| 2015-08-19 10:53:14 | 1) THE SUBMITTED VENT DETAIL IS INADEQUATE. SHOW THE |
| | TYPE OF VENT ( TYPE B, OR SINGLE WALL,ETC.) IF SINGLE |
| | WALL VENT, INDICATE THE THICKNESS OF THE METAL. THE |
| | SINGLE WALL VENT SHALL BE CONSTRUCTRED OF GALVANIZED |
| | SHEET METAL NOT LESS THAN 0.0304 INCH THICK PER 2010 |
| | FBC-FUEL GAS SEC.503.7 AND SHALL BE INSTALLED PER FGC |
| | 503.7.3 & 503.7.7. |
| | 2) IF VENT IS OTHER THAN SINGLE WALL PIPE, THE VENT |
| | SHALL COMPLY WITH 2010 FGC SEC.503.6.4, 503.6.5. |
| | 3) THE GAS LINE FROM THE GAS METER TO THE FIRST TEE |
| | CONNECTION SHALL BE 1 1/2" PER TABLE 402.4 (2). |
| | 4) INDICATE THE TYPE OF PIPE BEING USED FOR GAS THE |
| | SYSTEM. |
| | 5) THE TYPICAL GAS PIPE DROP SHOW 3 & 6 FT. DROPS TO |
| | THE APPLIANCES BUT THE GAS RISER SHOWS 2 & 4 FT. DROPS. |
| | CLARIFY. |
| | 6) IDENTIFY ON THE FAN LITERATURE THE SPECIFIC MODEL |
| | THAT IS BEING USED. WPB AMEND TO FBC SEC.107.2.1. |
| | 7) IDENTIFY ON THE MANUF. SPECS THE TYPE OF BACKDRAFT |
| | DAMPER BEING INSTALLED.WPB AMEND TO FBC SEC.107.2.1. |
| | 8) SUBMIT ADDITIONAL DOCUMENTATION AS TO HOW THE MAKE |
| | UP AIR FAN MEETS THE MINIMUM REQUIRED AMOUNT OF |
| | COMBUSTION AIR IN ACCORDANCE WITH THE 2010 FGC |
| | SEC.304.5,304.6,304.7,304.10,& 304.11. |
| | 9) HOW WILL THE FAN OPERATE - IS IT CONNECTED TO A |
| | LIGHT SWITCH AND OPERATE WHEN THE SPACE IS BEING USED? |
| | WHAT IS THE PURPOSE OF THE EDJ UNIT THAT IS BEING |
| | INSTALLED? |
| | |
| | I SUGGEST CONTACTING ME TO SET UP AN APPOINTMENT TO |
| | DISCUSS THE COMMENTS. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |