 ****NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. COMMENTS
 BELOW MAY BE ADDRESSED AFTER PERMIT IS PRINTED.
 REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF THE
 PROVISO OPTION IS ACCEPTABLE. OTHERWISE, RESUBMIT
 REQUIRED INFORMATION BEFORE ISSUING PERMIT.
  
  
 NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
  
 1- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010
 FBC-RESIDENTIAL.
 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST
 REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC.
 1803.6 FBC-2010.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC RULE 9N-3 FOR:
 A) MAHOGANY ENTRY DOOR SIZE AND ASSEMBLY AS SHOWN ON
 PLANS. (REPEAT COMMENT. NOT ADDRESSED).
 B) ROOF TILE. (REPEAT COMMENT. NOT ADDRESSED)
 C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVE. (REPEAT COMMENT. NOT ADDRESSED)
 D) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON DETAIL D1 OF SHEET A801. (REPEAT COMMENT.
 NOT ADDRESSED)
 E) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED)
  
 4- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 IN WRITING (NOT SIGNING AND SEALING) AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: REVIEW AND
 APPROVE ALSO ALL PRODUCT APPROVALS THAT WERE ALREADY
 SUBMITTED. (REPEAT COMMENT. NOT ADDRESSED)
  
 5- CLARIFY WHY THERE IS ANOTHER ENGINEER (NOT THE
 ENGINEER OF RECORD) SUBMITTING A "WINDOW & DOOR
 INSTALLATION?. ALSO, THE DESIGN PRESSURES ARE DIFFERENT
 THAN THOSE SPECIFIED BY THE ENGINEER OF RECORD. WHICH
 ONE IS THE ONE WITH THE CORRECT DESIGN PRESSURES? AND,
 THE SLIDING GLASS DOORS MULLIONS ARE NOT CLEAR
 (HORIZONTAL OR VERTICAL?). SEC. 107.2.1 CITY
 AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED)
  
 6- CLEARLY IDENTIFY MULLION SIZE FOR OPENINGS #108,
 #109 AND #110 TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. CLEARLY
 IDENTIFY THE VERTICAL AND HORIZONTAL MULLIONS. (REPEAT
 COMMENT. NOT ADDRESSED)
  
 7- TRUSS PACKAGE: (REPEAT COMMENT. NOT ADDRESSED)
 A) TRUSS PACKAGE DOESN'T COMPLY WITH SEC. 61G15-31.003.
 THE COVER PAGE IS MISSING THE ENGINEER OF RECORD
 INFORMATION AND EACH INDIVIDUAL TRUSS DRAWING NEEDS THE
 TRUSS ENGINEER'S INFORMATION.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE BEFORE SUBMITTAL.
  
 NOTE: TRUSS PACKAGE DOESN'T NEED TO BE RE-SUBMITTED TO
 THIS OFFICE NOW. ON RESIDENTIAL PROJECTS, THE
 CONTRACTOR MAY DELIVER THE REVISED TRUSS PACKAGE TO THE
 INSPECTOR AT TIME OF FRAMING INSPECTION.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE REVIEW PROCESS. (REPEAT COMMENT.
 RESPONSE LETTER NOT SUBMITTED. REVIEW TOOK LONGER
 LOOKING FOR THE INFORMATION).
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT OLD COPY FOR REFERENCE.
  