Plan Review Notes
Plan Review Notes For Permit 15050262
Permit Number 15050262
Review Stop P
Sequence Number 2
Notes
Date Text
2015-08-06 04:35:401)THE URINAL IN THE MEN'S RESTROOM ON THE FIRST FLOOR
 BY THE CLUB ROOM IS WITHIN THE LINE OF SIGHT WITH THE
 DOOR OPEN. SEE SHT.A5.06 - DETAIL C - PRIVACY SHALL BE
 PROVIDED IN ACCORDANCE WITH 2010 FPC SEC.310.5. 2ND
 REQUEST.
 2) THE OVERFLOW RAINWATER DOWNSPOUTS SHALL DISCHARGE A
 MINIMUM OF ONE FOOT AWAY FROM THE STRUCTURE SIDEWALL
 PER 2010 FBC 1503.7. PLACE A NOTE ON THE PLANS.THIS
 COMMENTS REFERS TO THE DOWNSPOUTS FROM THE GUTTERS.
 THEY ARE NOT UNDERGROUND.
 3) SHT. A2.05 - THE SCUPPER CALCULATION SHOWS 1551 SQ.
 FT. FOR SCUPPER #1 & 1282 SQ. FT. FOR SCUPPER #2, AND
 ALSO AT THE BOTTOM OF THE TABLE IT STATES "HORIZONTAL
 PROJECTED ROOF AREA" -1008 SQ. FT.- THIS DOES NOT ADD
 UP.PLEASE CLARIFY. IS THIS A TYPO ERROR?
 4) SHT. A2.05 - THIS BUILDING HAS TWO FLAT ROOFS
 IDENTIFY RWL-1 & RWL-2 ON THE PLANS. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.2ND REQUEST.
 5) THE STORM DRAINAGE RISER SHOWS OVERFLOW DRAINS, NOT
 SCUPPERS, YET THERE ARE TABLES FOR SCUPPER SIZING. ARE
 THERE OR ARE THERE NOT ROOF SCUPPERS ON THIS BUILDING?
 IF SO, SHOW THE LOCATION OF ALL SCUPPERS AND SHOW THE
 LENGTH AND HEIGHT DIMENSIONS OF THE SCUPPERS AND THE
 DESIGN HEAD ( IN INCHES). SCUPPERS SHALL BE SIZED PER
 THE 2010 FBC-PLUMBING TABLE 1106.7. IF NOT, DELETE ANY
 REFERENCE/TABLE TO ROOF SCUPPERS.
 6) SUBMIT GUTTER CALCULATIONS FOR THE ROOF GUTTERS AND
 DOWNSPOUTS. COMPLY W/ 2010 FPC SEC. 1106.6 & 1106.7.
 2ND REQUEST.
 7) SHT.A2.10 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS ( IF
 APPLICABLE ) AND PROVIDE SCUPPER CALCULATIONS.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 8) SHT. A2.15 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS (IF
 APPLICABLE ) AND PROVIDE SCUPPER CALCULATIONS. COMPLY
 WITH 2010 FBC-PLUMBING, SEC.1106.1 & TABLES 1106.2, (1)
 THROUGH 1106.2 (2), 1106.3,1106.7.
 9) THIS BUILDING HAS TWO LOWER ROOFS BUT THE ROOF DRAIN
 CALCULATIONS ON THE SHEET ARE BLANK. CLARIFY. SUBMIT
 ROOF DRAIN CALCULATIONS FOR THE LOWER ROOFS AND SHOW
 THE LOCATION OF THE SCUPPERS ( IF APPLICABLE ) AND
 PROVIDE SCUPPER CALCULATIONS.COMPLY WITH 2010
 FBC-PLUMBING, SEC.1106.1 & TABLES 1106.2, (1) THROUGH
 1106.2 (2), 1106.3,1106.7.
 10) SHT. P1.00 - SHOWS A 2 INCH WATER SERVICE TO
 BUILDING #2 AND SHT. WS-1 SHOWS A 4 INCH WATER SERVICE.
