| Plan Review Notes For Permit 15050262 |
| Permit Number |
15050262 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-08-05 16:11:28 | 2ND REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15050262 | | | 8/5/15 | | | | | | 1) REFERENCE COMMENT #1 FROM THE 1ST REVIEW: THE | | | REVISED ENERGY CALCULATIONS WERE NOT SUBMITTED. | | | 2) REFERENCE COMMENT #2 FROM THE 1ST REVIEW: THE | | | REQUESTED AC COOLING AND HEATING LOAD CALCULATIONS WERE | | | NOT SUBMITTED. | | | 3) REFERENCE COMMENT #3 FROM THE 1ST REVIEW: THE | | | REQUIRED EXHAUST FOR THE GROUND FLOOR TRASH ROOM IS NOT | | | SHOWN ON THE PLAN. REVISE THE FAN SCHEDULE ON SHEET | | | M-3.00 TO INCLUDE THE TRASH ROOM EXHAUST FANS ON THE | | | OTHER FLOORS, AND SHOW HOW MAKEUP AIR IS BEING | | | SUPPLIED. | | | 4) REFERENCE COMMENTS #5 & 6 FROM THE 1ST REVIEW: THE | | | SPECS FOR THE RINNAI WATER HEATER WERE NOT SUBMITTED. | | | 5) REFERENCE COMMENT #10: PLEASE REMOVE SHEET A-10.08 | | | SHOWING THE HILTI FIRESTOPPING DETAILS, THE ENGINEER OF | | | RECORD HAS INDICATED IN HIS NARRATIVE RESPONSE THAT HE | | | WILL BE USINGTREMCO. | | | 6) REFERENCE COMMENT #12: THE RESPONSE NARRATIVE FROM | | | THE ENGINEER IS STATING THAT THE CONDENSER TIE-DOWN | | | DETAILS ARE IN THE STRUCTURAL DRAWINGS. PLEASE INDICATE | | | ON WHICH PLAN SHEET THE DETAILS CAN BE FOUND. | | | 7) REFERENCE COMMENT #13: 2ND REQUEST FOR PRODUCT DATA | | | SHEETS, PRODUCT APPROVALS AND NOA'S TO BE SUBMITTED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|