| | PROJECT: KITCHEN RENNOVATION |
| | PERMIT#: 15050330 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) INSTAL SMOKE DETECTORS WHERE REQUIRED. SEE FBC-R |
| | 314-315 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | FBC-RESIDENTIAL 314 AND 315. |
| | |
| | 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 3) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL. |
| | (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS |
| | SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (1) |
| | BATHROOMS. |
| | |
| | 4) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| | BASIN. |
| | |
| | 5) NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER |
| | |
| | 6) FBC-E 708.3 RESIDENTIAL OCCUPANCIES. |
| | IN GROUP R-2, R-3, AND R-4 OCCUPANCIES AND BUILDINGS |
| | REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| | THE REQUIREMENTS OF SECTIONS 708.3.1 THROUGH 708.3.7 |
| | SHALL BE APPLICABLE ONLY TO WORK AREAS LOCATED WITHIN A |
| | DWELLING UNIT. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |