Plan Review Notes
Plan Review Notes For Permit 15050262
Permit Number 15050262
Review Stop B
Sequence Number 3
Notes
Date Text
2015-10-06 10:14:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050262
 ADD: 1851 DIVISION AVE.
 CONT: LANDMARK
 CONTACT: JORGE COSTAS
 TEL: (305)665-1146
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: TUES. OCT.06/2015
 SILVER PALM PLACE
 BLDG # 3/ 29 UNITS/ 4 STORY/BLDG TYPE: III-B/ R2
  
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 THIS REVIEW IS FOR BUILDING # 1 AND DOES NOT INCLUDE
 ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING,
 SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY
 AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION
 OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL
 NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH
 ASSOCIATED COST.
  
 1) PROVISO: NOTICE! ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2A-B) COMPLIED.
  
  
 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING
 FLORIDA S. S. 553.71(7)
 ?THRESHOLD BUILDING" .
  
 3E) 3RD REQUEST!!! NOTE TO DATE NO PERMIT APPLICATION
 WHERE THE OWNER HAS SIGNED AND THEIR SIGNATURES
 NOTARIZED. AHOLD WILL BE PUT ON THE PERMIT NOT TO ISSUE
 UNTIL THE OWNERS SIGNATURE IS ON THE PERMIT
 APPLICATION.
  
 3F)NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
  
 3G) NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM
 BEACHES? AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H)NOTICE ONLY! 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 5-9) COMPLIED
  
 10) SHEET A-200A:
 10A) COMPLIED.
  
 10B) REVISION REQUIRED. 3RD REQUEST. BETWEEN DWELLING
 UNITS AND DWELLING UNITS AND COMMON AREAS WALL TYPE W5
 HAS BEEN INDICATED A 6 INCH CONCRETE REINFORCED WALL
 WITH NO INSULATION. PLEASE PROVIDE DOCUMENTATION THAT
 COMPLIANCE WITH 2010 FBC-B 1207.2 HAS BEEN ACHIEVED.
  
 RESPONSE: WALL SOUND INSULATION THAT HAS ALREADY BEEN
 TESTED, IS FOUND ON SHEET A9.04 ALSO WALL TYPE SHEET
 A-8.01. NOTE THESE ARE SALES BROCHURES; THEY ARE NOT
 THE ACTUAL TEST. PROVIDE TEST REPORTS.
  
  
  
 11-19) COMPLIED.
  
 20)(A)REVISION REQUIRED: 3RD REQUEST. SHEET A4.02
 INDICATES 6 INCH CONCRETE SLAB. SHEET A-9.04 INDICATES
 THE USE OF (2) FLOOR INSULATION PRODUCTS, DB-4LOORING
 INSULATION, AND QT SCU 4002 PLEASE SUBMIT THE REPORTS
 FOR COMPLIANCE WITH 20A-20C, MISSING FLAME SPREAD.
  
 20)(B) REVISION REQUIRED: 3RD REQUEST. SHEET A-9.04
 ALSO SHOWS A WALL INSULATION TYPE DB-3, THIS IS A SALES
 BROCHURE PLEASE SUBMIT TEST INFORMATION, WALL
 INSULATION WILL NEED TO COMPLY WITH 1207.2 THE SALES
 BROCHURE SUBMITTED IS FOR WOOD AND METAL STUDS, NEVER
 TESTED ON A 6 INCH CONCRETE WALL. WALL INSULATION WILL
 NEED TO MEET 1207.2 ASTM E 90 AND SECTION 2010 FBC-B
 719.2 CONCEALED INSULATION FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE DEVELOPMENT OF 450.
  
  
 20A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 20B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 20C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 21-22) COMPLIED.
  
 23)PROVISO: PRODUCT APPROVALS/ DEFERRED SUBMITTALS.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 23A) )PROVISO: FOR GLAZED PRODUCT APPROVALS, IDENTIFY
 THE TYPE OF GLAZING, WIDTH & HEIGHT OF GLAZED OPENING,
 IF MULLIONS ARE USED, CIRCLE THE MULLION TO BE
 INSTALLED, PRESSURES, AND FASTENERS.
  
 23B) )PROVISO: FOR ROOFING APPROVALS: FLAT ROOF.
 HIGHLIGHT THE SUB-SYSTEM TO BE INSTALLED, NOTE THE
 PRESSURES, IF THEY REQUIRE ENHANCED FASTENING, RAS 117
 CALCULATIONS, AND SIGNED & SEALED CALCULATIONS.
  
 23C) )PROVISO: FOR THE SLOPED ROOF: PROVIDE THE TYPE OF
 TILE TO BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF
 FOAMED, IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED
 PRESSURES.
  
 23D) 2)PROVISO: EITHER THE DESIGN PROFESSIONAL OR THE
 CONTRACTOR CAN ELECT TO DEFER THE SUBMISSION OF THE
 PRODUCT APPROVALS TO AFTER PERMIT ISSUANCE IF THE
 PRESSURES FOR THE BUILDING ARE CORRECT AND A WRITTEN
 DOCUMENT ASKING FOR THE PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 24) )PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  