| 2015-05-13 11:10:23 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15050319 |
| | ADD: 600 S. DIXIE HWY SUITE # 737 |
| | CONT: CAPITAL CARPET & TILE |
| | TEL: ( 561)439-4500 |
| | E-MAIL: ALLENB@CAPITALCARPETAND TILE.COM |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. MAY 13/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS ARE NOT LEGIBLE MUST MEET DRAFTMAN |
| | QUALITY. 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING |
| | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| | MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| | |
| | 2) PLEASE PROVIDE THE BUILDING TYPE CRITEIA PER 2010 |
| | FBC-B TABLE 503. PLEASE ALSO PROVIDE THE SLAB |
| | THICKNESS. |
| | |
| | 2) THE SUBMITTED TESTING WAS COMPLETED WITH A DROPPED |
| | CEILING. THE FOLLOWING CODE SECTIONS WILL NEED TO SHOW |
| | CODE COMPLIANCE; |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION |
| | |
| | 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | TYPE III-TYPE V CONSTRUCTION: |
| | 719.2 CONCEALED INSTALLATION. |
| | INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| | BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| | |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 703.4 NONCOMBUSTIBILITY TESTS. |
| | THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| | SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| | MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| | 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| | ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| | CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| | MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| | BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| | INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| | LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| | AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| | |
| | 703.4.1 ELEMENTARY MATERIALS. |
| | MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| | IN ACCORDANCE WITH ASTM E 136. |
| | |
| | 703.4.2 COMPOSITE MATERIALS. |
| | MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| | MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| | MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 SHALL BE ACCEPTABLE AS |
| | NONCOMBUSTIBLE MATERIALS. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |