| 2015-06-20 10:49:17 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15050262 |
| | ADD: 1851 DIVISION AVE. |
| | CONT: TBD/ TO BE DETERMINED |
| | CONTACT: ALBERT OVIEDO |
| | TEL: (??????? |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. JUNE 20/2015 |
| | SILVER PALM PLACE |
| | BLDG # 3/ 29 UNITS/ 4 STORY/ R2 |
| | |
| | ACTION: DENIED |
| | |
| | THIS REVIEW IS FOR BUILDING # 3 AND DOES NOT INCLUDE |
| | ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING, |
| | SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY |
| | AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION |
| | OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL |
| | NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH |
| | ASSOCIATED COST. |
| | |
| | 1) NOTICE! ART IN PUBLIC PLACES |
| | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO. |
| | 4504-14, AND CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| | |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | |
| | 2A) COMPLIED. ELECTRONIC MEDIA: SUBMITTED AN INDEX. |
| | |
| | 2B) 2A) ELECTRONIC MEDIA: 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN |
| | APPROVED BY THE BUILDING OFFICIAL. THIS PLAN DOES NOT |
| | FOLLOW THE NAMING CONVENTION FOR EACH PAGE WITHIN THE |
| | SET OF PLANS AND SHOULD HAVE BEEN DENIED AT TIME OF |
| | ELECTRONIC SUBMISSION. THE ARCHITECTURAL SHEETS ARE NOT |
| | IN ORDER BECAUSE OF THE NAMING CONVENTION WAS NOT |
| | FOLLOWED, THE A1. SHEETS JUMP TO A-10 SERIES TO A-11 |
| | SERIES THEN TO A-2SERIES, THEY DO NOT FOLLOW THE |
| | SUBMITTED INDEX SHEET!!!!! THE PLANS DO NOT MEET THE |
| | CITY STANDARD FOR ELECTRONIC MEDIA REQUIRED BY THE |
| | ELECTRONIC PLAN REVIEW LIBERIAN, CAROLINE PUELL. PLEASE |
| | CONTACT MS. PUELL AT 805-6659 FOR FURTHER INSTRUCTIONS |
| | AND CLARIFICATIONS. |
| | |
| | 2C) THE ELECTRONIC PLANS SUBMITTED 370 PAGES ARE PLANS |
| | SUBMITTED 3 TIMES FOR 3 BUILDINGS. THE ONE SET OF PLANS |
| | HAS ALL THE BUILDING INFORMATION FOR THE 3 BUILDINGS. |
| | THIS STYLE OF SUBMITTAL IS MORE OF A MASTER, NO |
| | BUILDINGS CAN BE ISSUED UNTIL THE PLANS ARE CODE |
| | COMPLIANT FOR THE WHOLE OF THE PROJECT. THE PLANS |
| | SHOULD HAVE PULLED OUT OF THE SET OF DRAWINGS THAT DID |
| | NOT PERTAIN TO THAT BUILDING AND DETAIL SHEETS, DETAILS |
| | NOT PERTAINING TO THAT BUILDING STRUCK THROUGH. |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| | TO PROVIDE UNIFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE |
| | WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. THIS |
| | CODE SECTION IS FOR RECORD RETENTION BUT THE REALITY OF |
| | THIS IS, THE WAY THESE PLANS WERE SUBMITTED, IT IS VERY |
| | DIFFICULT TO FIND WHERE TO LOOK FOR CODE |
| | COMPLIANCE!!!!!!! |
| | |
| | 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING |
| | FLORIDA S. S. 553.71(7) |
| | ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 3A) THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | THESE FORMS ARE E-MAILED TO CONTACT: ALBERT OVIEDO |
| | E-MAIL ADDRESS: [email protected] |
| | FORMS SENT AT SUN. JUNE 07/2015 08:51 AM. |
| | |
