| | ****NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. COMMENTS |
| | BELOW MAY BE ADDRESSED AFTER PERMIT IS PRINTED. |
| | REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF THE |
| | PROVISO OPTION IS ACCEPTABLE. OTHERWISE, RESUBMIT |
| | REQUIRED INFORMATION BEFORE ISSUING PERMIT. |
| | |
| | |
| | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | |
| | 1- PROVIDE DRAINAGE PLAN. SEC R401.3 OF 2010 |
| | FBC-RESIDENTIAL. |
| | 2- SOIL TEST REPORT IS INCOMPLETE. PROVIDE SOIL TEST |
| | REPORT WITH ALL THE INFORMATION AS REQUIRED BY SEC. |
| | 1803.6 FBC-2010. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC RULE 9N-3 FOR: |
| | A) MAHOGANY ENTRY DOOR SIZE AND ASSEMBLY AS SHOWN ON |
| | PLANS. (REPEAT COMMENT. NOT ADDRESSED). |
| | B) ROOF TILE. (REPEAT COMMENT. NOT ADDRESSED) |
| | C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL |
| | FOR LISTED ADHESIVE. (REPEAT COMMENT. NOT ADDRESSED) |
| | D) PEEL & STICK CONCRETE ROOF TILE UNDERLAYMENT AS |
| | SPECIFIED ON DETAIL D1 OF SHEET A801. (REPEAT COMMENT. |
| | NOT ADDRESSED) |
| | E) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT |
| | COMMENT. NOT ADDRESSED) |
| | |
| | 4- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS |
| | IN WRITING (NOT SIGNING AND SEALING) AS REQUIRED BY |
| | SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: REVIEW AND |
| | APPROVE ALSO ALL PRODUCT APPROVALS THAT WERE ALREADY |
| | SUBMITTED. (REPEAT COMMENT. NOT ADDRESSED) |
| | |
| | 5- CLARIFY WHY THERE IS ANOTHER ENGINEER (NOT THE |
| | ENGINEER OF RECORD) SUBMITTING A "WINDOW & DOOR |
| | INSTALLATION?. ALSO, THE DESIGN PRESSURES ARE DIFFERENT |
| | THAN THOSE SPECIFIED BY THE ENGINEER OF RECORD. WHICH |
| | ONE IS THE ONE WITH THE CORRECT DESIGN PRESSURES? AND, |
| | THE SLIDING GLASS DOORS MULLIONS ARE NOT CLEAR |
| | (HORIZONTAL OR VERTICAL?). SEC. 107.2.1 CITY |
| | AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED) |
| | |
| | 6- CLEARLY IDENTIFY MULLION SIZE FOR OPENINGS #108, |
| | #109 AND #110 TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL. CLEARLY |
| | IDENTIFY THE VERTICAL AND HORIZONTAL MULLIONS. (REPEAT |
| | COMMENT. NOT ADDRESSED) |
| | |
| | 7- TRUSS PACKAGE: (REPEAT COMMENT. NOT ADDRESSED) |
| | A) TRUSS PACKAGE DOESN'T COMPLY WITH SEC. 61G15-31.003. |
| | THE COVER PAGE IS MISSING THE ENGINEER OF RECORD |
| | INFORMATION AND EACH INDIVIDUAL TRUSS DRAWING NEEDS THE |
| | TRUSS ENGINEER'S INFORMATION. |
| | |
| | B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS |
| | PACKAGE BEFORE SUBMITTAL. |
| | |
| | NOTE: TRUSS PACKAGE DOESN'T NEED TO BE RE-SUBMITTED TO |
| | THIS OFFICE NOW. ON RESIDENTIAL PROJECTS, THE |
| | CONTRACTOR MAY DELIVER THE REVISED TRUSS PACKAGE TO THE |
| | INSPECTOR AT TIME OF FRAMING INSPECTION. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE REVIEW PROCESS. (REPEAT COMMENT. |
| | RESPONSE LETTER NOT SUBMITTED. REVIEW TOOK LONGER |
| | LOOKING FOR THE INFORMATION). |
| | ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | SUBMITT OLD COPY FOR REFERENCE. |
| | |