2015-06-17 10:16:061ST REVIEW: FBC 2010 MECHANICAL- 6/17/15
 PERMIT # 15050262
 SILVER PALMS PLACE- BLDG. #3
  
 1) THE ENERGY CALCULATIONS FOR BUILDING #3 DO NOT
 INCLUDE DATA AND COMPLIANCE INFO FOR AC-1 (TRASH ROOM
 ON GROUND FLOOR).
 2) THE REQUIRED AC LOAD CALCULATIONS WERE NOT INCLUDED
 WITH THE SUPPORTING DOCUMENTS- SECTIONS 101.5 AND
 503.2.1 FBC-10 ENERGY CONSERVATION.
 3) SHEETS M1.11- M1.14: EXHAUST SYSTEMS AT A RATE OF
 1.00 CFM PER SF ARE REQUIRED FOR THE TRASH ROOMS AND
 THE TRASH CHUTES SHOWN ON THE GROUND THRU 4TH FLOORS-
 TABLE 6-4 ASHRAE 62.1- 07. PLEASE REVISE THE PLANS
 ACCORDINGLY, AND CLARIFY WHY ONLY THE GROUND FLOOR
 TRASH ROOM IS BEING CONDITIONED BY AC-1.
 4) M2.00 & M2.01: THE DRYER BOOSTER FANS SHOWN IN UNITS
 A, AND A & C ACCESSIBLE UNITS ARE PROHIBITED BY THE
 CITY OF WEST PALM BEACH FIRE RESCUE.
 5) M2.00 & M2.01: THE RINNAI DIRECT GAS VENTS SHALL BE
 LISTED FOR PLENUM INSTALLATIONS PER SECTION 503.2.3
 FBC-10 FUEL GAS. SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE WATER HEATER AND VENTING SYSTEM REVIEWED AND
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD.
 6) M2.00 & M2.01: PLACE A NOTE INDICATING THE REQUIRED
 CLEARANCE DISTANCES FOR THE THRU-WALL TERMINATION OF
 THE RINNAI DIRECT CONCENTRIC VENT.
 7) M3.00: PLEASE REMOVE OR REVISE ALL HVAC NOTES
 REFERENCING CODE SECTIONS FROM THE FBC-10 RESIDENTIAL
 CODE. THE PROPOSED PROJECT IS REGULATED BY THE FBC-10
 BUILDING CODES.
 8) M3.00: THE HVAC REFRIGERANT PIPING NOTES SHALL
 INDICATE THE PIPING INSULATION IS PLENUM RATED PER
 SECTION 602.2.1 FBC-10.
 9) M1.15: PROVIDE A SEQUENCE OF OPERATION FOR THE
 MOTORIZED EXHAUST DAMPER AT THE SIDEWALL OF THE
 ELEVATOR SHAFT.
 10) PIPE PENETRATION SEALS: SHEETS A.10.06 & A10.07
 SHOW TREMCO FIRE STOPPING DETAILS, AND SHEET A.10.08
 SHOWS HILTI. PLEASE SELECT ONE SYSTEM OR THE OTHER FOR
 THE AC REFRIGERANT AND CONDENSATE PIPINGS.
 11) PROVIDE A TYPICAL SECTION CUT FOR THE AHU'S IN THE
 PLENUM CLOSET INDICATING CLOSET CONSTRUCTION MATERIALS,
 CLEARANCES DISTANCE MEASUREMENTS AROUND THE UNITS,
 REFRIGERANT PIPING RUNS, AND PRIMARY AND SECONDARY
 CONDENSATE DISPOSAL DETAILS PER SECTION 307 FMC-10 (
 INCLUSIVE OF ALL SUB-SECTIONS).
 12) M3.01: WIND LOAD DESIGN PRESSURE CALCULATIONS AND
 TIE-DOWN ENGINEERING ARE REQUIRED FOR ANCHORING THE
 CONDENSER STANDS AND CONDENSER UNIS TO THE ROOF
 STRUCTURE- SECTION 301.12 FMC-10, AND SECTION 1609
 FBC-10 BUILDING. PLEASE REVISE THE DETAIL ACCORDINGLY
 AND CORRECT THE 150 MPH WIND LOAD SPECIFICATION.
 13) PROVIDE A SUBMITTAL PACKAGE WITH ALL DOCUMENTS
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD. PLEASE INCLUDE NOA'S, PRODUCT APPROVALS, AND
 MANUFACTURER'S SPECIFICATIONS FOR THE CONDENSER STANDS,
 THE EXHAUST AND O/A INTAKE FANS, THE O/A MOTORIZED
 DAMPERS, THE EXHAUST AND INTAKE WALL LOUVERS, THE
 ELEVATOR SHAFT MOTORIZED DAMPER, THE AC SYSTEMS, THE
 GAS WATER HEATER AND VENT SYSTEM, AND THE REFRIGERANT
 PIPE INSULATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER