| 2015-08-06 04:35:40 | 1)THE URINAL IN THE MEN'S RESTROOM ON THE FIRST FLOOR |
| | BY THE CLUB ROOM IS WITHIN THE LINE OF SIGHT WITH THE |
| | DOOR OPEN. SEE SHT.A5.06 - DETAIL C - PRIVACY SHALL BE |
| | PROVIDED IN ACCORDANCE WITH 2010 FPC SEC.310.5. 2ND |
| | REQUEST. |
| | 2) THE OVERFLOW RAINWATER DOWNSPOUTS SHALL DISCHARGE A |
| | MINIMUM OF ONE FOOT AWAY FROM THE STRUCTURE SIDEWALL |
| | PER 2010 FBC 1503.7. PLACE A NOTE ON THE PLANS.THIS |
| | COMMENTS REFERS TO THE DOWNSPOUTS FROM THE GUTTERS. |
| | THEY ARE NOT UNDERGROUND. |
| | 3) SHT. A2.05 - THE SCUPPER CALCULATION SHOWS 1551 SQ. |
| | FT. FOR SCUPPER #1 & 1282 SQ. FT. FOR SCUPPER #2, AND |
| | ALSO AT THE BOTTOM OF THE TABLE IT STATES "HORIZONTAL |
| | PROJECTED ROOF AREA" -1008 SQ. FT.- THIS DOES NOT ADD |
| | UP.PLEASE CLARIFY. IS THIS A TYPO ERROR? |
| | 4) SHT. A2.05 - THIS BUILDING HAS TWO FLAT ROOFS |
| | IDENTIFY RWL-1 & RWL-2 ON THE PLANS. WPB AMEND. TO 2010 |
| | FBC SEC. 107.2.1.2ND REQUEST. |
| | 5) THE STORM DRAINAGE RISER SHOWS OVERFLOW DRAINS, NOT |
| | SCUPPERS, YET THERE ARE TABLES FOR SCUPPER SIZING. ARE |
| | THERE OR ARE THERE NOT ROOF SCUPPERS ON THIS BUILDING? |
| | IF SO, SHOW THE LOCATION OF ALL SCUPPERS AND SHOW THE |
| | LENGTH AND HEIGHT DIMENSIONS OF THE SCUPPERS AND THE |
| | DESIGN HEAD ( IN INCHES). SCUPPERS SHALL BE SIZED PER |
| | THE 2010 FBC-PLUMBING TABLE 1106.7. IF NOT, DELETE ANY |
| | REFERENCE/TABLE TO ROOF SCUPPERS. |
| | 6) SUBMIT GUTTER CALCULATIONS FOR THE ROOF GUTTERS AND |
| | DOWNSPOUTS. COMPLY W/ 2010 FPC SEC. 1106.6 & 1106.7. |
| | 2ND REQUEST. |
| | 7) SHT.A2.10 - THIS BUILDING HAS TWO LOWER ROOFS BUT |
| | THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK. |
| | CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER |
| | ROOFS AND SHOW THE LOCATION OF THE SCUPPERS ( IF |
| | APPLICABLE ) AND PROVIDE SCUPPER CALCULATIONS.WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 8) SHT. A2.15 - THIS BUILDING HAS TWO LOWER ROOFS BUT |
| | THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK. |
| | CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER |
| | ROOFS AND SHOW THE LOCATION OF THE SCUPPERS (IF |
| | APPLICABLE ) AND PROVIDE SCUPPER CALCULATIONS. COMPLY |
| | WITH 2010 FBC-PLUMBING, SEC.1106.1 & TABLES 1106.2, (1) |
| | THROUGH 1106.2 (2), 1106.3,1106.7. |
| | 9) THIS BUILDING HAS TWO LOWER ROOFS BUT THE ROOF DRAIN |
| | CALCULATIONS ON THE SHEET ARE BLANK. CLARIFY. SUBMIT |
| | ROOF DRAIN CALCULATIONS FOR THE LOWER ROOFS AND SHOW |
| | THE LOCATION OF THE SCUPPERS ( IF APPLICABLE ) AND |
| | PROVIDE SCUPPER CALCULATIONS.COMPLY WITH 2010 |
| | FBC-PLUMBING, SEC.1106.1 & TABLES 1106.2, (1) THROUGH |
| | 1106.2 (2), 1106.3,1106.7. |
| | 10) SHT. P1.00 - SHOWS A 2 INCH WATER SERVICE TO |
| | BUILDING #2 AND SHT. WS-1 SHOWS A 4 INCH WATER SERVICE. |