| | 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 3F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| | THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS. |
| | |
| | 3G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 3H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 4) THE PERMIT VALUE OF $3,752,718.00 IS LOW. THIS |
| | REVIEW IS FOR A 4 STORY R2 BUILDING TYPE III-B FOR |
| | BUILDING # 3, THE VALUATION IS FIGURED $118.01 FROM THE |
| | IIC TABLE FEB. 01/ 2015. |
| | CALCULATED VALUE: |
| | BLDG. #3 TYPE III-B 61,409 SQ. FT. X $118.01= |
| | $7,246,876.00 |
| | |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 5) SAFEGUARDS DURING CONSTRUCTION; |
| | 5A) 2010 FBC-B 3306.2 WALKWAYS |
| | 5B) 2010 FBC-B 3306.3 DIRECTIONAL BARRICADES |
| | 5C) 2010 FBC-B CONSTRUCTION RAILINGS. 42 INCHES IN |
| | HEIGHT. |
| | 5D) 2010 FBC-B 3306.5 BARRIERS |
| | 5E) 2010 FBC-B 3309.1 FIRE EXTINGUISHERS |
| | 5F) 2010 FBC-B 3310.1 TEMPORARY LIGHTED STAIRWAY |
| | 5G) 2010 FBC-B 3311.1 / 905.3.1 STANDPIPES SHALL BE |
| | EXTENDED AS CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR |
| | OF THE HIGHEST POINT OF CONSTRUCTION HAVING SECURED |
| | DECKING OR FLOORING. |
| | |
| | 6) THE PERMIT APPLICATION CAME IN AS A TBD, TO BE |
| | DETERMINED. A HOLD WILL BE PUT ON THE ISSUANCE OF THIS |
| | PERMIT TO VERIFY LICENSURE REQUIREMENTS THAT THE |
| | CONTRACTOR HOLDS THE APPROPRIATE LICENSURE FOR A 4 |
| | STORY BUILDING. FLORIDA S. S. 489.113. |
| | |
| | 7) SHEET A-0.01: UNDER THE HEADING CONSTRUCTION TYPE IS |
| | FOUND A BOX CHECKED SPRINKLERS, YES . THIS IS NOT CLEAR |
| | SINCE THERE IS BLDGS. 2 & 3 ON THE SAME LINE AS |
| | BUILDING # 1. THE REAL QUESTION IS WILL THERE BE (2) |
| | TYPES OF FIRE SPRINKLERS, FOR BUILDING # 1 A NFPA 13 IN |
| | COMPLIANCE WITH FBC-B 903.3.1.1 AND WILL BUILDINGS 2 & |
| | 3 HAVE THE SAME TYPE OF FIRE SPRINKLERS OR WILL THEY |
| | HAVE A NFPA 13-R INCOMPLIANCE WITH FBC-B 903.3.1.2. IF |
| | BOTH SYSTEMS ARE GOING TO BE INSTALLED PLEASE LIST THEM |
| | IN THE BUILDING MATRIX AS SUCH. |
| | |
| | 8) SHEET A-1.01; |
| | 8A) DETAILS 3 AND 3.1 THE ACCESSIBLE & STANDARD PARKING |
| | DETAILS AND PARALLEL PARKING STRIPPING DETAILS ARE |
| | GOING TO NEED TO COMPLY WITH 2010 FBC-ACCESSIBILITY |
| | CODE ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF |
| | MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY |
| | BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. SEE |
| | WEST PALM BEACH MUNI-CODE SECTION 94-485 STALL PAINTING |
| | DETAIL. |
| | |
| | 8B) DETAIL # 10. THE FENCE DESIGN IS INDICATED TO MEET |
| | THE FBC-B 2010 ASCE 7-05. PLEASE NOTE THE ASCE -05 WAS |
| | IN THE 2007 FBC-B. THE 2010 FBC-B SECTION 1609. 1.1 THE |
| | DETERMINATION OF WIND USES THE ASCE 7-10. |
| | |
| | 9) 9) SHEET A-8.01 IDENTIFIES TYPE OF WALLS WITH WALL |
| | TAG ALPHA- NUMERICAL WALL TAGS FOR FIRE RESISTANCE |
| | RATINGS HOW DOES SHEET A-11.00 SERIES OF DRAWINGS |
| | RELATE TO SHEET A-8.01. SHEET A-8.01 DOES NOT HAVE |
| | BLOCK TYPE INFORMATION STATING THEY ARE A T012 OR T007 |
| | TYPE BLOCK? |
| | 10) SHEET A-2.11- A-2.15: |