 CLARIFY. 2ND REQUEST. THE CIVIL PLANS STILL SHOW A 4
 INCH WATER LINE. WHICH IS IT? THE PLANS SHALL
 CORRELATE.
 11) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE OIL
 SMART PUMP SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2ND REQUEST. THE RESPONSE STATED THEY WILL BE PROVIDED.
 WHEN?
 12) SHT. P4.00 - SHOW THE TONNAGE OF THE AIR
 CONDITIONING EQUIPMENT ON THE CONDENSATE RISER. COMPLY
 W/ TABLE 314.2.2. OF 2010 FPC. THE PLAN WAS ONLY
 CORRECTED FOR BUILDING #1. CORRECT THE PLAN FOR THE
 OTHER BUILDINGS. 2ND REQUEST.
 13) SUBMIT THE MANUFACTURER SPECIFICATIONS &
 INSTALLATION MANUAL FOR THE TANKLESS WATER HEATERS. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1. I CANNOT DETERMINE IF
 THE VENT LOCATIONS ARE APPROVED AND TO CODE WITHOUT THE
 INSTALLATION MANUAL THAT SHOWS THE REQUIREMENTS. MY
 CONCERNS ARE THAT THIS IS A DIRECT VENT APPLIANCE AND
 THE CLOSE PROXIMITY TO AN EXHAUST DUCT MAY CREATE A
 CODE ISSUE.2010 FBC-FUEL GAS CODE SEC.503.2.3.
 14) SUBMIT DETAILS ON THE DOMESTIC WATER PUMP PACKAGE.
 SUBMIT A DETAIL THAT SHOWS ALL THE PIPING. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1. 2ND REQUEST.
 15) IDENTIFY THE OVERFLOW DRAINS ON ALL THE ROOF PLANS.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 16) SHT. P1.00 - CLEARLY SHOW WHERE THE WATER SERVICE
 ENTERS THE STRUCTURE. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 17) THE AREA OF THE SLOPED ROOFS THAT ARE DRAINING ONTO
 THE LOWER ROOFS SHALL BE INCLUDED IN THE ROOF DRAINAGE
 CALCULATIONS. THIS WAS OVERLOOKED IN FIRST REVIEW.2010
 FBC -PLUMBING SECS.1106.2 & 1106.3.
 18) THE PLUMBING DRAWINGS REFER TO THE ARCHITECTURAL
 PLANS FOR DOWNSPOUT DETAILS. I COULD NOT FIND ANY
 DOWNSPOUT DETAILS IN THE ARCHITECTURAL PLANS. CLARIFY.
 19) NOTE #14 ON THE ENLARGED ARCHITECTURAL FLOOR PLANS
 REFER TO THE ARCHITECTURAL AND PLUMBING DRAWINGS FOR
 DETAILS FOR THE GUTTERS AND DOWNSPOUTS. I COULD NOT
 FIND ANY DETAILS ON ANY OF THESE PLANS. CLARIFY.
 20) AS UPLOADED, ALL THE PLUMBING DRAWINGS ARE LABELED
 AS "P' DRAWINGS. THERE IS NO WAY TO DISCERN WHICH
 DRAWINGS ARE FOR BUILDING #1, #2 OR #3. PLEASE SUBMIT
 ONLY THE DRAWINGS THAT ARE APPLICABLE TO THIS PERMIT
 AND THIS BUILDING. THIS APPLIES TO ALL THE DRAWINGS.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 21) SEVERAL RESPONSES ON THE PLAN REVIEW COMMENT STATE
 "REFER TO REVISED ROOF PLAN" OR "SEE ARCHITECTURAL
 DRAWINGS." THESE RESPONSES ARE VAGUE AND
 INCONCLUSIVE.PLEASE PROVIDE THE SPECIFIC DRAWING NUMBER
 WHEN REFERENCING PLAN SHEETS.. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW