Plan Review Notes
Plan Review Notes For Permit 15050391
Permit Number 15050391
Review Stop B
Sequence Number 1
Notes
Date Text
2015-05-13 14:48:20RESIDENTIAL (R2) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- SOUND INSULATION MATERIAL SUBMITTED:
 A) PROVIDE TWO COPIES OF THE FLAME SPREAD INDEX AND
 SMOKE DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM
 E 84 OR UL 723 AS REQUIRED BY SEC. 719.1 OF 2010
 FBC-BUILDING.
  
 B) PROVIDE TWO COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF 2010 FBC_BUILDING.
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
 C) PROVIDE TWO COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF 2010 FBC_BUILDING.
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  