2015-07-24 11:29:242ND REVIEW: FBC 2010 MECHANICAL
  
 1) THE REQUESTED SUBMITTALS FOR THE DRYERS HAVE NOT
 BEEN REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL
 OF RECORD AS REQUESTED: PLEASE COMPLY AND PROVIDE
 EQUIPMENT SCHEDULES ON THE PLAN AS REQUESTED IN THE 1ST
 REVIEW.
 2) AS REQUESTED IN THE FIRST REVIEW, PROVIDE MAKE-UP
 AIR CALCULATIONS ON THE PLAN FOR THE DRYERS- (SEE
 MANUFACTURER'S RECOMMENDATIONS), AND VENTILATION
 CALCULATIONS FOR THE NEW LAUNDRY ROOM- (TABLE 403.3
 FBC-MECHANICAL). SHOW HOW ALL AIR IS BEING SUPPLIED AND
 CONTROLLED.
 3) AS REQUESTED IN THE 1ST REVIEW, PROVIDE FRONT AND
 PLAN VIEWS OF THE EXHAUST VENTS: INDICATE THE TYPE AND
 SIZE OF THE DUCTS, LENGTH OF THE CONNECTORS, HEIGHTS OF
 RISERS, TOTAL RUN CALCULATIONS AND TERMINATION
 LOCATIONS.
 4) SHOW COMPLIANCE WITH SECTION 504.4 FOR REQUIRED
 BACKDRAFT DAMPERS TO BE INSTALLED AT THE DRYER VENT
 TERMINATIONS.
 5) INDICATE IF THE GAS-FIRED WATER HEATER IS NEW OR
 EXISTING ON THE PLAN. IF THE UNIT IS NEW, SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE WATER HEATER AND
 VENT SYSTEM, AND PROVIDE A VENTING DIAGRAM. THE VENTING
 DIAGRAM SHALL SHOW THE TYPE AND SIZE OF VENT PIPE,
 TOTAL LENGTH OF CONNECTORS AND RISERS, AND TERMINATION
 LOCATION- REFER TO SECTION 504 FBC-10 FUEL GAS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER