Plan Review Notes
Plan Review Notes For Permit 15050267
Permit Number 15050267
Review Stop M
Sequence Number 3
Notes
Date Text
2015-08-21 11:29:573RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15050267
 8/21/15
  
 1) AS PREVIOUSLY REQUESTED PLEASE PROVIDE
 MANUFACTURER'S SPECS FOR THE GREENHECK LOUVER, AND A
 VALID FLORIDA PRODUCT APPROVAL OR MIAMI DADE NOA FOR
 THE GREENHECK LOUVER. PLEASE NOTE THAT THE LOUVER CAN
 PROTECT BOTH THE MAKEUP AIR OPENING AND THE EXHAUST FAN
 OPENING- CURRENTLY PLAN IS NOT SHOWING HOW THE FAN
 OPENING WILL BE PROTECTED. PLEASE ADDRESS THIS ISSUE.
 2) THE SUBMITTED SPECS FOR THE EXHAUST FAN DO NOT SHOW
 WHICH OF THE GREENHECK TYPE SE1 FANS WILL BE USED.
 PLEASE SUBMIT THE CUT SHEETS FOR THAT MODEL ONLY, AND
 PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN THAT INCLUDES
 THE MODEL NUMBER, CFM CAPACITY, AND ELECTRICAL DATA.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  