| Notes |
| Date |
Text |
| 2015-05-13 14:48:20 | RESIDENTIAL (R2) ALTERATION, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- SOUND INSULATION MATERIAL SUBMITTED: | | | A) PROVIDE TWO COPIES OF THE FLAME SPREAD INDEX AND | | | SMOKE DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM | | | E 84 OR UL 723 AS REQUIRED BY SEC. 719.1 OF 2010 | | | FBC-BUILDING. | | | | | | B) PROVIDE TWO COPIES OF THE SOUND TRANSMISSION CLASS | | | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS | | | REQUIRED BY SEC. 1207.2 OF 2010 FBC_BUILDING. | | | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE | | | ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT | | | ACOUSTICAL CEILING. | | | | | | C) PROVIDE TWO COPIES OF THE IMPACT INSULATION CLASS | | | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS | | | REQUIRED BY SEC. 1207.3 OF 2010 FBC_BUILDING. | | | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE | | | ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT | | | ACOUSTICAL CEILING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|