 PROJECT: KITCHEN RENNOVATION
 PERMIT#: 15050330
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) INSTAL SMOKE DETECTORS WHERE REQUIRED. SEE FBC-R
 314-315 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315.
  
 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 3) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL.
 (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS
 SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (1)
 BATHROOMS.
  
 4) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN.
  
 5) NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER
  
 6) FBC-E 708.3 RESIDENTIAL OCCUPANCIES.
 IN GROUP R-2, R-3, AND R-4 OCCUPANCIES AND BUILDINGS
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 THE REQUIREMENTS OF SECTIONS 708.3.1 THROUGH 708.3.7
 SHALL BE APPLICABLE ONLY TO WORK AREAS LOCATED WITHIN A
 DWELLING UNIT.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  