Plan Review Notes
Plan Review Notes For Permit 15050267
Permit Number 15050267
Review Stop M
Sequence Number 1
Notes
Date Text
2015-06-08 17:17:241ST REVIEW: FBC 2010 MECHANICAL
  
 1) A COMPLETE REVIEW OF THE PROPOSED PROJECT CANNOT BE
 COMPLETED WITHOUT SUBMITTAL OF COMPLETE MANUFACTURER'S
 SPECIFICATIONS FOR THE NEW DRYERS AND VENTS.
 THE SUBMITTALS SHALL BE REVIEWED AND APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD- SECTION 614 FBC-10 FUEL
 GAS. PLEASE NOTE THAT THE CODE CLASSIFIES DRYERS AS
 EITHER RESIDIENTIAL OR COMMERCIAL, AND THE
 MANUFACTURER'S MAKE THAT DETERMINATION DEPENDING USAGE.
 2) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE
 DRYERS, AND CLARIFY IF THE DRYERS WILL BE
 COIN-OPERATED.
 3) INDICATE THE SOURCE OF, AND THE AMOUNT OF MAKE-UP
 AIR REQUIRED BY THE MANUFACTURER FOR EACH DRYER.
 4) PROVIDE A VENTILATION CALCULATION FOR THE LAUNDRY
 ROOM IN COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL.
 THE DESIGN PROFESSIONAL SHALL VERIFY THE EXISTING
 SYSTEMS ARE MEETING THE REQUIRED DEMAND, OR PROVIDE
 PLANS AND DETAILS FOR WHATEVER MODIFICATIONS OR
 INSTALLATIONS WILL BE NECESSARY.
 5) PROVIDE FRONT AND PLAN VIEWS OF THE EXHAUST VENTS:
 INDICATE THE TYPE AND SIZE OF THE DUCTS, LENGTH OF THE
 CONNECTORS, HEIGHTS OF RISERS, TOTAL RUN CALCULATIONS
 AND TERMINATION LOCATIONS.
  