Plan Review Notes
Plan Review Notes For Permit 15050356
Permit Number 15050356
Review Stop B
Sequence Number 2
Notes
Date Text
2015-07-24 12:45:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. REVISE PLAN TO INCORPORATE CHANGES TO THE STRUCTURAL
 DESIGN, FBC 2010 RESIDENTIAL 301.
  
 2ND REVIEW, NOT ADDRESSED. STRUCTURAL CHANGES WERE MADE
 IN INK. INCORPORATE THESE CHANGES INTO A SIGNED AND
 SEALED PLAN, FBC 2010 RESIDENTIAL 301, FBC 107. THE
 STRUCTURAL CHANGES REDUCE THE SIZE OF THE COLUMNS.
  
 2. REVISE PLAN TO INCORPORATE THE "FLORIDA GLASS" ROOF
 AND WALLS, FBC 2010 RESIDENTIAL 301, FBC 107.
  
 2ND REVIEW, NOT ADDRESSED. A LETTER WAS PROVIDED WHICH
 STATES THAT THE PRODUCT IS ACCEPTABLE FOR USE AS
 INDICATED ON THE PLANS. THE PLANS REFER TO 20X20
 SCREEN. MY UNDERSTANDING OF THE FLORIDA GLASS PRODUCT
 IS THAT IT IS NOT 20X20 SCREEN; IT IS SCREEN WHICH IS
 VINYL LAMINATED.
  
 NEW COMMENTS:
  
 3. THE LETTER FROM THE ARCHITECT STATES TWO THINGS:
  
 A. FLORIDA GLASS IS A VINYL LAMINATED SCREEN WHICH IS
 INSTALLED SO THAT IT WILL BREAK AWAY IN HIGH WINDS, AND
  
 B. IN THE EVENT OF A STORM WHICH EXCEEDS 75MPH, THE
 PANELS WOULD NEED TO BE REMOVED.
  
 THE PLAN DOES NOT DEPICT PANELS. NOTHING ON THE PLAN
 INDICATES THAT THE SCREEN IS TO BE REMOVED, OR THAT IT
 WILL AUTOMATICALLY BREAK AWAY.
  
 IS THIS A VINYL REMOVABLE PANEL FBC 2010 RESIDENTIAL
 2002.3.3? IF THIS IS THE CASE, REVISE PLAN TO PROVIDE A
 DETAIL FOR THE REMOVABLE PANELS, REVISE PLAN TO INCLUDE
 THE SIGNAGE REQUIRED.
  
 PER ARCHITECT, THE PANELS ARE ALSO REQUIRED TO BE
 REMOVED. PLAN DOES NOT SHOW REMOVABLE PANELS. IT IS NOT
 CLEAR WHETHER THIS IS DESIGNED TO BREAK AWAY OR TO BE
 REMOVED. ALSO THERE IS A REFERENCE TO A HVHZ CODE
 SECTION, BUT PALM BEACH COUNTY IS NOT IN THE HVHZ.
 DESIGN AND CODE COMPLIANCE ARE NOT CLEARLY
 DEMONSTRATED.
  
 4. DUE TO THE ADDITIONAL WEIGHT OF THE FLORIDA GLASS,
 AS WELL AS THE USE OF WHAT APPEARS TO BE AN OPAQUE
 PRODUCT ON THE ROOF (IT APPEARS THAT WATER AND WIND
 WILL NOT PENETRATE THIS BRAND OF VINYL COATED SCREEN),
 PROVIDE CALCULATIONS TO SHOW THAT THE ROOF AND WALL
 MEMBERS CAN ACCOMODATE THE LOADS.
  
 ALSO, TO BE CLEAR AS TO DESIGN INTENT, REVISE GENERAL
 NOTES WIND INFORMATION TO INCLUDE ENCLOSURE
 CLASSIFICATION (OPEN, PARTIALLY ENCLOSED, OR ENCLOSED).
  
 5. IF THIS PRODUCT IS REQUIRED TO BE REMOVED BY THE
 HOMEOWNER, PROVIDE A LETTER FROM THE HOMEOWNER WHICH
 OUTLINES THE PLAN AS TO HOW THIS WILL BE ACCOMPLISHED.
 THIS IS BEING REQUIRED DUE TO THE UNUSUAL INSTALLATION
 OF THIS PRODUCT ON THE ROOF (TYPICALLY THIS IS USED ON
 THE BOTTOM PORTION OF SCREEN WALLS).
  
 6. THE PLAN SPECIFIES 20X20 MESH MAX SCREEN. REVISE
 THIS TO SPECIFY THE PRODUCT PROPOSED (FLORIDA GLASS) OR
 REVISE THE APPLICATION TO BE CONSISTENT WITH THE PLAN
 (20X20 MAX SCREEN). IF WATER CANNOT PENETRATE THIS
 PRODUCT, IT APPEARS THAT IT DOES NOT MEET THE 20X20
 MESH MAX REQUIREMENT WHICH WAS SPECIFIED BY THE
 ARCHITECT.
  
 NOT ENOUGH INFORMATION (OR CONFLICTING INFORMATION
 PROVIDED) TO DETERMINE CODE COMPLIANCE.
  
 7. SEE FLORIDA STATUTE 553.80(2)(C):
  
 (B) WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS'
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 8. WHEN RESUBMITTING, CONTRACTOR NAME SHOULD BE THE
 COMPANY NAME. DOCUMENTS ARE FILED BY THE LEGAL COMPANY
 NAME WHO IS THE APPLICANT. FAILURE TO DO SO MAY RESULT
 IN PLANS BEING MISFILED. I HAVE REVISED YOUR RECENT
 RESUBMITTAL FORM TO HAVE "G&D SCREEN" AS CONTRACTOR.
  
  
  