| Date |
Text |
| 2015-06-13 10:31:54 | THE BRISTOL |
| | BUILDING PLAN REVIEW |
| | W. P. B. FOUNDATION PERMIT: 15050292 |
| | ADD: 1100 S. FLAGLER DR. |
| | CONT: SUFFOLK |
| | TEL: ( 561)832-1616 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | 2010 FLORIDA BUILDING CODE W * 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS |
| | ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. JUNE 13/2015 |
| | ACTION: DENIED |
| | |
| | 1) NOTICE AT RISK, THIS PERMIT IS FOR A FOUNDATION |
| | ONLY, PLEASE PROVIDE AN APPENDIX TO THE PERMIT |
| | APPLICATION, DESCRIPTION OF WORK, AS TO WHAT WORK IS TO |
| | BE ACCOMPLISHED UNDER THIS FOUNDATION PERMIT. THE CITY |
| | CONSIDERS A FOUNDATION PERMIT ANY WORK TO BE COMPLETED |
| | UNTIL THE BUILDING LEVEL IS EVEN WITH GRADE. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.3.3. THE BUILDING |
| | OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE |
| | CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A |
| | BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS |
| | FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN |
| | SUBMITTED, PROVIDED THAT ADEQUATE INFORMATION AND |
| | DETAILED STATEMENTS HAVE BEEN FILED COMPLYING WITH |
| | PERTINENT REQUIREMENTS OF THIS CODE. THE HOLDER OF SUCH |
| | PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING |
| | OR STRUCTURE SHALL PROCEED AT THE HOLDER?S OWN RISK |
| | WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT |
| | A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED. |
| | |
| | 2) NOTICE ONLY; THE CITY OF WEST PALM BEACH ART IN |
| | PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY |
| | REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE |
| | PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE |
| | TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $500,000. PER CITY OF WEST PALM BEACH |
| | ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE |
| | OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| | |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | |
| | 3) FLOOD ZONE CERTIFICATES |
| | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31/2015 |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 4) THERE ARE SEVERAL DOCUMENTS THAT HAVE BEEN SUBMITTED |
| | IN THE SUPPORTING DOCUMENT FILE, NONE OF THESE FILES |
| | INDICATE THAT THE ARCHITECT OF RECORD HAS REVIEWED THEM |
| | THERE IS NO SHOP DRAWING STAMP OF APPROVAL WITH |
| | APPROVAL OR APPROVED AS NOTED. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | 61G1-23.015 RESPONSIBLE SUPERVISING CONTROL OVER |
| | ARCHITECTURAL PRACTICE OUTSIDE OF THE ARCHITECTS? |
| | OFFICE. |
| | |
| | 5) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| | ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 5A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | FORMS WERE SENT TO: [email protected] AT SAT. JUNE |
| | 13/ 2015 08:30 AM |
| | |
| | 5C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 5D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 5E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 5F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE |
| | E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED, |
| | THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED |
| | AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, |
| | TWO SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) |
| | FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK |
| | & WHITE.. |
| | |
| | 5G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 5H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | |
| | 6) PLEASE SHOW HOW SLOPE LIMITS WILL BE ACHIEVED. 2010 |
| | FBC-B 3304.1.1 SLOPE LIMITS. SLOPES FOR PERMANENT FILL |
| | SHALL NOT BE STEEPER THAN ONE UNIT VERTICAL IN TWO |
| | UNITS HORIZONTAL (50-PERCENT SLOPE). CUT SLOPES FOR |
| | PERMANENT EXCAVATIONS SHALL NOT BE STEEPER THAN ONE |
| | UNIT VERTICAL IN TWO UNITS HORIZONTAL (50-PERCENT |
| | SLOPE). DEVIATION FROM THE FOREGOING LIMITATIONS FOR |
| | CUT SLOPES SHALL BE PERMITTED ONLY UPON THE |