| | 10A) THIS COMMENT WILL STAND FOR ALL DOORS ON ALL |
| | FLOORS. THE FRONT ENTRY DOORS DO NOT INDICATE A DOOR |
| | IDENTIFICATION TAG, PLEASE PROVIDE COMPLIANCE WITH 2010 |
| | FBC-B TABLE 715.4. |
| | |
| | 10B) BETWEEN DWELLING UNITS AND DWELLING UNITS AND |
| | COMMON AREAS WALL TYPE W5 HAS BEEN INDICATED A 6 INCH |
| | CONCRETE REINFORCED WALL WITH NO INSULATION. PLEASE |
| | PROVIDE DOCUMENTATION THAT COMPLIANCE WITH 2010 FBC-B |
| | 1207.2 HAS BEEN ACHIEVED. |
| | |
| | 10C) ) BETWEEN DWELLING UNITS AND DWELLING UNITS AND |
| | COMMON AREAS WALL TYPE W9 HAS BEEN INDICATED AS A 6 |
| | INCH METAL STUD WALL, SOUND INSULATION BLANKET AND 5/8 |
| | INCH FIRE-CODE GYPSUM. PLEASE PROVIDE DOCUMENTATION |
| | THAT COMPLIANCE WITH 2010 FBC-B 1207.2 HAS BEEN |
| | ACHIEVED. |
| | |
| | 11) SHEET A-2.14 ) PLEASE SHOW HOW COMPLIANCE WITH |
| | 1209.2 WILL BE ACHIEVED 20 INCH X 30 INCH ATTIC ACCESS. |
| | 12) SHEET A-2.15. ) PLEASE SHOW COMPLIANCE WITH THE |
| | UPPER 50% OF REQUIRED ROOF VENTS. THE HIPPED ROOFS SHOW |
| | SOFFIT VENTS BUT THERE IS NO NOTATION OF CODE |
| | COMPLIANCE FOR 2010 FBC-B 1203.2 WITH 50% OF THE |
| | REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS |
| | LOCATED IN THE UPPER PORTION OF THE SPACE TO BE |
| | VENTILATED AT LEAST 3 FEET ABOVE THE EAVE OR CORNICE |
| | VENTS, WITH THE BALANCE OF THE REQUIRED VENTILATION |
| | PROVIDED BY THE EAVE VENTS. |
| | |
| | 13) SEE SHEET 2014- 16 S.P.-A7.00-A7.03, THIS SHEET IS |
| | LOADED TWICE. DISCREPANCY . |
| | |
| | 14) SHEET A-7-06 TRASH CHUTE; |
| | 14A) DETAIL # 1 PLEASE PROVIDE DETAIL OF THE 2ND FLOOR |
| | BOTTOM OF SHAFT ENCLOSURE FIRE PROOFING OF HORIZONTAL |
| | ASSEMBLY. FBC-B 713.4.1.1 THROUGH PENETRATIONS. |
| | |
| | 14 B) PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS ON |
| | THE HORIZONTAL DAMPER THAT CLOSES OFF THE TRASH CHUTE |
| | FROM THE REMAINDER OF THE TERMINATION ROOM. FBC-B |
| | 708.13.1. THIS MAY BE A HEAT ACTIVATED CLOSING DEVICE |
| | SHALL BE PERMITTED BETWEEN THE SHAFT AND THE |
| | TERMINATION ROOM. |
| | |
| | 14C) DETAIL C DOES INDICATE A FIRE SPRINKLER RISER |
| | WITHIN THE SHAFT BUT NO COMPLIANCE WITH FBC-B |
| | 903.2.11.2. CHUTES EXTENDING 3 OR MORE FLOORS SHALL |
| | HAVE ADDITIONAL SPRINKLER HEADS AT ALTERNATING FLOORS |
| | AND AT THE TOP OF THE SHAFT. |
| | |
| | 15) SHEET A-9.03 DETAIL # 6 SHOWS A WATERPROOFING |
| | DETAIL OF THE COMMON PEDESTRIAN WALKWAYS FOR ALL |
| | BUILDINGS, IS THE SHERCRETE BASE AND TOP COAT ALSO TO |
| | ACT AS THE FLOOR INSULATION THAT IS REQUIRED UNDER |
| | SECTION FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | ALL COMMON AREAS WILL NEED TO COMPLY WITH STRUCTURE |
| | BORNE SOUND. PLEASE PROVIDE ALL TESTING REPORTS FOR |
| | THIS PRODUCT. |
| | |
| | 16) SHEET A-9.04 INDICATES THE USE OF (2) FLOOR |
| | INSULATION PRODUCTS, EASY MAT AND KNAUF INSULATION, |
| | PLEASE SUBMIT THE REPORTS FOR COMPLIANCE WITH: |
| | |
| | 16A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 16B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 16C) NOTICE!!! DIFFERENT THAN TYPE I TYPE II BLDGS. |
