| Date |
Text |
| 2015-09-14 13:55:55 | 3RD REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15050267 |
| | 9/14/15 |
| | |
| | 1) THIS IS THE 3RD SUBMITTAL ON THIS PROJECT AND |
| | COMMENTS FROM THE 1ST REVIEW STILL EXIST. I AM |
| | REPRINTING THEM HERE. PLEASE CORRECT AND REVISE THE |
| | PLAN ACCORDINGLY: |
| | 2) (PROVIDE A VENTILATION CALCULATION FOR THE LAUNDRY |
| | ROOM IN COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL. |
| | THE DESIGN PROFESSIONAL SHALL VERIFY THE EXISTING |
| | SYSTEMS ARE MEETING THE REQUIRED DEMAND, OR PROVIDE |
| | PLANS AND DETAILS FOR WHATEVER MODIFICATIONS OR |
| | INSTALLATIONS WILL BE NECESSARY.) |
| | PLEASE NOTE THAT THE MECHANICAL VENTILATION RATE PER |
| | THE TABLE IS 7.5 CFM PER PERSON WITH THE OCCUPANT |
| | DENSITY LEVEL 20 PERSONS PER 1000 SQ. FT. SHOW THE |
| | CALCULATION ON THE PLANS AND CLARIFY HOW THE SYSTEM |
| | WILL FUNCTION (APPARENTLY THE WALL FAN HAS BEEN REMOVED |
| | FROM THE PLANS). |
| | IF USING THE NATUTURAL VENTILATION METHOD, PLEASE |
| | PROVIDE A CALCULATION TO VERIFY COMPLIANCE WITH SECTION |
| | 402.2 ( MINIMUM OPENABLE AREA TO THE OUTDOORS SHALL BE |
| | 4 PERCENT OF THE FLOOR AREA BEING VENTILATED). |
| | *NOTE: PLEASE REVIEW SECTION 304.9.3 FBC-10 FUEL GAS- |
| | COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM. |
| | WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING'S |
| | MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE |
| | THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. |
| | IF YOU HAVE ANY QUESTIONS, NEED FURTHER CLARIFICATION, |
| | OR WOULD LIKE TO SET UP A MEETING TO HELP EXPEDITE THE |
| | PERMITTING PROCESS PLEASE CONTACT ME. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |