Plan Review Notes
Plan Review Notes For Permit 15050392
Permit Number 15050392
Review Stop B
Sequence Number 5
Notes
Date Text
2015-08-12 16:30:40FITH BUILDING REVIEW COMMENTS:
  
  
 NOTE: THE FOLLOWING COMMENTS MAY BE APPROVED WITH
 PROVISO. WAITING FOR CONTRACTOR'S CONFIRMATION ON
 PROVISO. FEES MAY APPLY.
  
 1- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 ***RESPONSE TO ARCHITECT'S E-MAIL DATED 8/11/15 (SEE
 COPY BELOW):
 NOTE ON DRAWING A201 PARTIALLY ADDRESSES THE
 REQUIREMENT. IT ONLY MENTION GUTTERS AND LEADERS. THE
 PURPOSE OF THIS CODE SECTION IS TO PROVIDE A LOT
 GRADING PLAN SHOWING HOW DIVERTING ALL THE SURFACE
 DRAINAGE TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION.
  
 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC.
 1803.6 FBC-2010.
  
 ***RESPONSE TO ARCHITECT'S E-MAIL DATED 8/11/15 (SEE
 COPY BELOW):
 MARK FROM DELCREST WILL GET THE SOIL TEST REPORT WITH
 ALL THE INFORMATION.
  
 3- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. SPECIFY
 TYPE AND NUMBER OF NAILS OR SCREWS.
  
 ***RESPONSE TO ARCHITECT'S E-MAIL DATED 8/11/15 (SEE
 COPY BELOW):
 REVISED DRAWING A801 WAS NOT SUBMITTED TO THE CITY YET.
 E-MAIL ATTACHMENT SHOWS TYPICAL 1-STORY WALL SECTION
 DETAIL D1 WITH THE FOLLOWING SPECIFICATIONS: "ENTEGRA
 FLAT ROOF TILE (NAIL W/ (2) 8D GALV RINGSHANK COIL
 NAILS PER TILE. SEE ROOFING PERMIT". ROOF TILE FLORIDA
 PRODUCT APPROVAL FL7804-R7 SUBMITTED DOESN'T HAVE ANY
 INFORMATION SHOWING THE PROPOSED FASTENING. WITHOUT THE
 ATTACHMENT RESISTANCE INFORMATION I CAN NOT VERIFY IF
 THE PROPOSED NAILS WILL MEET THE DESIGN PRESSURES OF
 SEC. R301 OF 2010 FBC-RESIDENTIAL. ARCHITECT TO PROVIDE
 CALCULATIONS SHOWING THAT THE PROPOSED NAIL-ON SYSTEM
 WILL MEET THE DESIGN CRITERIA OF SEC. R301. (NOTE:
 TYPICALLY MIAMI-DADE NOA'S LIST ALL THIS INFORMATION.
 FLORIDA PRODUCT APPROVALS DON'T. THAT'S WHY THE
 ARCHITECT NEEDS TO PROVIDE THE INFORMATION).
  
 4-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) MAHOGANY
 ENTRY DOOR SIZE AND ASSEMBLY AS SHOWN ON DOOR SCHEDULE.
  
 ***RESPONSE TO ARCHITECT'S E-MAIL DATED 8/11/15 (SEE
 COPY BELOW):
 REVISED DRAWING A202 WAS NOT SUBMITTED TO THE CITY YET.
 E-MAIL ATTACHMENT SHOWS REVISED DOOR SCHEDULE WITH
 ENTRY DOOR #102 SIZE AS FOLLOWS 3'-4" WD X 8'-0" HGT.
 PGT SERIES "FD-750" OUTSWING ALUMINUM FRENCH DOOR NOA
 14-1117.05 SUBMITTED DOESN'T COVER DOORS WITH THE WIDTH
 SPECIFIED ON THE DOOR SCHEDULE. PROVIDE NEW PRODUCT
 APPROVAL THAT COVERS THIS SIZE OR REVISE DOOR SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  
  
 JULIO,
 I WANT TO APOLOGIZE AS I AM NOT SURE WHAT IS HAPPENING
 BUT IT SEEMS YOU AREN?T GETTING THE CORRECTION INFO I
 HAVE PROVIDED ON THIS JOB.
 ATTACHED IS MY 2ND RESPONSE LETTER TO YOU FOR THE
 COMMENTS FROM 7/22/15.
 ALSO ANY SHEETS THAT WERE REVISED AND CLOUDED REGARDING
 YOUR COMMENTS BELOW
 MY RESPONSES TO YOUR COMMENTS ARE IN GREEN BELOW
 1- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL.
 FOR THE DRAINAGE PLAN I ADDED THE ROOF GUTTER/DRAINAGE
 NOTE TO SHEET A201 (SEE ATTACHED SHEET A201)
 THIS IS WHAT I HAVE DONE ON OTHER IBIS JOBS FOR SHELLEY
 FRIEFELD (SOUTHERN HOMES)
  
 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE
 INFORMATION AS REQUIRED BY SEC. 1803.6 FBC-2010.
 MARK FROM DELCREST IS TRYING TO GET THE SOIL TEST INFO
 CORRECTED.
  
 3- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC.
 107.2.1.2 CITY AMENDMENTS. SPECIFY TYPE AND NUMBER OF
 NAILS OR SCREWS.
 WE CHANGED TO NAIL DOWN ROOF ON 1ST COMMENTS AND I HAD
 ADDED THE NOTE TO ATTACH PER ROOFING PERMIT.
 I HAVE ADDED THE NAILING SPECIFIED BY THE ROOFING
 PERMIT (SEE ATTACHED SHEET A901)
  
 4-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) MAHOGANY
 ENTRY DOOR SIZE AND
 ASSEMBLY AS SHOWN ON DOOR SCHEDULE.
 MAHOGANY DOOR WAS CHANGED TO PGT FD-750 OUTSWING DOOR &
 SIDELIGHTS ON 1ST COMMENTS (SEE ATTACHED SHEET A202)
 I REVIEWED & APPROVED THE NOA FOR THIS WITH ALL THE
 OTHER SUBMITTED NOA?S.
  
 B) ROOF TILE ADHESIVE AS SPECIFIED ON DETAIL D1 ON
 SHEET A801.
  
 ROOF CHANGED TO NAIL DOWN TILE ON 1ST COMMENTS
  
 C) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON DETAIL D1 OF SHEET A801.
  
 PEEL & STICK WAS ELIMINATED ON THE 1ST COMMENTS
  
  
 GARY STOFFT
  
 - LOT 15 BP BLDG COMMENTS 02.PDF - 1501021 LOT 15 BP
 A201 FL REV02.PDF - 1501021 LOT 15 BP A202 FL REV01.PDF