| | TYPE III-TYPE V CONSTRUCTION: |
| | 2010 FBC-B 719.2 CONCEALED INSTALLATION. INSULATING |
| | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF |
| | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD |
| | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| | OF NOT MORE THAN 450. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 17) SHEET S-3.02 UNDER THE HEADING WINDLOAD PRESSURES |
| | FOR WINDOWS AND DOORS, THE PLANS DO NOT INDICATE THE |
| | MEAN ROOF HEIGHT THESE PRESSURE WERE TAKEN FOR, |
| | BUILDING 1 IS A (5) STORY WHEREAS BUILDINGS 2 & 3 ARE |
| | BOTH 4 STORY BUILDINGS. DEFINITIONS, CHAPTER 2. MEAN |
| | ROOF HEIGHT. THE AVERAGE OF THE ROOF EAVE HEIGHT AND |
| | THE HEIGHT TO THE HIGHEST POINT ON THE ROOF SURFACE, |
| | EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR ROOF ANGLE OF |
| | LESS THAN OR EQUAL TO 10 DEGREES (0.18 RAD). |
| | |
| | 18) SHEET S-3.02 COMPONENTS AND CLADDING THE ROOF |
| | PRESSURES FOR ROOF ZONES 1,2 & 3 WERE NOT PROVIDED FOR |
| | 10 SQ. FT. PLEASE ALSO NOTE THERE ARE 2 MEAN ROOF |
| | HEIGHTS TO CONSIDER, THE 5 STORY AND 4 STORY. THE OTHER |
| | ISSUE IS THE PRESSURES FOR THE FLAT ROOFS AS WELL AS |
| | FOR THE SLOPED ROOF. FBC-B 1609.1.5 & 1609.1.2.3.1. |
| | |
| | 19A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 19B) WILL PRODUCT APPROVALS FOR ,WINDOWS, DOORS, EXT. |
| | WALL LOUVERS, ROOFING COMPONENTS BE SUBMITTED FOR THE |
| | WORST CASE SCENARIO BUILDING # 5 OR WILL THE APPROVALS |
| | BE DIFFERENT FOR BUILDING # 1 THAN BUILDINGS 2 & 3. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 20A) FOR GLAZED PRODUCT APPROVALS, IDENTIFY THE TYPE OF |
| | GLAZING, WIDTH & HEIGHT OF GLAZED OPENING, IF MULLIONS |
| | ARE USED, CIRCLE THE MULLION TO BE INSTALLED, |
| | PRESSURES, AND FASTENERS. |
| | |
| | 20B) FOR ROOFING APPROVALS: FLAT ROOF. HIGHLIGHT THE |
| | SUB-SYSTEM TO BE INSTALLED, NOTE THE PRESSURES, IF THEY |
| | REQUIRE ENHANCED FASTENING, RAS 117 CALCULATIONS, AND |
| | SIGNED & SEALED CALCULATIONS. |
| | |
| | 20C) FOR THE SLOPED ROOF: PROVIDE THE TYPE OF TILE TO |
| | BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF FOAMED, |
| | IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED PRESSURES. |
| | |
| | 20D) EITHER THE DESIGN PROFESSIONAL OR THE CONTRACTOR |
| | CAN ELECT TO DEFER THE SUBMISSION OF THE PRODUCT |
| | APPROVALS TO AFTER PERMIT ISSUANCE IF THE PRESSURES FOR |
| | THE BUILDING ARE CORRECT AND A WRITTEN DOCUMENT ASKING |
| | FOR THE PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS. |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 21) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 22) LIFE SAFETY SHEETS COMMON STATEMENT FOR ALL |
| | BUILDINGS AND ALL FLOORS. THE ROOMS THAT HAVE A |
| | FRACTION OF AN OCCUPANT IS ROLLED DOWN. THE RULE IS TO |
| | ROLL UP TO THE NEXT FULL OCCUPANT. EXAMPLE IS UNIT A, |
| | 648/200= 4 X 3 UNITS= 12 OCCUPANTS NOT 10. |
| | FLORIDA BUILDING CODE INFORMAL INTERPRETATION 5479 |
| | TUES. DEC. 17/2007. OCCUPANTS ONLY COME IN AS A HOLE, |
| | ALWAYS ROUND UP. |
| | |
| | 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |