2015-05-14 12:43:00PROVIDE LOAD CALCULATION. INDICATED SIZE OF EXISTING
 PANELBOARD AND SERVICE. VERIFY THE EXISTING SERVICE CAN
 CARRY THE NEW ELECTRICAL LOADS. PROVIDE A PANEL
 SCHEDULE SHOWING ALL WIRE AND CIRCUIT SIZES.NEC 215.5,
 220.10
  
 SEE ELECTRIC PERMIT #15040378
 R. LECKY, ELECTRICAL PLANS EXAMINER