Plan Review Notes
Plan Review Notes For Permit 15050383
Permit Number 15050383
Review Stop M
Sequence Number 1
Notes
Date Text
2015-05-18 18:24:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) THE REVISED PLANS ARE MISSING INFORMATION THAT WAS
 PROVIDED ON THE APPROVED PLANS. FBC 107.2.1
  
 3) THE PLANS FROM THE FLORIDA LICENSED ARCHITECT CAN
 NOT BE COPIED AND MODIFIED BY ANYONE ELSE WITHOUT THEIR
 WRITTEN PERMISSION. FS 481
  
 4) REVISIONS TO THE APPROVED PLANS ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE DESIGNER OF RECORD WHICH IS
 THE ARCHITECT IN THIS INSTANCE. FS 481
  
 5) IF THE A/C CONTRACTOR WISHES TO BECOME THE DESIGNER
 OF RECORD FOR THIS PROJECT, HE WILL HAVE TO SUBMIT A
 NOTARIZED LETTER STATING SUCH AND SUBMIT HIS OWN
 DRAWINGS FOR REVIEW AS ALLOWED BY FS 471.003 (2) (H)
  
  
  
  