| Plan Review Notes For Permit 15050392 |
| Permit Number |
15050392 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-08-10 12:46:47 | | | | NOTE: THE FOLLOWING COMMENTS MAY BE APPROVED WITH | | | PROVISO. WAITING FOR CONTRACTOR'S CONFIRMATION ON | | | PROVISO. FEES MAY APPLY. | | | | | | FOURTH BUILDING REVIEW COMMENTS: | | | | | | 1- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010 | | | FBC-RESIDENTIAL. | | | 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST | | | REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC. | | | 1803.6 FBC-2010. | | | 3- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS | | | REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. SPECIFY | | | TYPE AND NUMBER OF NAILS OR SCREWS. | | | 4-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) MAHOGANY | | | ENTRY DOOR SIZE AND ASSEMBLY AS SHOWN ON DOOR SCHEDULE. | | | B) ROOF TILE ADHESIVE AS SPECIFIED ON DETAIL D1 ON | | | SHEET A801. C) PEEL & STICK CONCRETE ROOF TILE | | | UNDERLAYMENT AS SPECIFIED ON DETAIL D1 OF SHEET A801. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | |
|