| 2015-07-24 14:45:16 | RESIDENTIAL (R3) RENOVATIONS, MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC |
| | |
| | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2 |
| | COPIES) AS REQUIRED BY SEC. M1401.3 OF 2010 |
| | FBC-RESIDENTIAL |
| | |
| | 2- EQUIPMENT LISTED ON THE MECHANICAL PLAN TO MATCH |
| | EQUIPMENT LISTED ON THE EQUIPMENT SIZING CALCULATIONS |
| | REQUIRED ON ITEM #1 ABOVE. SEC. 107.3.5.3(10) CITY |
| | AMENDMENTS. |
| | |
| | 3- INFORMATION SHOWN ON THE AIR COOLED CONDENSING UNIT |
| | SLAB MOUNTED DETAIL IS NOT LEGIBLE. REVISE AS REQUIRED. |
| | SEC. 107.2.1.4 CITY AMENDMENTS. |
| | |
| | 4- THE DESIGN CRITERIA SPECIFIED ON THE MECHANICAL |
| | PLANS IS INCORRECT. ENGINEER OF RECORD TO REVISE AS |
| | REQUIRED. SEC. R301 OF 2020 FBC-RESIDENTIAL. |
| | |
| | 5- TRANSFER GRILLS ON FIRST FLOOR MECHANICAL PLAN ARE |
| | LOCATED IN THE DOOR. THE TRANSFER GRILLS NEED TO BE |
| | LOCATED ON THE WALL NOT IN THE DOOR A SHOWN ON SECOND |
| | FLOOR MECHANICAL PLAN. REVISE AS REQUIRED. SEC. M1602.4 |
| | OF THE 200 FBC-RESIDENTIAL. |
| | |
| | 6- 1ST FLOOR MECHANICAL PLAN: CLARIFY TYPE AND SIZE OF |
| | SUPPLY AIR DUCT. IS IT FLEXIBLE OR DUCTED FIBERGLASS. |
| | FOR EXAMPLE PLANS SPECIFY 6" DIAMETER SUPPLY BUT IT'S |
| | SHOWN AS RECTANGULAR DUCT. SECOND FLOOR IS SHOWN |
| | CORRECTLY. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | SUBMIT OLD COPIES FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |