| 2015-06-28 08:32:58 | THIS REVIEW WAS DONE UNDER PERMIT #15050261 WHICH HAD |
| | THE PLANS FOR ALL THREE BUILDINGS. SOME OF THE COMMENTS |
| | MAY ONLY BE APPLICABLE TO BUILDING #1 AND DO NOT APPLY |
| | TO BUILDINGS #2 & #3. |
| | |
| | |
| | 1) THE URINAL IN THE MEN'S RESTROOM ON THE FIRST FLOOR |
| | BY THE CLUB ROOM IS WITHIN THE LINE OF SIGHT WITH THE |
| | DOOR OPEN. SEE SHT.A5.06 - DETAIL C - PRIVACY SHALL BE |
| | PROVIDED IN ACCORDANCE WITH 2010 FPC SEC.310.5. |
| | 2) RAINWATER DOWNSPOUTS SHALL DISCHARGE A MINIMUM OF |
| | ONE FOOT AWAY FROM THE STRUCTURE SIDEWALL PER 2010 FBC |
| | 1503.7. |
| | 3) THE ROOF DRAINAGE CALCULATIONS FOR THE DESIGN OF THE |
| | STORMWATER SYSTEM SHALL INCLUDE ONE-HALF OF THE AREA OF |
| | ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF |
| | PER THE 2010 FPC SEC.1106.4. SHOW THAT THIS HAS BEEN |
| | DONE WITH THE SIZING OF THE STORM DRAINAGE SYSTEM. |
| | 4) SHT. A2.05 - SCUPPER CALCULATION - SEE ROOF SQ.FT. |
| | W/PARAPET.- THE SQUARE FOOTAGE CANNOT BE READ. CLARIFY. |
| | 5) SHT. A2.05 - THE SCUPPER CALCULATION SHOWS 1551 SQ. |
| | FT. FOR SCUPPER #1 & 1282 SQ. FT. FOR SCUPPER #2, AND |
| | ALSO AT THE BOTTOM OF THE TABLE IT STATES HORIZONTAL |
| | PROJECTED ROOF AREA -1008 SQ. FT. PLEASE CLARIFY. IS |
| | THIS A DISCREPANCY? |
| | 6) SHT. A2.05 - SHOW THE LOCATION OF THE SCUPPERS ON |
| | THE PLAN AND THE LOCATION OF RWL-1 & RWL-2. WPB AMEND. |
| | TO 2010 FBC SEC. 107.2.1. |
| | 7) SUBMIT GUTTER CALCULATIONS FOR THE GABLE END GUTTERS |
| | AND DOWNSPOUTS. COMPLY W/ 2010 FPC SEC. 1106.6 & |
| | 1106.7. |
| | 8) SHT.A2.10 - THIS BUILDING HAS TWO LOWER ROOFS BUT |
| | THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK. |
| | CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER |
| | ROOFS AND SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE |
| | SCUPPER CALCULATIONS. |
| | 9) SHT. A2.15 - THIS BUILDING HAS TWO LOWER ROOFS BUT |
| | THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK. |
| | CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER |
| | ROOFS AND SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE |
| | SCUPPER CALCULATIONS. |
| | 10) SHT. P1.00 - SHOWS A 2" WATER SERVICE TO BUILDING |
| | #2 AND SHT. WS-1 SHOWS A 4" WATER SERVICE. CLARIFY. |
| | 11) SHT. P1.00 - SHOW THE TERMINATION POINTS OF THE |
| | STORM AND CONDENSATE DRAINS ON THE PLANS. WPB AMEND. TO |
| | 2010 FBC SEC.107.2.1. |
| | 12) SHT. P2.00 - PLANS REFER TO THE CIVIL DRAWINGS FOR |
| | THE CONTINUATION OF THE STORM AND CONDENSATE DRAINS. |
| | THESE LINES ARE NOT SHOWN ON THE CIVIL DRAWINGS. |
| | CLARIFY. |
| | 13) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE OIL |
| | SMART PUMP SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 14) AIR CHAMBERS ARE NOT PERMITTED FOR WATER HAMMER. |
| | DELETE ALL REFERENCE ON THE PLUMBING PLANS TO AIR |
| | CHAMBERS. A WATER HAMMER ARRESTOR SHALL BE INSTALLED |
| | WHERE QUICK ?CLOSING VALVES ARE UTILIZED. FPC |
| | SEC.604.9. |
| | 15) SHT. P4.00 - SHOW THE TONNAGE OF THE EQUIPMENT ON |
| | THE CONDENSATE RISER. COMPLY W/ TABLE 314.2.2. OF 2010 |
| | FPC |
| | 16) SUBMIT THE MANUFACTURER SPECIFICATIONS FOR THE |
| | TANKLESS WATER HEATERS. WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1. |
| | 17) SHOW THE LOCATION OF ALL THE GAS VENTS FROM THE |
| | TANKLESS WATER HEATERS. |
| | 18) SUBMIT DETAILS ON THE DOMESTIC WATER PUMP PACKAGE. |
| | WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| 2015-06-27 12:26:49 | REVIEW NOT COMPLETE. |