| Plan Review Notes For Permit 15050397 |
| Permit Number |
15050397 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-06 10:22:15 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. THE SIGNATURE OF | | | THE SYSTEM DESIGNER IS REQUIRED ON THE MECHANICAL | | | PLANS. FS 471.003 (2)(H) | | | | | | 2) FBC-R - M 1602.4 BALANCED AIR RETURN. THE 10" | | | TRANSFER DUCT FROM THE MASTER BEDROOM SUITE IS TOO | | | SMALL. THE DIAMETER OF THE SUPPLY AIR DUCTS ENTERING | | | THE MASTER SUITE IS 64 SQ.IN. WHICH REQUIRES A 12 | | | SQ.IN. DIAMETER TRANSFER DUCT. | | | | | | 3) FBC-R 1602.2 PROHIBITED SOURCES. RETURN AIR FOR A | | | FORCED-AIR HEATING OR COOLING SYSTEM SHALL NOT BE TAKEN | | | FROM A KITCHEN. | | | | | | 4) THE SIZE OF THE RETURN AIR GRILL IS NOT SPECIFIED ON | | | THE PLANS. FBC 107.2.1 | | | | | | 5) THE CFMS IN THE MASTER CLOSET AND BATH ROOM #2 IS | | | SPECIFIED ON THE PLANS AS 3 CFMS. IS THIS CORRECT ? FBC | | | 107.2.1 | | | | | | 6) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | | ADDRESSED. | | | | | | | | | | | | | | | | | | | | | |
|