-MAIL:?????
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. MAY 16/2015
 ACTION: DENIED
  
 1) SHEET GS-1 MISSING THE GEOTECHNICAL REPORT PREPARED
 BY RESOURCENET INTERNATIONAL, INC PROJECT NUMBER :
 1409. REVIEW 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL.
  
 2) SHEET GS-1 WIND DESIGN CRITERIA: THE EXPOSURE IS
 INDICATED AS A EXPOSURE B. TO THE WEST IS LAKE
 MANGONIA. 2010 FBC-B SURFACE ROUGHNESS C. OPEN TERRAIN
 WITH SCATTERED OBSTRUCTIONS HAVING HEIGHTS GENERALLY
 LESS THAN 30 FEET (9144 MM). THIS CATEGORY INCLUDES
 FLAT OPEN COUNTRY AND GRASSLANDS.THIS SURFACE ROUGHNESS
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN SURFACE
 ROUGHNESS B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN
 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF
 SURFACE ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE
 THAN 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET
 IN THE UPWIND DIRECTION. SHORT-TERM (LESS THAN TWO
 YEAR) CHANGES IN THE PRE-EXISTING TERRAIN EXPOSURE, FOR
 THE PURPOSES OF DEVELOPMENT, SHALL NOT BE CONSIDERED
 SURFACE ROUGHNESS C. WHERE DEVELOPMENT BUILDOUT WILL
 OCCUR WITHIN THREE YEARS AND THE RESULTANT CONDITION
 WILL MEET THE DEFINITION OF SURFACE ROUGHNESS B,
 SURFACE ROUGHNESS B SHALL BE REGULATING FOR THE PURPOSE
 OF PERMITTING. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY
 AND GRASSLANDS AND SHALL EXTEND DOWNWIND FOR A DISTANCE
 OF 1500 FEET.
  
 3A) SHEET GS-5 & 16S-8 BOTH SHOW GUARDRAIL SYSTEMS
 PLEASE SHOW COMPLIANCE WITH: 2010 FBC-B 1013.2 REQUIRED
 GUARDS SHALL BE NOT LESS THAN 42 INCHES (1067 MM) HIGH,
 MEASURED VERTICALLY ABOVE THE ADJACENT WALKING
 SURFACES, ADJACENT FIXED SEATING OR THE LINE CONNECTING
 THE LEADING EDGES OF THE TREADS.
  
 3B) PROVIDE COMPLIANCE WITH: 2010 FBC-B 1013.3 OPENING
 LIMITATIONS. EXCEPTION (3). AT ELEVATED WALKING
 SURFACES FOR ACCESS TO AND USE OF ELECTRICAL,
 MECHANICAL OR PLUMBING SYSTEMS OR EQUIPMENT, GUARDS
 SHALL NOT HAVE OPENINGS WHICH ALLOW PASSAGE OF A SPHERE
 21 INCHES (533 MM) IN DIAMETER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER