| Plan Review Notes For Permit 15050267 |
| Permit Number |
15050267 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-08-21 11:29:57 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15050267 | | | 8/21/15 | | | | | | 1) AS PREVIOUSLY REQUESTED PLEASE PROVIDE | | | MANUFACTURER'S SPECS FOR THE GREENHECK LOUVER, AND A | | | VALID FLORIDA PRODUCT APPROVAL OR MIAMI DADE NOA FOR | | | THE GREENHECK LOUVER. PLEASE NOTE THAT THE LOUVER CAN | | | PROTECT BOTH THE MAKEUP AIR OPENING AND THE EXHAUST FAN | | | OPENING- CURRENTLY PLAN IS NOT SHOWING HOW THE FAN | | | OPENING WILL BE PROTECTED. PLEASE ADDRESS THIS ISSUE. | | | 2) THE SUBMITTED SPECS FOR THE EXHAUST FAN DO NOT SHOW | | | WHICH OF THE GREENHECK TYPE SE1 FANS WILL BE USED. | | | PLEASE SUBMIT THE CUT SHEETS FOR THAT MODEL ONLY, AND | | | PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN THAT INCLUDES | | | THE MODEL NUMBER, CFM CAPACITY, AND ELECTRICAL DATA. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|