Plan Review Notes
Plan Review Notes For Permit 15050392
Permit Number 15050392
Review Stop B
Sequence Number 3
Notes
Date Text
2015-07-30 10:51:58 
  
 *****NOTES:
 A) THE COMMENTS BELOW ARE BASED ONLY ON THE
 RE-SUBMITTAL PACKAGE I HAVE IN FRONT OF ME TO DO THE
 REVIEW. WHATEVER I AM ASKING FOR IS BECAUSE IS NOT
 HERE.
  
 B) I ALSO NOTICED THAT THERE IS ONLY ONE SET OF PRODUCT
 APPROVALS IN THIS PACKAGE: THE OTHER SET OF PRODUCT
 APPROVALS WAS SIGNED OUT ON 7/24/15. THE FOLLOWING ARE
 THE NOA'S THAT WE HAVE IN THIS PACKAGE: GARAGE DOOR NOA
 12-0517.16, FRENCH DOORS NOA 14-1117.05, SLIDING GLASS
 DOORS NOA 14-0128.11, MULLIONS NOA 14-1105.01, FIXED
 WINDOWS NOA 13-0502.03 AND HORIZONTAL SLIDING WINDOWS
 NOA 11-1114.04. THEREFORE, WE NEED THE SECOND SET
 RE-SUBMITTED. THE PRODUCT APPROVALS THAT WERE SIGNED
 OUT AND THE PRODUCT APPROVALS LISTED BELOW NEED TO BE
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD.
  
  
  
 NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC.
 1803.6 FBC-2010. (REPEAT COMMENT. NOT ADDRESSED).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) MAHOGANY ENTRY DOOR SIZE AND ASSEMBLY AS SHOWN ON
 PLANS. (REPEAT COMMENT. NOT ADDRESSED).
 B) ROOF TILE. (REPEAT COMMENT. NOT ADDRESSED)
 C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVE. (REPEAT COMMENT. NOT ADDRESSED)
 D) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON DETAIL D1 OF SHEET A801. (REPEAT COMMENT.
 NOT ADDRESSED)
 E) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED)
  
 4- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 IN WRITING (NOT SIGNING AND SEALING) AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: REVIEW AND
 APPROVE ALSO ALL PRODUCT APPROVALS THAT WERE ALREADY
 SUBMITTED. (REPEAT COMMENT. NOT ADDRESSED)
  
 5- CLARIFY WHY THERE IS ANOTHER ENGINEER (NOT THE
 ENGINEER OF RECORD) SUBMITTING A "WINDOW & DOOR
 INSTALLATION?. ALSO, THE DESIGN PRESSURES ARE DIFFERENT
 THAN THOSE SPECIFIED BY THE ENGINEER OF RECORD. WHICH
 ONE IS THE ONE WITH THE CORRECT DESIGN PRESSURES? AND,
 THE SLIDING GLASS DOORS MULLIONS ARE NOT CLEAR
 (HORIZONTAL OR VERTICAL?). SEC. 107.2.1 CITY
 AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED)
  
 6- CLEARLY IDENTIFY MULLION SIZE FOR OPENINGS #108,
 #109 AND #110 TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. CLEARLY
 IDENTIFY THE VERTICAL AND HORIZONTAL MULLIONS. (REPEAT
 COMMENT. NOT ADDRESSED)
  
 7- TRUSS PACKAGE: (REPEAT COMMENT. NOT ADDRESSED)
 A) TRUSS PACKAGE DOESN'T COMPLY WITH SEC. 61G15-31.003.
 THE COVER PAGE IS MISSING THE ENGINEER OF RECORD
 INFORMATION AND EACH INDIVIDUAL TRUSS DRAWING NEEDS THE
 TRUSS ENGINEER'S INFORMATION.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE BEFORE SUBMITTAL.
  
 NOTE: TRUSS PACKAGE DOESN'T NEED TO BE RE-SUBMITTED TO
 THIS OFFICE NOW. ON RESIDENTIAL PROJECTS, THE
 CONTRACTOR MAY DELIVER THE REVISED TRUSS PACKAGE TO THE
 INSPECTOR AT TIME OF FRAMING INSPECTION.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE REVIEW PROCESS. (REPEAT COMMENT.
 RESPONSE LETTER NOT SUBMITTED. REVIEW TOOK LONGER
 LOOKING FOR THE INFORMATION).
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT OLD COPY FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]