2015-08-19 10:53:141) THE SUBMITTED VENT DETAIL IS INADEQUATE. SHOW THE
 TYPE OF VENT ( TYPE B, OR SINGLE WALL,ETC.) IF SINGLE
 WALL VENT, INDICATE THE THICKNESS OF THE METAL. THE
 SINGLE WALL VENT SHALL BE CONSTRUCTRED OF GALVANIZED
 SHEET METAL NOT LESS THAN 0.0304 INCH THICK PER 2010
 FBC-FUEL GAS SEC.503.7 AND SHALL BE INSTALLED PER FGC
 503.7.3 & 503.7.7.
 2) IF VENT IS OTHER THAN SINGLE WALL PIPE, THE VENT
 SHALL COMPLY WITH 2010 FGC SEC.503.6.4, 503.6.5.
 3) THE GAS LINE FROM THE GAS METER TO THE FIRST TEE
 CONNECTION SHALL BE 1 1/2" PER TABLE 402.4 (2).
 4) INDICATE THE TYPE OF PIPE BEING USED FOR GAS THE
 SYSTEM.
 5) THE TYPICAL GAS PIPE DROP SHOW 3 & 6 FT. DROPS TO
 THE APPLIANCES BUT THE GAS RISER SHOWS 2 & 4 FT. DROPS.
 CLARIFY.
 6) IDENTIFY ON THE FAN LITERATURE THE SPECIFIC MODEL
 THAT IS BEING USED. WPB AMEND TO FBC SEC.107.2.1.
 7) IDENTIFY ON THE MANUF. SPECS THE TYPE OF BACKDRAFT
 DAMPER BEING INSTALLED.WPB AMEND TO FBC SEC.107.2.1.
 8) SUBMIT ADDITIONAL DOCUMENTATION AS TO HOW THE MAKE
 UP AIR FAN MEETS THE MINIMUM REQUIRED AMOUNT OF
 COMBUSTION AIR IN ACCORDANCE WITH THE 2010 FGC
 SEC.304.5,304.6,304.7,304.10,& 304.11.
 9) HOW WILL THE FAN OPERATE - IS IT CONNECTED TO A
 LIGHT SWITCH AND OPERATE WHEN THE SPACE IS BEING USED?
 WHAT IS THE PURPOSE OF THE EDJ UNIT THAT IS BEING
 INSTALLED?
  
 I SUGGEST CONTACTING ME TO SET UP AN APPOINTMENT TO
 DISCUSS THE COMMENTS.
  