| Plan Review Notes For Permit 15050267 |
| Permit Number |
15050267 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-24 10:05:28 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. PROVIDE A LEGIBLE AND ACCURATE SYMBOL LEGEND AS PER | | | FBC | | | 2. YOU SHALL SUBMIT SPECIFIC LOAD CALCS AS REQUIRED BY | | | NEC 220 | | | 3. IDENTIFY ALL EQUIPMENT AND ITS SPECIFIC LOCATION ON | | | THE FLOOR PLANS, ALONG WITH ITS DEDICATED ELECTRICAL | | | CKT. | | | 4. IDENTIFY EVERY ELECTRICAL PANEL SHOWN ON THE FLOOR | | | PLANS WITH ITS RESPECTIVE CIRCUIT DIRECTORY. | | | 5. PROVIDE AN ELECTRICAL RISER DIAGRAM INCLUDING ALL | | | ELECTRICAL PANELS ON SITE. | | | 6. YOU SHALL PROVIDE A LIGHTING PLAN COMPLIANT WITH | | | FBC-E SECTION 505. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. |
|