| 2015-05-15 09:29:20 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15050267 |
| | ADD: 1001 36TH ST. #M33 |
| | CONT: TBD |
| | TEL: (386)7056 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. JULY 17/15 |
| | ACTION: DENIED |
| | |
| | 1) THE WALL BETWEEN THE EXISTING LAUNDRY ROOM AND |
| | EXISTING ROOM IS TO BE DEMOLISHED, IS THIS A BLOCK |
| | WALL, LOAD BEARING WALL, IT APPEARS TO BE DRAWN TO BE A |
| | 8 INCH WALL? THE PLANS SHEET A3 APPEAR TO HAVE THE SAME |
| | WALL LINE IN THE SAME LOCATION107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 2) THE PLANS ALSO SHOW A NEW 2 X 2 FOOT MAKE UP AIR |
| | FAN, PLEASE PROVIDE THE STRUCTURAL DETAILS FOR THE NEW |
| | OPENING AND THE ANCHORING OF THE FAN AND EXTERIOR |
| | LOUVER TO KEEP THE RAIN OUT. LOAD BEARING WALLS, PART |
| | OF THE MAIN WIND FORCE RESISTING SYSTEM. |
| | |
| | 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(C) WALL LOUVERS |
| | |
| | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |