| 2015-06-24 11:42:38 | 6/24/2015 |
| | PROJECT: THE BRISTOL 1100 S. FLAGLER |
| | PERMIT#: 15050292 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW FOUNDATION ONLY |
| | ACTION: DENIED |
| | |
| | THERE ARE NO ELECTRICAL PLANS OR SPECIFICATIONS |
| | INCLUDED WITH THIS SUBMITTAL. REVISE YOUR PLANS IN |
| | RESPONSE TO THE FOLLOWING REVIEW COMMENTS: |
| | |
| | 1) AS A FOUNDATION ONLY PERMIT THE MINIMUM PLAN REVIEW |
| | CRITERIA SHALL INCLUDE BUT NOT BE LIMITED TO AN |
| | ELECTRICAL GOUNDING ELECTRODE SYSTEM DESIGN DETAIL PER |
| | THE NEC ARTICLE 250. SEE NEC 250.30(7) AND 250.50 AND |
| | 250.52 |
| | |
| | 2) PG. MEP INDICATES AN FPL DUCT BANK BUT DOES NOT |
| | INDICATE ANY UNDERGROUND CONDUITS THAT MAY BE AFFECTED |
| | BY THE INSTALLATION OF THE FOUNDATION PILES OR FOOTINGS |
| | SUCH AS ON SITE GERERATOR POWER FOR EMERGENCY POWER |
| | LOADS OR STANDBY POWER LOADS PER FBC 403.7, 403.8 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |