Plan Review Notes
Plan Review Notes For Permit 15050262
Permit Number 15050262
Review Stop P
Sequence Number 1
Notes
Date Text
2015-06-28 08:32:58THIS REVIEW WAS DONE UNDER PERMIT #15050261 WHICH HAD
 THE PLANS FOR ALL THREE BUILDINGS. SOME OF THE COMMENTS
 MAY ONLY BE APPLICABLE TO BUILDING #1 AND DO NOT APPLY
 TO BUILDINGS #2 & #3.
  
  
 1) THE URINAL IN THE MEN'S RESTROOM ON THE FIRST FLOOR
 BY THE CLUB ROOM IS WITHIN THE LINE OF SIGHT WITH THE
 DOOR OPEN. SEE SHT.A5.06 - DETAIL C - PRIVACY SHALL BE
 PROVIDED IN ACCORDANCE WITH 2010 FPC SEC.310.5.
 2) RAINWATER DOWNSPOUTS SHALL DISCHARGE A MINIMUM OF
 ONE FOOT AWAY FROM THE STRUCTURE SIDEWALL PER 2010 FBC
 1503.7.
 3) THE ROOF DRAINAGE CALCULATIONS FOR THE DESIGN OF THE
 STORMWATER SYSTEM SHALL INCLUDE ONE-HALF OF THE AREA OF
 ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF
 PER THE 2010 FPC SEC.1106.4. SHOW THAT THIS HAS BEEN
 DONE WITH THE SIZING OF THE STORM DRAINAGE SYSTEM.
 4) SHT. A2.05 - SCUPPER CALCULATION - SEE ROOF SQ.FT.
 W/PARAPET.- THE SQUARE FOOTAGE CANNOT BE READ. CLARIFY.
 5) SHT. A2.05 - THE SCUPPER CALCULATION SHOWS 1551 SQ.
 FT. FOR SCUPPER #1 & 1282 SQ. FT. FOR SCUPPER #2, AND
 ALSO AT THE BOTTOM OF THE TABLE IT STATES HORIZONTAL
 PROJECTED ROOF AREA -1008 SQ. FT. PLEASE CLARIFY. IS
 THIS A DISCREPANCY?
 6) SHT. A2.05 - SHOW THE LOCATION OF THE SCUPPERS ON
 THE PLAN AND THE LOCATION OF RWL-1 & RWL-2. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 7) SUBMIT GUTTER CALCULATIONS FOR THE GABLE END GUTTERS
 AND DOWNSPOUTS. COMPLY W/ 2010 FPC SEC. 1106.6 &
 1106.7.
 8) SHT.A2.10 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE
 SCUPPER CALCULATIONS.
 9) SHT. A2.15 - THIS BUILDING HAS TWO LOWER ROOFS BUT
 THE ROOF DRAIN CALCULATIONS ON THE SHEET ARE BLANK.
 CLARIFY. SUBMIT ROOF DRAIN CALCULATIONS FOR THE LOWER
 ROOFS AND SHOW THE LOCATION OF THE SCUPPERS AND PROVIDE
 SCUPPER CALCULATIONS.
 10) SHT. P1.00 - SHOWS A 2" WATER SERVICE TO BUILDING
 #2 AND SHT. WS-1 SHOWS A 4" WATER SERVICE. CLARIFY.
 11) SHT. P1.00 - SHOW THE TERMINATION POINTS OF THE
 STORM AND CONDENSATE DRAINS ON THE PLANS. WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 12) SHT. P2.00 - PLANS REFER TO THE CIVIL DRAWINGS FOR
 THE CONTINUATION OF THE STORM AND CONDENSATE DRAINS.
 THESE LINES ARE NOT SHOWN ON THE CIVIL DRAWINGS.
 CLARIFY.
 13) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE OIL
 SMART PUMP SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 14) AIR CHAMBERS ARE NOT PERMITTED FOR WATER HAMMER.
 DELETE ALL REFERENCE ON THE PLUMBING PLANS TO AIR
 CHAMBERS. A WATER HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK ?CLOSING VALVES ARE UTILIZED. FPC
 SEC.604.9.
 15) SHT. P4.00 - SHOW THE TONNAGE OF THE EQUIPMENT ON
 THE CONDENSATE RISER. COMPLY W/ TABLE 314.2.2. OF 2010
 FPC
 16) SUBMIT THE MANUFACTURER SPECIFICATIONS FOR THE
 TANKLESS WATER HEATERS. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 17) SHOW THE LOCATION OF ALL THE GAS VENTS FROM THE
 TANKLESS WATER HEATERS.
 18) SUBMIT DETAILS ON THE DOMESTIC WATER PUMP PACKAGE.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  