| | PRESENTATION OF A SOIL INVESTIGATION REPORT ACCEPTABLE |
| | TO THE BUILDING OFFICIAL. |
| | |
| | 7) WHEN EXCAVATING WILL THE EXCESS SOILS BE STORED ON |
| | SITE?2010 FBC-B 3304.1.2 SURCHARGE. NO FILL OR OTHER |
| | SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY |
| | BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE |
| | IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED |
| | BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR |
| | FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION |
| | SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED |
| | AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER |
| | MOVEMENT. |
| | |
| | 8) PLEASE PROVIDE COMPLIANCE WITH: POLLUTION PREVENTION |
| | PLAN. 2010 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING |
| | PUBLIC AND PRIVATE PROPERTY SHALL BE PROTECTED FROM |
| | DAMAGE DURING CONSTRUCTION, REMODELING AND DEMOLITION |
| | WORK. PROVISIONS SHALL BE MADE TO CONTROL WATER RUNOFF |
| | AND EROSION DURING CONSTRUCTION OR DEMOLITION |
| | ACTIVITIES. THE PERSON MAKING OR CAUSING AN EXCAVATION |
| | TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO THE OWNERS |
| | OF ADJOINING BUILDINGS ADVISING THEM THAT THE |
| | EXCAVATION IS TO BE MADE AND THAT THE ADJOINING |
| | BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL |
| | BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE |
| | SCHEDULED STARTING DATE OF THE EXCAVATION. |
| | 109.3.10 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ. |
| | FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | 9)PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B 3303.5 |
| | WATER ACCUMULATION. PROVISION SHALL BE MADE TO PREVENT |
| | THE ACCUMULATION OF WATER OR DAMAGE TO ANY FOUNDATIONS |
| | ON THE PREMISES OR THE ADJOINING PROPERTY. |
| | |
| | 10)FBC-B 3306.9 ADJACENT TO EXCAVATIONS. EVERY |
| | EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR LESS |
| | FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A |
| | BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE |
| | LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT |
| | LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE |
| | BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE |
| | STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN |
| | CHAPTER 16. |
| | 11) PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE |
| | PROVIDE COMPLIANCE WITH: FBC-B 3306.5 BARRIERS. |
| | BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN |
| | HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY |
| | NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE |
| | ENTIRE LENGTH OF THE CONSTRUCTION SITE. |
| | 12) 2010 FBC-B [F] 3309.1 WHERE REQUIRED. ALL |
| | STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED WITH |
| | NOT LESS THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER |
| | IN ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS |
| | THAN ORDINARY HAZARD AS FOLLOWS: |
| | 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| | COMBUSTIBLE MATERIALS HAVE ACCUMULATED. |
| | 2. IN EVERY STORAGE AND CONSTRUCTION SHED. |
| | 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| | PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| | STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| | 9F) FBC-B 3309.2 FIRE HAZARDS. |
| | THE PROVISIONS OF THIS CODE AND THE FLORIDA FIRE |
| | PREVENTION CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD |
| | AGAINST ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION |
| | OPERATIONS. |
| | |
| | 13) [F] 3311.1 WHERE REQUIRED. IN BUILDINGS REQUIRED TO |
| | HAVE STANDPIPES BY SECTION 905.3.1, NOT LESS THAN ONE |
| | STANDPIPE SHALL BE PROVIDED FOR USE DURING |
| | CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED WHEN |
| | THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40 FEET |
| | (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF FIRE |
| | DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE |
| | PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT |
| | ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH |
| | STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES |
| | TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF |
| | CONSTRUCTION HAVING SECURED DECKING OR FLOORING. |
| | 14) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR |
| | SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS |
| | WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED |
| | SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN |
| | ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO |
| | VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE |
| | PURSUANT TO SECTION 113 OF THIS CHAPTER. |
| | 15) ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR |
| | BUILDINGS) THAT ARE GOING TO HAVE MEETING IN THEM WILL |
| | BE REQUIRED TO GET A PERMIT, 102.2( E ) MOBILE OR |
| | MODULAR STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT |
| | THAT THE PROVISIONS OF PART V (SECTION 553.501-553.513, |
| | FLORIDA STATUTES) RELATING TO ACCESSIBILITY BY PERSONS |
| | WITH DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR |
| | STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND |
| | ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR |
| | STRUCTURES. |
| | |
| | 16) DEPENDING ON THE SIZE OF THE CONSTRUCTION TRAILERS, |
| | CLOSENESS TO BUILDINGS AND OR OTHER CONSTRUCTION |
| | TRAILERS THE FIRE DEPARTMENT THROUGH THE FIRE |
| | PREVENTION CODE MAY REQUIRE FIRE SPRINKLERS. |
| | |
| | 17) PLEASE NOTE THERE IS CONCERN RAISED THAT A SEAWALL |
| | REPAIR PERMIT IS IN FOR REVIEW, PERMIT # 15041128. IS |
| | THERE ANY CONCERNS THIS PORTION OF THE PROJECT NEEDS TO |
| | BE COMPLETED BEFORE THE AUGER CAST PILING BEGIN? IN THE |
| | GFA SOILS REPORT ON PAGE 10 IN BOLD PRINT AND UNDER |
| | LINED IS THE FOLLOWING COMMENT: |
| | |
| | |
| | I BELIEVE THIS IS COVERED UNDER SECTION 2010 FBC-B |
| | 1803.3. ADDITIONAL STUDIES MAY BE REQUIRED. |
| | |
| | |
| | 18) TO DATE THERE HAS BEEN NO PERMIT APPLIED FOR, FOR |
| | TEST PILING INCOMPLIANCE WITH THE 2010 FBC-B |
| | 1810.3.3.1.2 LOAD TEST. |
| | |
| | 19) TO DATE WE HAVE NO COMPANY SIGNED ON TO OVERSEE THE |
| | AUGER CAST PILE OR TEST PILE. FBC-B 1803.4 QUALIFIED |
| | REPRESENTATIVE. 2010 FLORIDA BUILDING CODE W * 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION SECTION 117 TESTS. THE |
| | BUILDING OFFICIAL MAY REQUIRE TESTS OR TEST REPORTS AS |
| | PROOF OF COMPLIANCE. REQUIRED TESTS ARE TO BE MADE AT |
| | THE EXPENSE OF THE OWNER, OR AGENT, BY AN APPROVED |
| | TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| | |
| | 20) SHEET S1.01 NOTE # 20B UNDER THE HEADING REINFORCED |
| | CONCRETE MASONRY STATES THAT OBSERVE PLACEMENT OF AT |
| | LEAST 10% OF THE INDIVIDUAL UNITS FOR EACH GROUT LIFT. |
| | FL. S. S. 553.79 (5)(A) THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO AND APPROVED BY THE ENFORCING |
| | AGENCY BEFORE THE ISSUANCE OF A BUILDING PERMIT FOR THE |
| | CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE OF |
| | THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE SPECIFIC |
| | INSPECTION PROCEDURES AND SCHEDULES SO THAT THE |
| | BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 21) SHEET S1.1 FOUNDATIONS NOTE # 5-9 PROVIDE DETAILS |
| | ON THE BACK FILLING OF THE BASEMENT WALLS. SHEET A0.24 |
| | HEADING THERMAL & MOISTURE PROTECTION. PLEASE PROVIDE |
| | COMPLIANCE WITH: 2010 FBC-B 1805.3 WATERPROOFING 1-4. |
| | |
| | 22) CONCERNS THE PLANS DO NOT PROVIDE DOCUMENTATION OF |
| | CODE SECTION 2010 FBC-B 403.3.2 REQUIRED FIRE PUMPS |
| | SHALL BE SUPPLIED BY CONNECTIONS TO A MINIMUM OF (2) |
| | WATER MAINS LOCATED IN DIFFERENT STREETS. ALSO REVIEW |
| | THE EXCEPTION. |
| | |
| | 23) THERE IS A QUESTION OF THE BONDING OF THE STEEL |
| | RE-ENFORCEMENT FOR ELECTRICAL. IS THERE ALSO GOING TO |
| | BE ANY LIGHTNING BONDING GOING TO BE REQUIRED? PERMIT |
| | WILL NEED TO BE PULLED FOR THE SCHEDULING OF THESE |
| | INSPECTIONS, NO DETAILS. |
| | |
| | 24) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |