2015-08-13 09:04:47PERMIT #15050261 - 838 ADAMS STREET (66 UNITS)
 PERMIT #15050262 - 1851 DIVISION AVENUE (29 UNITS)
 PERMIT #15050263 - 1807 DIVISION AVENUE (25 UNITS)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: DESIGN TEAM INDICATED, "MEP ENGINEER
 HAS ANSWERED IN A SEPARATE LETTER"; HOWEVER, THIS
 LETTER IS NOT LOCATED IN THE RESUBMITTAL DOCUMENTS FOR
 THE 2ND REVIEW.
 ORIGINAL COMMENT - THE FIRE DEPARTMENT REQUIRES PLANS
 AND PERMITS FOR ALL CONSTRUCTION RELATED TRAILERS AND
 MODULAR BUILDINGS. ADDITIONALLY PER NFPA 241- STANDARD
 FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND
 DEMOLITION OPERATIONS, SECTION 4.2: TEMPORARY OFFICES,
 TRAILERS, AND OTHER FACILITIES OF COMBUSTIBLE
 CONSTRUCTION OR HOUSING COMBUSTIBLE CONTENTS SHALL BE
 SEPARATED FROM ADJACENT BUILDINGS, TRAILERS OR
 STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. PER TABLE
 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 RESPONSE COMMENT: DESIGN TEAM INDICATED, "MEP ENGINEER
 HAS ANSWERED IN A SEPARATE LETTER"; HOWEVER, THIS
 LETTER IS NOT LOCATED IN THE RESUBMITTAL DOCUMENTS FOR
 THE 2ND REVIEW.
 ORIGINAL COMMENT - PER NFPA 241 SECTION 4.2.2:
 DETACHMENT BETWEEN TEMPORARY STRUCTURES, ADEQUATE
 TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND PORTABLE
 EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET PM-1: PER SECTION 18.2.3.5.3
 (NFPA 1), FIRE LANES SHALL BE MARKED WITH FREESTANDING
 SIGNS READING, "FIRE LANE - NO PARKING BY ORDER OF THE
 FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE
 BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF
 SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS
 SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED
 A MAXIMUM OF 60 FEET APART. FIRE DEPARTMENT ACCESS
 ROADS SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE
 APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL
 HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND
 AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET WS-1: FIRE MAINS SUPPLYING TWO
 OR MORE FIRE HYDRANTS WILL NEED TO BE LOOPED AND WILL
 NOT BE PERMITTED TO TERMINATE AT A DEAD END BLOWOFF
 CAP.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET WS-1: THE FIRELINE BACKFLOW
 PREVENTERS SHALL COMPLY WITH NFPA 24 SECTION 6.2.1, ALL
 CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 RESPONSE COMMENT - ONLY ONE EXIT SIGN ADDED. DUAL
 SIGNAGE IS NEEDED FOR EXIT TRAVEL IN BOTH DIRECTIONS TO
 TWO SEPARATE EXITS.
 ORIGINAL COMMENT - SHEET E2.01A & SHEET E2.01B: PROVIDE
 TWO ADDITIONAL EXIT SIGNS IN THE EXIT ACCESS CORRIDOR
 NEAR COLUMN INTERSECTION B.1/1.2. TYPICAL ALL LEVELS.
  
 RESPONSE COMMENT - ONLY ONE EXIT SIGN ADDED. DUAL
 SIGNAGE IS NEEDED FOR EXIT TRAVEL IN BOTH DIRECTIONS TO
 TWO SEPARATE EXITS.
 ORIGINAL COMMENT - SHEET E2.07: PROVIDE TWO ADDITIONAL
 EXIT SIGNS IN THE EXIT ACCESS CORRIDOR NEAR COLUMN
 INTERSECTION A.4/8.1. TYPICAL ALL LEVELS.
  
 RESPONSE COMMENT - REVIEW COMMENT NOT ADDRESSED;
 REVISED PLANS NOT SUBMITTED.
 ORIGINAL COMMENT - SHEET E2.12: PROVIDE TWO ADDITIONAL
 EXIT SIGNS IN THE EXIT ACCESS CORRIDOR NEAR COLUMN
 INTERSECTION A.4/8.1. TYPICAL ALL LEVELS.
  
 RESPONSE COMMENT: SHEET FP2.04 NOW INCLUDES A STATEMENT
 THAT SPRINKLERS ARE BEING REQUIRED BY THE LOCAL
 JURISDICTION. THIS IS AN INCORRECT STATEMENT;
 COMBUSTIBLE CONCEALED ROOF SPRINKLER PROTECTION IS
 REQUIRED BY NFPA 13 SECTION 8.15. SHEET FP2.05 HAS NOT
 BEEN CORRECTED AT ALL.
 ORIGINAL COMMENT - SHEET FP2.04 & FP2.05: PLAN
 INDICATES NO SPRINKLER PROTECTION FOR THE
 NON-ACCESSIBLE TRUSS SPACE; CONTRARY TO NFPA 13 SECTION
 8.15. INDICATE A CODE REFERENCE PERMITTING THIS
 COMBUSTIBLE CONCEALED SPACE FROM BEING PROTECTED BY
 FIRE SPRINKLERS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE