Plan Review Notes
Plan Review Notes For Permit 15050262
Permit Number 15050262
Review Stop M
Sequence Number 2
Notes
Date Text
2015-08-05 16:11:282ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15050262
 8/5/15
  
 1) REFERENCE COMMENT #1 FROM THE 1ST REVIEW: THE
 REVISED ENERGY CALCULATIONS WERE NOT SUBMITTED.
 2) REFERENCE COMMENT #2 FROM THE 1ST REVIEW: THE
 REQUESTED AC COOLING AND HEATING LOAD CALCULATIONS WERE
 NOT SUBMITTED.
 3) REFERENCE COMMENT #3 FROM THE 1ST REVIEW: THE
 REQUIRED EXHAUST FOR THE GROUND FLOOR TRASH ROOM IS NOT
 SHOWN ON THE PLAN. REVISE THE FAN SCHEDULE ON SHEET
 M-3.00 TO INCLUDE THE TRASH ROOM EXHAUST FANS ON THE
 OTHER FLOORS, AND SHOW HOW MAKEUP AIR IS BEING
 SUPPLIED.
 4) REFERENCE COMMENTS #5 & 6 FROM THE 1ST REVIEW: THE
 SPECS FOR THE RINNAI WATER HEATER WERE NOT SUBMITTED.
 5) REFERENCE COMMENT #10: PLEASE REMOVE SHEET A-10.08
 SHOWING THE HILTI FIRESTOPPING DETAILS, THE ENGINEER OF
 RECORD HAS INDICATED IN HIS NARRATIVE RESPONSE THAT HE
 WILL BE USINGTREMCO.
 6) REFERENCE COMMENT #12: THE RESPONSE NARRATIVE FROM
 THE ENGINEER IS STATING THAT THE CONDENSER TIE-DOWN
 DETAILS ARE IN THE STRUCTURAL DRAWINGS. PLEASE INDICATE
 ON WHICH PLAN SHEET THE DETAILS CAN BE FOUND.
 7) REFERENCE COMMENT #13: 2ND REQUEST FOR PRODUCT DATA
 SHEETS, PRODUCT APPROVALS AND NOA'S TO BE SUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  