Plan Review Notes
Plan Review Notes For Permit 15050267
Permit Number 15050267
Review Stop P
Sequence Number 2
Notes
Date Text
2015-07-16 04:50:321) SUBMIT A TYPICAL VENT DETAIL FOR THE GAS DRYERS.
 SHOW THE SIZE, THE TYPE OF VENT, THE HEIGHT OF THE VENT
 ABOVE FINISH GRADE,
 2) SHOW THE TOTAL DEVELOPED LENGTH OF THE GAS PIPING
 FROM THE POINT OF DELIVERY TO THE FURTHEST OUTLET ON
 THE SYSTEM. THERE IS OVER-TYPE ON THE GAS RISER SO SOME
 OF THE PIPE SIZES AND DIMENSIONS CANNOT BE READ.SHOW
 THE LENGTH OF THE TYPICAL PIPE DROPS TO THE DRYERS.
 3) INDICATE THE PSI OF THE GAS COMING INTO THE
 STRUCTURE. THE PLANS SHOW 5 PSI AT THE METER.IS THIS
 GOING TO BE THE PSI FOR THE SYSTEM? FOR A 5 PSI SYSTEM,
 THE FUEL GAS CODE HAS ONLY ONE TABLE AND THAT IS WITH A
 PRESSURE DROP OF 3.5 PSI. IS THIS THE TABLE YOU ARE
 USING? IF SO, INDICATE SUCH ON THE GAS PLANS WPB AMEND.
 TO FBC SEC. 107.3.5.1.5.
 4) SHOW THE LOCATION OF ALL LINE GAS PRESSURE REDUCING
 REGULATORS ( IF APPLICABLE ) AND SHOW THE VENTING OF
 THE REGULATORS PER 2010 FUEL GAS CODE SEC. 410.3,
 410.3.1. ALL REGULATORS SHALL BE ACCESSIBLE.
 5) THE GAS RISER SHOWS THE GAS LINE TO THE WATER HEATER
 AS 1 INCH AND THE PLAN VIEW SHOWS IT AS 3/4 ". WHICH IS
 IT?
 6) HOW WAS THE SIZE OF THE LINT TRAP DETERMINED? SUBMIT
 FLOW CALCULATIONS CONFIRMING THAT INTERCEPTOR IS OF
 ADEQUATE CAPACITY FOR THIS SYSTEM. 2010 FPC 1003.2.
 7) VENTS AND BRANCH VENTS EXCEEDING EXCEEDING 40 FEET
 IN DEVELOPED LENGTH SHALL BE INCREASED BY ONE PIPE SIZE
 FOR THE ENTIRE LENGTH OF THE VENT PIPE IN ACCORDANCE
 WITH 2010 FPC SEC.916.2, 916.4.
 8) THE GAS PIPING SHALL BE BONDED PER 2010 FGC
 SEC.310.1.
 9) EXHAUST DUCTS FOR CLOTHES DRYERS SHALL BE EQUIPPED
 WITH BACKDRAFT DAMPERS.2010 FGC SEC.614.4.
 10) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 DRYERS. 2010 FGC SEC.304.1.
 11) SHT. M-1 SHOWS 10 DRYERS BUT ONLY 8 EXHAUSTS.
 CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  