Plan Review Notes
Plan Review Notes For Permit 15050267
Permit Number 15050267
Review Stop M
Sequence Number 4
Notes
Date Text
2015-09-14 13:55:553RD REVIEW: FBC 2010 MECHANICAL
 PERMIT #15050267
 9/14/15
  
 1) THIS IS THE 3RD SUBMITTAL ON THIS PROJECT AND
 COMMENTS FROM THE 1ST REVIEW STILL EXIST. I AM
 REPRINTING THEM HERE. PLEASE CORRECT AND REVISE THE
 PLAN ACCORDINGLY:
 2) (PROVIDE A VENTILATION CALCULATION FOR THE LAUNDRY
 ROOM IN COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL.
 THE DESIGN PROFESSIONAL SHALL VERIFY THE EXISTING
 SYSTEMS ARE MEETING THE REQUIRED DEMAND, OR PROVIDE
 PLANS AND DETAILS FOR WHATEVER MODIFICATIONS OR
 INSTALLATIONS WILL BE NECESSARY.)
 PLEASE NOTE THAT THE MECHANICAL VENTILATION RATE PER
 THE TABLE IS 7.5 CFM PER PERSON WITH THE OCCUPANT
 DENSITY LEVEL 20 PERSONS PER 1000 SQ. FT. SHOW THE
 CALCULATION ON THE PLANS AND CLARIFY HOW THE SYSTEM
 WILL FUNCTION (APPARENTLY THE WALL FAN HAS BEEN REMOVED
 FROM THE PLANS).
 IF USING THE NATUTURAL VENTILATION METHOD, PLEASE
 PROVIDE A CALCULATION TO VERIFY COMPLIANCE WITH SECTION
 402.2 ( MINIMUM OPENABLE AREA TO THE OUTDOORS SHALL BE
 4 PERCENT OF THE FLOOR AREA BEING VENTILATED).
 *NOTE: PLEASE REVIEW SECTION 304.9.3 FBC-10 FUEL GAS-
 COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM.
 WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING'S
 MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE
 THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR.
 IF YOU HAVE ANY QUESTIONS, NEED FURTHER CLARIFICATION,
 OR WOULD LIKE TO SET UP A MEETING TO HELP EXPEDITE THE
 PERMITTING PROCESS PLEASE CONTACT ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved