Plan Review Notes
Plan Review Notes For Permit 15050262
Permit Number 15050262
Review Stop B
Sequence Number 1
Notes
Date Text
2015-06-20 10:49:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050262
 ADD: 1851 DIVISION AVE.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: ALBERT OVIEDO
 TEL: (???????
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SAT. JUNE 20/2015
 SILVER PALM PLACE
 BLDG # 3/ 29 UNITS/ 4 STORY/ R2
  
 ACTION: DENIED
  
 THIS REVIEW IS FOR BUILDING # 3 AND DOES NOT INCLUDE
 ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING,
 SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY
 AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION
 OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL
 NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH
 ASSOCIATED COST.
  
 1) NOTICE! ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2A) COMPLIED. ELECTRONIC MEDIA: SUBMITTED AN INDEX.
  
 2B) 2A) ELECTRONIC MEDIA: 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. THIS PLAN DOES NOT
 FOLLOW THE NAMING CONVENTION FOR EACH PAGE WITHIN THE
 SET OF PLANS AND SHOULD HAVE BEEN DENIED AT TIME OF
 ELECTRONIC SUBMISSION. THE ARCHITECTURAL SHEETS ARE NOT
 IN ORDER BECAUSE OF THE NAMING CONVENTION WAS NOT
 FOLLOWED, THE A1. SHEETS JUMP TO A-10 SERIES TO A-11
 SERIES THEN TO A-2SERIES, THEY DO NOT FOLLOW THE
 SUBMITTED INDEX SHEET!!!!! THE PLANS DO NOT MEET THE
 CITY STANDARD FOR ELECTRONIC MEDIA REQUIRED BY THE
 ELECTRONIC PLAN REVIEW LIBERIAN, CAROLINE PUELL. PLEASE
 CONTACT MS. PUELL AT 805-6659 FOR FURTHER INSTRUCTIONS
 AND CLARIFICATIONS.
  
 2C) THE ELECTRONIC PLANS SUBMITTED 370 PAGES ARE PLANS
 SUBMITTED 3 TIMES FOR 3 BUILDINGS. THE ONE SET OF PLANS
 HAS ALL THE BUILDING INFORMATION FOR THE 3 BUILDINGS.
 THIS STYLE OF SUBMITTAL IS MORE OF A MASTER, NO
 BUILDINGS CAN BE ISSUED UNTIL THE PLANS ARE CODE
 COMPLIANT FOR THE WHOLE OF THE PROJECT. THE PLANS
 SHOULD HAVE PULLED OUT OF THE SET OF DRAWINGS THAT DID
 NOT PERTAIN TO THAT BUILDING AND DETAIL SHEETS, DETAILS
 NOT PERTAINING TO THAT BUILDING STRUCK THROUGH.
 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE UNIFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. THIS
 CODE SECTION IS FOR RECORD RETENTION BUT THE REALITY OF
 THIS IS, THE WAY THESE PLANS WERE SUBMITTED, IT IS VERY
 DIFFICULT TO FIND WHERE TO LOOK FOR CODE
 COMPLIANCE!!!!!!!
  
 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING
 FLORIDA S. S. 553.71(7)
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 THESE FORMS ARE E-MAILED TO CONTACT: ALBERT OVIEDO
 E-MAIL ADDRESS: [email protected]
 FORMS SENT AT SUN. JUNE 07/2015 08:51 AM.
  
 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 3F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 3G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 4) THE PERMIT VALUE OF $3,752,718.00 IS LOW. THIS
 REVIEW IS FOR A 4 STORY R2 BUILDING TYPE III-B FOR
 BUILDING # 3, THE VALUATION IS FIGURED $118.01 FROM THE
 IIC TABLE FEB. 01/ 2015.
 CALCULATED VALUE:
 BLDG. #3 TYPE III-B 61,409 SQ. FT. X $118.01=
 $7,246,876.00
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5) SAFEGUARDS DURING CONSTRUCTION;
 5A) 2010 FBC-B 3306.2 WALKWAYS
 5B) 2010 FBC-B 3306.3 DIRECTIONAL BARRICADES
 5C) 2010 FBC-B CONSTRUCTION RAILINGS. 42 INCHES IN
 HEIGHT.
 5D) 2010 FBC-B 3306.5 BARRIERS
 5E) 2010 FBC-B 3309.1 FIRE EXTINGUISHERS
 5F) 2010 FBC-B 3310.1 TEMPORARY LIGHTED STAIRWAY
 5G) 2010 FBC-B 3311.1 / 905.3.1 STANDPIPES SHALL BE
 EXTENDED AS CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR
 OF THE HIGHEST POINT OF CONSTRUCTION HAVING SECURED
 DECKING OR FLOORING.
  
 6) THE PERMIT APPLICATION CAME IN AS A TBD, TO BE
 DETERMINED. A HOLD WILL BE PUT ON THE ISSUANCE OF THIS
 PERMIT TO VERIFY LICENSURE REQUIREMENTS THAT THE
 CONTRACTOR HOLDS THE APPROPRIATE LICENSURE FOR A 4
 STORY BUILDING. FLORIDA S. S. 489.113.
  
 7) SHEET A-0.01: UNDER THE HEADING CONSTRUCTION TYPE IS
 FOUND A BOX CHECKED SPRINKLERS, YES . THIS IS NOT CLEAR
 SINCE THERE IS BLDGS. 2 & 3 ON THE SAME LINE AS
 BUILDING # 1. THE REAL QUESTION IS WILL THERE BE (2)
 TYPES OF FIRE SPRINKLERS, FOR BUILDING # 1 A NFPA 13 IN
 COMPLIANCE WITH FBC-B 903.3.1.1 AND WILL BUILDINGS 2 &
 3 HAVE THE SAME TYPE OF FIRE SPRINKLERS OR WILL THEY
 HAVE A NFPA 13-R INCOMPLIANCE WITH FBC-B 903.3.1.2. IF
 BOTH SYSTEMS ARE GOING TO BE INSTALLED PLEASE LIST THEM
 IN THE BUILDING MATRIX AS SUCH.
  
 8) SHEET A-1.01;
 8A) DETAILS 3 AND 3.1 THE ACCESSIBLE & STANDARD PARKING
 DETAILS AND PARALLEL PARKING STRIPPING DETAILS ARE
 GOING TO NEED TO COMPLY WITH 2010 FBC-ACCESSIBILITY
 CODE ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. SEE
 WEST PALM BEACH MUNI-CODE SECTION 94-485 STALL PAINTING
 DETAIL.
  
 8B) DETAIL # 10. THE FENCE DESIGN IS INDICATED TO MEET
 THE FBC-B 2010 ASCE 7-05. PLEASE NOTE THE ASCE -05 WAS
 IN THE 2007 FBC-B. THE 2010 FBC-B SECTION 1609. 1.1 THE
 DETERMINATION OF WIND USES THE ASCE 7-10.
  
 9) 9) SHEET A-8.01 IDENTIFIES TYPE OF WALLS WITH WALL
 TAG ALPHA- NUMERICAL WALL TAGS FOR FIRE RESISTANCE
 RATINGS HOW DOES SHEET A-11.00 SERIES OF DRAWINGS
 RELATE TO SHEET A-8.01. SHEET A-8.01 DOES NOT HAVE
 BLOCK TYPE INFORMATION STATING THEY ARE A T012 OR T007
 TYPE BLOCK?
 10) SHEET A-2.11- A-2.15:
 10A) THIS COMMENT WILL STAND FOR ALL DOORS ON ALL
 FLOORS. THE FRONT ENTRY DOORS DO NOT INDICATE A DOOR
 IDENTIFICATION TAG, PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B TABLE 715.4.
  
 10B) BETWEEN DWELLING UNITS AND DWELLING UNITS AND
 COMMON AREAS WALL TYPE W5 HAS BEEN INDICATED A 6 INCH
 CONCRETE REINFORCED WALL WITH NO INSULATION. PLEASE
 PROVIDE DOCUMENTATION THAT COMPLIANCE WITH 2010 FBC-B
 1207.2 HAS BEEN ACHIEVED.
  
 10C) ) BETWEEN DWELLING UNITS AND DWELLING UNITS AND
 COMMON AREAS WALL TYPE W9 HAS BEEN INDICATED AS A 6
 INCH METAL STUD WALL, SOUND INSULATION BLANKET AND 5/8
 INCH FIRE-CODE GYPSUM. PLEASE PROVIDE DOCUMENTATION
 THAT COMPLIANCE WITH 2010 FBC-B 1207.2 HAS BEEN
 ACHIEVED.
  
 11) SHEET A-2.14 ) PLEASE SHOW HOW COMPLIANCE WITH
 1209.2 WILL BE ACHIEVED 20 INCH X 30 INCH ATTIC ACCESS.
 12) SHEET A-2.15. ) PLEASE SHOW COMPLIANCE WITH THE
 UPPER 50% OF REQUIRED ROOF VENTS. THE HIPPED ROOFS SHOW
 SOFFIT VENTS BUT THERE IS NO NOTATION OF CODE
 COMPLIANCE FOR 2010 FBC-B 1203.2 WITH 50% OF THE
 REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS
 LOCATED IN THE UPPER PORTION OF THE SPACE TO BE
 VENTILATED AT LEAST 3 FEET ABOVE THE EAVE OR CORNICE
 VENTS, WITH THE BALANCE OF THE REQUIRED VENTILATION
 PROVIDED BY THE EAVE VENTS.
  
 13) SEE SHEET 2014- 16 S.P.-A7.00-A7.03, THIS SHEET IS
 LOADED TWICE. DISCREPANCY .
  
 14) SHEET A-7-06 TRASH CHUTE;
 14A) DETAIL # 1 PLEASE PROVIDE DETAIL OF THE 2ND FLOOR
 BOTTOM OF SHAFT ENCLOSURE FIRE PROOFING OF HORIZONTAL
 ASSEMBLY. FBC-B 713.4.1.1 THROUGH PENETRATIONS.
  
 14 B) PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS ON
 THE HORIZONTAL DAMPER THAT CLOSES OFF THE TRASH CHUTE
 FROM THE REMAINDER OF THE TERMINATION ROOM. FBC-B
 708.13.1. THIS MAY BE A HEAT ACTIVATED CLOSING DEVICE
 SHALL BE PERMITTED BETWEEN THE SHAFT AND THE
 TERMINATION ROOM.
  
 14C) DETAIL C DOES INDICATE A FIRE SPRINKLER RISER
 WITHIN THE SHAFT BUT NO COMPLIANCE WITH FBC-B
 903.2.11.2. CHUTES EXTENDING 3 OR MORE FLOORS SHALL
 HAVE ADDITIONAL SPRINKLER HEADS AT ALTERNATING FLOORS
 AND AT THE TOP OF THE SHAFT.
  
 15) SHEET A-9.03 DETAIL # 6 SHOWS A WATERPROOFING
 DETAIL OF THE COMMON PEDESTRIAN WALKWAYS FOR ALL
 BUILDINGS, IS THE SHERCRETE BASE AND TOP COAT ALSO TO
 ACT AS THE FLOOR INSULATION THAT IS REQUIRED UNDER
 SECTION FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 ALL COMMON AREAS WILL NEED TO COMPLY WITH STRUCTURE
 BORNE SOUND. PLEASE PROVIDE ALL TESTING REPORTS FOR
 THIS PRODUCT.
  
