| 2015-06-19 09:35:32 | BECAUSE YOU ARE USING THE SAME PLANS FOR THIS AS FOR |
| | PERMIT #15050263, THE ELECTRICAL PLAN REVIEW COMMENTS |
| | ARE EXACTLY THE SAME. |
| | |
| | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER FOR THE CITY OF WEST PALM BEACH HAVE COMPLETED |
| | THE REVIEW OF THE ABOVE MENTIONED PERMIT. BELOW ARE THE |
| | COMMENTS WITH REGARDS TO THE CORRECTIONS NOTED. AS THIS |
| | WAS A PAGE BY PAGE REVIEW, YOU WILL NOTICE REPEATED |
| | COMMENTS ON EACH RESPECTIVE PAGE. EACH OF THE COMMENTS |
| | NOTED HAVE BEEN CLOUDED OR IN SOME WAY IDENTIFIED IN A |
| | RED LAYER ON THE DIGITAL PLANS WHICH WERE REVIEWED |
| | USING PROJECTDOX. |
| | |
| | PG. E1.00, E.4.00A |
| | THE FOLLOWING NOTE SHALL BE ADDED WITH REGARDS TO THE |
| | BACKGROUND AUDIO. |
| | 1. ALL BACKGROUND AUDIO SHALL BE MUTED VIA THE FACP IN |
| | THE EVENT OF AN ALARM CONDITION. |
| | PG. E1.10 |
| | THOUGH THIS IS A PHOTOMETRIC SHEET, THE FOLLOWING IS A |
| | SUGGESTION AND MAYBE A COMMENT WHICH MAY BE ADDED |
| | SOMEWHERE ON THE PLANS TO AVOID PROBLEMS LATER. |
| | 1. POOL CONTRACTOR TO COORDINATE W/GC TO AVOID FUTURE |
| | ENCROACHMENT INTO NEC REGULATED POOL AREA REQUIRED BY |
| | NEC 680.10 WHICH PROHIBITS ANY NON-POOL RELATED |
| | RACEWAYS WITHIN 5' OF POOL'S EDGE. |
| | PG. E2.01A, E2.01B, E2.02A, E2.02B, E2.03A, E2.03B, |
| | E2.07, E2.08, E2.12, E2.13, |
| | 1. EXIT LIGHTING REQUIRED. THIS LIGHT SHALL BE VISIBLE |
| | FROM ALL PATHS OF TRAVEL OF THE CORRIDOR. |
| | PG. E2.01C, E2.02C, E2.03C, E2.04C, E2.07A, E2.08A, |
| | E2.09A, E2.12A, E2.13A, E2.14A |
| | 1. ON EVERY FLOOR ABOVE THE GROUND LEVEL, THE STAIRS |
| | ARE A PART OF THE EMERGENCY EGRESS, AND SHOULD BE |
| | ILLUMINATED ACCORDINGLY AND INCLUDED AS SUCH. |
| | PG. E2.04A, |
| | 1. EXIT LIGHTING REQUIRED. THIS LIGHT SHALL BE VISIBLE |
| | FROM ALL PATHS OF TRAVEL OF THE CORRIDOR. |
| | 2. EXIT LIGHT REQUIRED ON THE ROOF SIDE OF THESE DOORS. |
| | DEPENDENT ON SITE CONDITIONS ADDITIONAL LIGHTS MAY BE |
| | REQUIRED. |
| | 3. THIS SPACE REQUIRES LIGHTING AS PER NEC |
| | 210.70(A)(3). THERE SHALL BE EMERGENCY LIGHTING FOR |
| | EMERGENCY EGRESS AS WELL. |
| | PG. E2.04B, E2.09, E2.14 |
| | 1. EXIT LIGHTING REQUIRED. THIS LIGHT SHALL BE VISIBLE |
| | FROM ALL PATHS OF TRAVEL OF THE CORRIDOR. |
| | 2. EXIT LIGHT REQUIRED ON THE ROOF SIDE OF THESE DOORS. |
| | DEPENDENT ON SITE CONDITIONS ADDITIONAL LIGHTS MAY BE |
| | REQUIRED. |
| | 3. THIS SPACE REQUIRES LIGHTING AS PER NEC |
| | 210.70(A)(3). THERE SHALL BE EMERGENCY LIGHTING FOR |
| | EMERGENCY EGRESS AS WELL. |
| | 4. THIS UNIT IS FURTHER THAN THE ALLOWABLE DISTANCE |
| | FROM THE SERVICE OUTLET PER NEC 210.63. |
| | PG. E2.06A, E2.11A, |
| | 1. THOUGH ON THE GROUND FLOOR, THESE STAIRS SHALL BE |
| | CONSIDERED A PART OF THE EMERGENCY EGRESS. |
| | PG. E3.00 |
| | 1. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM |
| | THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE |
| | A BATHROOM W/O A SHOWER. |
| | PG. E3.01, E3.02 (TYPICAL TO BOTH UNITS) |
| | 1. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM |
| | THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE |
| | A BATHROOM W/O A SHOWER. |
| | 2. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM |
| | THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE |
| | A BATHROOM W/O A SHOWER. |
| | 3. NEC 210.52(C)(4) SEPARATES THE AREA WITH THE SINK |
| | THUS REQUIRING AN OUTLET ON THIS END OF THE COUNTER TOP |
| | 4. NEC 210.52.(A)(2) REQUIRES AN OUTLET ON A WALL SPACE |
| | OF 2' OR LARGER |
| | 5. NEC 210.70(A)(3) A LIGHTING OUTLET CONTROLLED BY A |
| | WALL SWITCH SHALL BE INSTALLED IN SPACES USED FOR |
| | STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICING. THE |
| | LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE |
| | EQUIPMENT REQUIRING SERVICING. THE CLOSET IN WHICH THE |
| | SMC BOX/CABINET IS IN SHALL HAVE THE REQUIRED LIGHTING. |
| | PG. E3.03 (TYPICAL TO BOTH UNITS) |
| | 1. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM |
| | THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE |
| | A BATHROOM W/O A SHOWER. |
| | 2. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM |
| | THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE |
| | A BATHROOM W/O A SHOWER. |
| | 3. NEC 210.52(C)(4) SEPARATES THE AREA WITH THE SINK |
| | THUS REQUIRING AN OUTLET ON THIS END OF THE COUNTER TOP |
| | 4. NEC 210.70(A)(3) A LIGHTING OUTLET CONTROLLED BY A |
| | WALL SWITCH SHALL BE INSTALLED IN SPACES USED FOR |
| | STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICING. THE |
| | LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE |
| | EQUIPMENT REQUIRING SERVICING. THE CLOSET IN WHICH THE |
| | SMC BOX/CABINET IS IN SHALL HAVE THE REQUIRED LIGHTING. |
| | 5. HERE WE HAVE A PROBLEM: |
| | A) FBC-R 314.3(2) REQUIRES THAT THE SMOKE DETECTOR |
| | OUTSIDE THE BEDROOM BE IN THE IMMEDIATE AREA. |
| | B) NFPA 72 SECTION 29.8.3.4(6) REQUIRES THAT A SMOKE |
| | DETECTOR INSTALLED INSIDE OF OR WITHIN 3' OF THE DOOR |
| | OF THE BATHROOM BE LISTED FOR THE PURPOSE. |
| | THEREFORE THERE SHALL BE A PROPERLY LISTED SMOKE |
| | DETECTOR PLACED IN THIS AREA TO PROTECT THESE TWO |
| | BEDROOMS |
| | PG. E4.00B |
| | 1. EXIT LIGHT ILLUMINATED ON BOTH SIDES REQUIRED HERE. |
| | 2. EXIT LIGHT DUAL ARROWS REQUIRED HERE |
| | 3. THIS AREA IS PART OF THE EMERGENCY EGRESS AND THUS |
| | SHALL BE ILLUMINATED AS SUCH. |
| | PG. E4.01, E4.03, E4.05, E4.06, |
| | 1. INCORRECTLY MENTIONED ARC-FLASH (ARC-FLASH |
| | PROTECTION AS PER NEC 110.16) |
| | PG. E4.07, E4.08, |
| | 1. THERE APPEARS TO BE CLEARANCE ISSUES IN VIOLATION OF |
| | NEC 110.26 BETWEEN THE OUTLET ON THE WALL AND THE |
| | COMPACTING APPARATUS. |
| | PG. E5.01, E5.02, E5.03, |
| | 1. AS PER NEC 230.8, UNDERGROUND SERVICE RACEWAYS SHALL |
| | BE SEALED AS INDICATED IN 300.5. |
| | 2. ALL SPARE UNDERGROUND RACEWAYS SHALL BE SEALED AS |
| | WELL. |
| | 3. PANELBOARDS & METER SOCKETS SHALL BE MARKED AS |
| | INDICATED BY NEC 110.16 FOR ARC-FLASH PROTECTION. |
| | PG. E5.06 |
| | 1. THE QUOTED SECTION DOES NOT EXIST IN THE 2008 |
| | EDITION OF THE NEC. PLEASE CORRECT ACCORDINGLY |
| | PG. E6.00, E6.01, |
| | 1. FIRE ALARM CIRCUITS SHALL COMPLY WITH BOTH NEC 760 & |
| | NFPA 72, SECTION 10.6.5 |
| | 2. SEE PG. E6.02, FOR PANEL ?CH? SCHEDULE. |
| | 3. CORRECT THIS LABEL DESIGNATION LABEL |
| | 4. PER NEC 4322.52, ELECTRIC DRINKING FOUNTAINS SHALL |
| | BE ON A GFI CIRCUIT (PG. E6.02) |
| | PG. FA1.00, FA2.00 |
| | 1. SEPARATE PERMIT & SUBMITTAL REQUIRED FOR FIRE ALARM |
| | WORK |
| | |