Plan Review Notes
Plan Review Notes For Permit 15050262
Permit Number 15050262
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-19 09:35:32BECAUSE YOU ARE USING THE SAME PLANS FOR THIS AS FOR
 PERMIT #15050263, THE ELECTRICAL PLAN REVIEW COMMENTS
 ARE EXACTLY THE SAME.
  
 PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER FOR THE CITY OF WEST PALM BEACH HAVE COMPLETED
 THE REVIEW OF THE ABOVE MENTIONED PERMIT. BELOW ARE THE
 COMMENTS WITH REGARDS TO THE CORRECTIONS NOTED. AS THIS
 WAS A PAGE BY PAGE REVIEW, YOU WILL NOTICE REPEATED
 COMMENTS ON EACH RESPECTIVE PAGE. EACH OF THE COMMENTS
 NOTED HAVE BEEN CLOUDED OR IN SOME WAY IDENTIFIED IN A
 RED LAYER ON THE DIGITAL PLANS WHICH WERE REVIEWED
 USING PROJECTDOX.
  
 PG. E1.00, E.4.00A
 THE FOLLOWING NOTE SHALL BE ADDED WITH REGARDS TO THE
 BACKGROUND AUDIO.
 1. ALL BACKGROUND AUDIO SHALL BE MUTED VIA THE FACP IN
 THE EVENT OF AN ALARM CONDITION.
 PG. E1.10
 THOUGH THIS IS A PHOTOMETRIC SHEET, THE FOLLOWING IS A
 SUGGESTION AND MAYBE A COMMENT WHICH MAY BE ADDED
 SOMEWHERE ON THE PLANS TO AVOID PROBLEMS LATER.
 1. POOL CONTRACTOR TO COORDINATE W/GC TO AVOID FUTURE
 ENCROACHMENT INTO NEC REGULATED POOL AREA REQUIRED BY
 NEC 680.10 WHICH PROHIBITS ANY NON-POOL RELATED
 RACEWAYS WITHIN 5' OF POOL'S EDGE.
 PG. E2.01A, E2.01B, E2.02A, E2.02B, E2.03A, E2.03B,
 E2.07, E2.08, E2.12, E2.13,
 1. EXIT LIGHTING REQUIRED. THIS LIGHT SHALL BE VISIBLE
 FROM ALL PATHS OF TRAVEL OF THE CORRIDOR.
 PG. E2.01C, E2.02C, E2.03C, E2.04C, E2.07A, E2.08A,
 E2.09A, E2.12A, E2.13A, E2.14A
 1. ON EVERY FLOOR ABOVE THE GROUND LEVEL, THE STAIRS
 ARE A PART OF THE EMERGENCY EGRESS, AND SHOULD BE
 ILLUMINATED ACCORDINGLY AND INCLUDED AS SUCH.
 PG. E2.04A,
 1. EXIT LIGHTING REQUIRED. THIS LIGHT SHALL BE VISIBLE
 FROM ALL PATHS OF TRAVEL OF THE CORRIDOR.
 2. EXIT LIGHT REQUIRED ON THE ROOF SIDE OF THESE DOORS.
 DEPENDENT ON SITE CONDITIONS ADDITIONAL LIGHTS MAY BE
 REQUIRED.
 3. THIS SPACE REQUIRES LIGHTING AS PER NEC
 210.70(A)(3). THERE SHALL BE EMERGENCY LIGHTING FOR
 EMERGENCY EGRESS AS WELL.
 PG. E2.04B, E2.09, E2.14
 1. EXIT LIGHTING REQUIRED. THIS LIGHT SHALL BE VISIBLE
 FROM ALL PATHS OF TRAVEL OF THE CORRIDOR.
 2. EXIT LIGHT REQUIRED ON THE ROOF SIDE OF THESE DOORS.
 DEPENDENT ON SITE CONDITIONS ADDITIONAL LIGHTS MAY BE
 REQUIRED.
 3. THIS SPACE REQUIRES LIGHTING AS PER NEC
 210.70(A)(3). THERE SHALL BE EMERGENCY LIGHTING FOR
 EMERGENCY EGRESS AS WELL.
 4. THIS UNIT IS FURTHER THAN THE ALLOWABLE DISTANCE
 FROM THE SERVICE OUTLET PER NEC 210.63.
 PG. E2.06A, E2.11A,
 1. THOUGH ON THE GROUND FLOOR, THESE STAIRS SHALL BE
 CONSIDERED A PART OF THE EMERGENCY EGRESS.
 PG. E3.00
 1. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM
 THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE
 A BATHROOM W/O A SHOWER.
 PG. E3.01, E3.02 (TYPICAL TO BOTH UNITS)
 1. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM
 THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE
 A BATHROOM W/O A SHOWER.
 2. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM
 THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE
 A BATHROOM W/O A SHOWER.
 3. NEC 210.52(C)(4) SEPARATES THE AREA WITH THE SINK
 THUS REQUIRING AN OUTLET ON THIS END OF THE COUNTER TOP
 4. NEC 210.52.(A)(2) REQUIRES AN OUTLET ON A WALL SPACE
 OF 2' OR LARGER
 5. NEC 210.70(A)(3) A LIGHTING OUTLET CONTROLLED BY A
 WALL SWITCH SHALL BE INSTALLED IN SPACES USED FOR
 STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICING. THE
 LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE
 EQUIPMENT REQUIRING SERVICING. THE CLOSET IN WHICH THE
 SMC BOX/CABINET IS IN SHALL HAVE THE REQUIRED LIGHTING.
 PG. E3.03 (TYPICAL TO BOTH UNITS)
 1. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM
 THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE
 A BATHROOM W/O A SHOWER.
 2. THIS NOTE SHALL BE AMENDED TO ALSO INCLUDE 36" FROM
 THE TIP OF A CEILING FAN BLADE, & CORRECTED TO EXCLUDE
 A BATHROOM W/O A SHOWER.
 3. NEC 210.52(C)(4) SEPARATES THE AREA WITH THE SINK
 THUS REQUIRING AN OUTLET ON THIS END OF THE COUNTER TOP
 4. NEC 210.70(A)(3) A LIGHTING OUTLET CONTROLLED BY A
 WALL SWITCH SHALL BE INSTALLED IN SPACES USED FOR
 STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICING. THE
 LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE
 EQUIPMENT REQUIRING SERVICING. THE CLOSET IN WHICH THE
 SMC BOX/CABINET IS IN SHALL HAVE THE REQUIRED LIGHTING.
 5. HERE WE HAVE A PROBLEM:
 A) FBC-R 314.3(2) REQUIRES THAT THE SMOKE DETECTOR
 OUTSIDE THE BEDROOM BE IN THE IMMEDIATE AREA.
 B) NFPA 72 SECTION 29.8.3.4(6) REQUIRES THAT A SMOKE
 DETECTOR INSTALLED INSIDE OF OR WITHIN 3' OF THE DOOR
 OF THE BATHROOM BE LISTED FOR THE PURPOSE.
 THEREFORE THERE SHALL BE A PROPERLY LISTED SMOKE
 DETECTOR PLACED IN THIS AREA TO PROTECT THESE TWO
 BEDROOMS
 PG. E4.00B
 1. EXIT LIGHT ILLUMINATED ON BOTH SIDES REQUIRED HERE.
 2. EXIT LIGHT DUAL ARROWS REQUIRED HERE
 3. THIS AREA IS PART OF THE EMERGENCY EGRESS AND THUS
 SHALL BE ILLUMINATED AS SUCH.
 PG. E4.01, E4.03, E4.05, E4.06,
 1. INCORRECTLY MENTIONED ARC-FLASH (ARC-FLASH
 PROTECTION AS PER NEC 110.16)
 PG. E4.07, E4.08,
 1. THERE APPEARS TO BE CLEARANCE ISSUES IN VIOLATION OF
 NEC 110.26 BETWEEN THE OUTLET ON THE WALL AND THE
 COMPACTING APPARATUS.
 PG. E5.01, E5.02, E5.03,
 1. AS PER NEC 230.8, UNDERGROUND SERVICE RACEWAYS SHALL
 BE SEALED AS INDICATED IN 300.5.
 2. ALL SPARE UNDERGROUND RACEWAYS SHALL BE SEALED AS
 WELL.
 3. PANELBOARDS & METER SOCKETS SHALL BE MARKED AS
 INDICATED BY NEC 110.16 FOR ARC-FLASH PROTECTION.
 PG. E5.06
 1. THE QUOTED SECTION DOES NOT EXIST IN THE 2008
 EDITION OF THE NEC. PLEASE CORRECT ACCORDINGLY
 PG. E6.00, E6.01,
 1. FIRE ALARM CIRCUITS SHALL COMPLY WITH BOTH NEC 760 &
 NFPA 72, SECTION 10.6.5
 2. SEE PG. E6.02, FOR PANEL ?CH? SCHEDULE.
 3. CORRECT THIS LABEL DESIGNATION LABEL
 4. PER NEC 4322.52, ELECTRIC DRINKING FOUNTAINS SHALL
 BE ON A GFI CIRCUIT (PG. E6.02)
 PG. FA1.00, FA2.00
 1. SEPARATE PERMIT & SUBMITTAL REQUIRED FOR FIRE ALARM
 WORK
  