| | CLARIFY. 2ND REQUEST. THE CIVIL PLANS STILL SHOW A 4 |
| | INCH WATER LINE. WHICH IS IT? THE PLANS SHALL |
| | CORRELATE. |
| | 11) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE OIL |
| | SMART PUMP SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 2ND REQUEST. THE RESPONSE STATED THEY WILL BE PROVIDED. |
| | WHEN? |
| | 12) SHT. P4.00 - SHOW THE TONNAGE OF THE AIR |
| | CONDITIONING EQUIPMENT ON THE CONDENSATE RISER. COMPLY |
| | W/ TABLE 314.2.2. OF 2010 FPC. THE PLAN WAS ONLY |
| | CORRECTED FOR BUILDING #1. CORRECT THE PLAN FOR THE |
| | OTHER BUILDINGS. 2ND REQUEST. |
| | 13) SUBMIT THE MANUFACTURER SPECIFICATIONS & |
| | INSTALLATION MANUAL FOR THE TANKLESS WATER HEATERS. WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. I CANNOT DETERMINE IF |
| | THE VENT LOCATIONS ARE APPROVED AND TO CODE WITHOUT THE |
| | INSTALLATION MANUAL THAT SHOWS THE REQUIREMENTS. MY |
| | CONCERNS ARE THAT THIS IS A DIRECT VENT APPLIANCE AND |
| | THE CLOSE PROXIMITY TO AN EXHAUST DUCT MAY CREATE A |
| | CODE ISSUE.2010 FBC-FUEL GAS CODE SEC.503.2.3. |
| | 14) SUBMIT DETAILS ON THE DOMESTIC WATER PUMP PACKAGE. |
| | SUBMIT A DETAIL THAT SHOWS ALL THE PIPING. WPB AMEND. |
| | TO 2010 FBC SEC. 107.2.1. 2ND REQUEST. |
| | 15) IDENTIFY THE OVERFLOW DRAINS ON ALL THE ROOF PLANS. |
| | WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 16) SHT. P1.00 - CLEARLY SHOW WHERE THE WATER SERVICE |
| | ENTERS THE STRUCTURE. WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1. |
| | 17) THE AREA OF THE SLOPED ROOFS THAT ARE DRAINING ONTO |
| | THE LOWER ROOFS SHALL BE INCLUDED IN THE ROOF DRAINAGE |
| | CALCULATIONS. THIS WAS OVERLOOKED IN FIRST REVIEW.2010 |
| | FBC -PLUMBING SECS.1106.2 & 1106.3. |
| | 18) THE PLUMBING DRAWINGS REFER TO THE ARCHITECTURAL |
| | PLANS FOR DOWNSPOUT DETAILS. I COULD NOT FIND ANY |
| | DOWNSPOUT DETAILS IN THE ARCHITECTURAL PLANS. CLARIFY. |
| | 19) NOTE #14 ON THE ENLARGED ARCHITECTURAL FLOOR PLANS |
| | REFER TO THE ARCHITECTURAL AND PLUMBING DRAWINGS FOR |
| | DETAILS FOR THE GUTTERS AND DOWNSPOUTS. I COULD NOT |
| | FIND ANY DETAILS ON ANY OF THESE PLANS. CLARIFY. |
| | 20) AS UPLOADED, ALL THE PLUMBING DRAWINGS ARE LABELED |
| | AS "P' DRAWINGS. THERE IS NO WAY TO DISCERN WHICH |
| | DRAWINGS ARE FOR BUILDING #1, #2 OR #3. PLEASE SUBMIT |
| | ONLY THE DRAWINGS THAT ARE APPLICABLE TO THIS PERMIT |
| | AND THIS BUILDING. THIS APPLIES TO ALL THE DRAWINGS. |
| | WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 21) SEVERAL RESPONSES ON THE PLAN REVIEW COMMENT STATE |
| | "REFER TO REVISED ROOF PLAN" OR "SEE ARCHITECTURAL |
| | DRAWINGS." THESE RESPONSES ARE VAGUE AND |
| | INCONCLUSIVE.PLEASE PROVIDE THE SPECIFIC DRAWING NUMBER |
| | WHEN REFERENCING PLAN SHEETS.. WPB AMEND. TO 2010 FBC |
| | SEC. 107.2.1. |
| | |
| | |