 16) SHEET A-9.04 INDICATES THE USE OF (2) FLOOR
 INSULATION PRODUCTS, EASY MAT AND KNAUF INSULATION,
 PLEASE SUBMIT THE REPORTS FOR COMPLIANCE WITH:
  
 16A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 16B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 16C) NOTICE!!! DIFFERENT THAN TYPE I TYPE II BLDGS.
 TYPE III-TYPE V CONSTRUCTION:
 2010 FBC-B 719.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 17) SHEET S-3.02 UNDER THE HEADING WINDLOAD PRESSURES
 FOR WINDOWS AND DOORS, THE PLANS DO NOT INDICATE THE
 MEAN ROOF HEIGHT THESE PRESSURE WERE TAKEN FOR,
 BUILDING 1 IS A (5) STORY WHEREAS BUILDINGS 2 & 3 ARE
 BOTH 4 STORY BUILDINGS. DEFINITIONS, CHAPTER 2. MEAN
 ROOF HEIGHT. THE AVERAGE OF THE ROOF EAVE HEIGHT AND
 THE HEIGHT TO THE HIGHEST POINT ON THE ROOF SURFACE,
 EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR ROOF ANGLE OF
 LESS THAN OR EQUAL TO 10 DEGREES (0.18 RAD).
  
 18) SHEET S-3.02 COMPONENTS AND CLADDING THE ROOF
 PRESSURES FOR ROOF ZONES 1,2 & 3 WERE NOT PROVIDED FOR
 10 SQ. FT. PLEASE ALSO NOTE THERE ARE 2 MEAN ROOF
 HEIGHTS TO CONSIDER, THE 5 STORY AND 4 STORY. THE OTHER
 ISSUE IS THE PRESSURES FOR THE FLAT ROOFS AS WELL AS
 FOR THE SLOPED ROOF. FBC-B 1609.1.5 & 1609.1.2.3.1.
  
 19A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 19B) WILL PRODUCT APPROVALS FOR ,WINDOWS, DOORS, EXT.
 WALL LOUVERS, ROOFING COMPONENTS BE SUBMITTED FOR THE
 WORST CASE SCENARIO BUILDING # 5 OR WILL THE APPROVALS
 BE DIFFERENT FOR BUILDING # 1 THAN BUILDINGS 2 & 3.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 20A) FOR GLAZED PRODUCT APPROVALS, IDENTIFY THE TYPE OF
 GLAZING, WIDTH & HEIGHT OF GLAZED OPENING, IF MULLIONS
 ARE USED, CIRCLE THE MULLION TO BE INSTALLED,
 PRESSURES, AND FASTENERS.
  
 20B) FOR ROOFING APPROVALS: FLAT ROOF. HIGHLIGHT THE
 SUB-SYSTEM TO BE INSTALLED, NOTE THE PRESSURES, IF THEY
 REQUIRE ENHANCED FASTENING, RAS 117 CALCULATIONS, AND
 SIGNED & SEALED CALCULATIONS.
  
 20C) FOR THE SLOPED ROOF: PROVIDE THE TYPE OF TILE TO
 BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF FOAMED,
 IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED PRESSURES.
  
 20D) EITHER THE DESIGN PROFESSIONAL OR THE CONTRACTOR
 CAN ELECT TO DEFER THE SUBMISSION OF THE PRODUCT
 APPROVALS TO AFTER PERMIT ISSUANCE IF THE PRESSURES FOR
 THE BUILDING ARE CORRECT AND A WRITTEN DOCUMENT ASKING
 FOR THE PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 21) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 22) LIFE SAFETY SHEETS COMMON STATEMENT FOR ALL
 BUILDINGS AND ALL FLOORS. THE ROOMS THAT HAVE A
 FRACTION OF AN OCCUPANT IS ROLLED DOWN. THE RULE IS TO
 ROLL UP TO THE NEXT FULL OCCUPANT. EXAMPLE IS UNIT A,
 648/200= 4 X 3 UNITS= 12 OCCUPANTS NOT 10.
 FLORIDA BUILDING CODE INFORMAL INTERPRETATION 5479
 TUES. DEC. 17/2007. OCCUPANTS ONLY COME IN AS A HOLE,
 ALWAYS ROUND UP.
  
 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  