2015-05-12 05:20:381) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED
 PER FBC- FUEL GAS SEC.301.3.
 2) IS THE WATER HEATER A STORAGE TANK OR TANKLESS?
 INDICATE SUCH ON THE GAS RISER. IF TANKLESS, A SEPARATE
 ELECTRIC PERMIT WILL BE REQUIRED AND GAS/PLUMBING
 INSPECTIONS WILL BE PLACED ON HOLD UNTIL AN ELECTRIC
 PERMIT APPLICATION AND PLANS ARE SUBMITTED, REVIEWED,
 APPROVED AND A PERMIT ISSUED.
 3) SUBMIT CALCULATIONS FOR COMBUSTION AIR IN ACCORDANCE
 WITH 2010 FBC-FUEL GAS SEC.304.1.
 4) SUBMIT VENT DETAILS FOR ALL APPLIANCES.2010 FBC-FUEL
 GAS SEC.501.2, 502.1, 503.1.
 5) THE TABLE YOU SUBMITTED FOR THE CSST NOTES A
 PRESSURE DROP OF 3.0 IN. WATER COLUMN. THERE IS NO
 CORRESPONDING TABLE FOR THIS PRESSURE DROP FOR METALLIC
 (GALV.) PIPE. PLEASE CONFIRM THAT THIS IS THE CORRECT
 TABLE AND SUBMIT COPY OF SIZING TABLE FOR THE METALLIC
 PIPE.
 6) IF THE TABLE FOR THE METALLIC PIPE IS 402.4 (2), THE
 MAX.BTU LOAD FOR 3/4" PIPE AT 80 FEET IS 117,000. THE
 MIN. PIPE SIZE AT THE METER WILL HAVE TO BE 1".
 7) SIZE THE BRANCH LINE TO THE WATER HEATER. WPB AMEND.
 TO 2010 FBC SEC. 107.3.5.3.
 8) SIZE THE LINE AT THE METER. WPB AMEND. TO 2010 FBC
 SEC. 107.3.5.3.
 9) THE DRAWING SHOWS THE EHD FOR THE CSST CHANGING FROM
 23 TO 25 . IS THIS CORRECT? CLARIFY.
  