2015-10-06 10:22:15PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE SIGNATURE OF
 THE SYSTEM DESIGNER IS REQUIRED ON THE MECHANICAL
 PLANS. FS 471.003 (2)(H)
  
 2) FBC-R - M 1602.4 BALANCED AIR RETURN. THE 10"
 TRANSFER DUCT FROM THE MASTER BEDROOM SUITE IS TOO
 SMALL. THE DIAMETER OF THE SUPPLY AIR DUCTS ENTERING
 THE MASTER SUITE IS 64 SQ.IN. WHICH REQUIRES A 12
 SQ.IN. DIAMETER TRANSFER DUCT.
  
 3) FBC-R 1602.2 PROHIBITED SOURCES. RETURN AIR FOR A
 FORCED-AIR HEATING OR COOLING SYSTEM SHALL NOT BE TAKEN
 FROM A KITCHEN.
  
 4) THE SIZE OF THE RETURN AIR GRILL IS NOT SPECIFIED ON
 THE PLANS. FBC 107.2.1
  
 5) THE CFMS IN THE MASTER CLOSET AND BATH ROOM #2 IS
 SPECIFIED ON THE PLANS AS 3 CFMS. IS THIS CORRECT ? FBC
 107.2.1
  
 6) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  
  