| Notes |
| Date |
Text |
| 2015-06-13 02:27:23 | 1) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB | | | AMEND.TO 2010 FBC SEC. 107.3.5.. | | | 2) ONLY ONE SET OF PLANS BEARS THE SEAL AND SIGNATURE | | | OF THE DESIGNER OF RECORD. SUBMIT TWO SETS OF PLANS | | | THAT BEAR THE SEAL AND SIGNATURE OF THE DESIGN | | | PROFESSIONAL OF RECORD. FL. ADMIN. CODE RULE | | | 61G15-23.002 | | | 3) SHT. C-1 - GENERAL NOTES - REFERENCE IS MADE TO THE | | | STANDARD PLUMBING CODE.THE CODE IN EFFECT IS THE 2010 | | | FLORIDA BUILDING CODE - PLUMBING. WPB AMEND.TO 2010 FBC | | | SEC. 102.2. R EVISE THE NOTE. | | | 4) SHT. D-1 - SIZE ALL SECTIONS OF THE SANITARY RISER | | | DIAGRAM.(2ND FLOOR RISER AND ALL LOOP VENTS.) WPB | | | AMEND. TO 2010 FBC SEC. 107.3.5.3. | | | 5)THE LAYOUT OF THE SANITARY RISER DOES NOT MATCH THE | | | FLOOR PLAN. THE LOCATION OF THE FIXTURES DO NOT | | | CORRELATE WITH THE FLOOR PLAN.SEE THE BATH NEAR THE | | | LAUNDRY ROOM AND THE BATH BETWEEN BEDROON #1 & #2. | | | 6) THE RISER SHOWS ONE LAVATORY FOR THE BATH BETWEEN | | | BEDROOMS # 1 & #2 AND THE FLOOR PLAN SHOWS TWO. | | | CLARIFY. | | | 7) THE WATER HEATER ON THE SECOND FLOOR REQUIRES A PAN | | | UNDERNEATH AND A PAN DRAIN THAT SHALL DISCHARGE TO THE | | | EXTERIOR. THE PAN AND PAN DRAIN SHALL COMPLY WITH 2010 | | | FBCR SEC.P2801.5 THRU P2801.5.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|