2015-07-24 10:05:28PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. PROVIDE A LEGIBLE AND ACCURATE SYMBOL LEGEND AS PER
 FBC
 2. YOU SHALL SUBMIT SPECIFIC LOAD CALCS AS REQUIRED BY
 NEC 220
 3. IDENTIFY ALL EQUIPMENT AND ITS SPECIFIC LOCATION ON
 THE FLOOR PLANS, ALONG WITH ITS DEDICATED ELECTRICAL
 CKT.
 4. IDENTIFY EVERY ELECTRICAL PANEL SHOWN ON THE FLOOR
 PLANS WITH ITS RESPECTIVE CIRCUIT DIRECTORY.
 5. PROVIDE AN ELECTRICAL RISER DIAGRAM INCLUDING ALL
 ELECTRICAL PANELS ON SITE.
 6. YOU SHALL PROVIDE A LIGHTING PLAN COMPLIANT WITH
 FBC-E SECTION 505.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.