| 2015-07-02 10:36:36 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. |
| | |
| | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | 1. ELECTRICAL NOTES, GENERAL #6, PLEASE NOTE THAT ROMEX |
| | IS A BRAND NAME AND NOT A CABLE TYPE. CORRECT THE NOTE |
| | TO REFLECT THE CABLE TYPE INTENDED FOR USE. |
| | 2. ELECTRICAL NOTES, GENERAL #13, ANY CONDUCTOR EXPOSED |
| | TO WET LOCATIONS, REGARDLESS OF SIZE SHALL BE LISTED |
| | ACCORDINGLY. |
| | 3. ELECTRICAL NOTES, OUTLETS #3, TAMPER-RESISTANT |
| | OUTLETS REQUIREMENTS IS AT NEC 406.11 AND NOT AT NEC |
| | 210.52. CORRECT NOTE ACCORDINGLY. |
| | 4. ELECTRICAL NOTES, SMOKE DETECTOR #2, SHALL BE |
| | AMENDED TO INCLUDE THE TIP OF A CEILING/PADDLE FAN |
| | BLADE. |
| | 5. REVISE THE ELECTRICAL RISER DIAGRAM TO INCLUDE THE |
| | INTER-SYSTEM BONDING TERMINAL REQUIRED BY NEC 520.94 |
| | 6. IF AHU #1 IN GARAGE 1 IS TO BE INSIDE THE ATTIC OR |
| | ON A PLATFORM, THE REQUIREMENTS OF NEC 110.33(B) SHALL |
| | APPLY. THIS MAY ALSO APPLY TO AHU #2 IN GARAGE 2. |
| | 7. FBC-R SECTION 315 STATES THAT YOU SHALL HAVE CARBON |
| | MONOXIDE (CO) DETECTION WITHIN 10? OF EVERY SLEEPING |
| | AREA. THEREFORE, THOSE DETECTORS OUTSIDE THE BEDROOM |
| | USED TO COMPLY W/FBC-R 314 SHALL BE COMBINATION TYPE |
| | DETECTORS. |
| | 8. NEC 210.52(E)(1) REQUIRES THAT THERE BE A GFCI |
| | PROTECTED RECEPTACLE INSTALLED AT THE FRONT & BACK OF |
| | THE RESIDENCE. |
| | 9. NEC 406.8 REQUIRES THAT ALL RECEPTACLES INSTALLED IN |
| | WET LOCATIONS NOT ONLY HAVE AN IN-USE TYPE COVE BUT |
| | ALSO BE LISTED AS WEATHER RESISTANT ?WR?. |
| | 10. FBC-ENERGY CONSERVATION REQUIRES THAT AT LEAST 50% |
| | OF ALL LAMPS IN PERMANENTLY INSTALLED FIXTURES BE |
| | HIGH-EFFICIENCY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |