Plan Review Notes
Plan Review Notes For Permit 15050261
Permit Number 15050261
Review Stop B
Sequence Number 2
Notes
Date Text
2015-08-18 16:51:05BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: ALBERT OVIEDO
 TEL: (???????
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: TUES. AUGUST 18/2015
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2
  
 ACTION: DENIED
  
 THIS REVIEW IS FOR BUILDING # 1 AND DOES NOT INCLUDE
 ANY SITE AMENITIES, POOL, POOL DECK, FENCING, PAVING,
 SIDEWALKS, AND OR PARKING LOT & STRIPING, ACCESSIBILITY
 AND OR FAIR HOUSING, TEMPORARY TRAILER / CONSTRUCTION
 OFFICES FOR ANY OF THE ABOVE MENTIONED AREAS. THEY WILL
 NEED TO TOO BE REVIEWED UNDER SEPARATE PERMIT WITH
 ASSOCIATED COST.
  
 1) NOTICE! ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2A-B) COMPLIED.
  
 2C) THE ELECTRONIC PLANS SUBMITTED 368 PAGES ARE PLANS
 SUBMITTED 3 TIMES FOR 3 BUILDINGS. THE ONE SET OF PLANS
 HAS ALL THE BUILDING INFORMATION FOR THE 3 BUILDINGS.
 THIS STYLE OF SUBMITTAL IS MORE OF A MASTER, NO
 BUILDINGS CAN BE ISSUED UNTIL THE PLANS ARE CODE
 COMPLIANT FOR THE WHOLE OF THE PROJECT. THE PLANS
 SHOULD HAVE PULLED THE SHEETS THAT DID NOT PERTAIN TO
 THAT BUILDING AND DETAIL SHEETS, DETAILS NOT PERTAINING
 TO THAT BUILDING STRUCK THROUGH. 107.2.1.4 QUALITY OF
 BUILDING PLANS. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE UNIFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES. THIS CODE SECTION IS
 FOR RECORD RETENTION BUT THE REALITY OF THIS IS, THE
 WAY THESE PLANS WERE SUBMITTED, IT IS VERY DIFFICULT TO
 FIND WHERE TO LOOK FOR CODE COMPLIANCE!!!!!!!
  
 3) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING
 FLORIDA S. S. 553.71(7)
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) 2ND REQUEST, THE RESPONSE INDICATES THE WRITTEN
 THRESHOLD INSPECTION PLAN WAS SUBMITTED PLEASE INDICATE
 WHERE IT CAN BE LOCATED?
 THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) COMPLIED. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE. CONTACT KEN CONRAD MANAGER OF
 THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 THESE FORMS ARE E-MAILED TO CONTACT: ALBERT OVIEDO
 E-MAIL ADDRESS: [email protected]
 FORMS SENT AT SUN. JUNE 07/2015 08:51 AM.
  
 3C) COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) COMPLIED. FOR THE SPECIAL INSPECTOR PLEASE PROVIDE
 A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3E) NOTE TO DATE NO CONTRACTOR HAS SUBMITTED A PERMIT
 APPLICATION WHERE THE OWNER AND QUALIFIER HAVE SIGNED
 AND THEIR SIGNATURES NOTARIZED.
 THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected]
  
 3F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
  
 3G) NOTICE ONLY! PLEASE CALL THE CITY OF WEST PALM
 BEACHES? AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H)NOTICE ONLY! 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4) THE PERMIT VALUE OF $11,712,570.25 IS LOW. THERE IS
 A DISCREPANCY IN THE BUILDING TYPE FOR BUILDING # 1, SO
 THE VALUATION IS FIGURED FOR BOTH BUILDING TYPES.
 CALCULATED VALUE:
 BLDG. TYPE I-B 93,992 X $146.27= $13,748,209.00
 BLDG. TYPE II-B 93,992 X $133.25= $12,524,443.00
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5)2ND REQUEST. SAFEGUARDS DURING CONSTRUCTION;
 5A) 2010 FBC-B 3306.2 WALKWAYS
 5B) 2010 FBC-B 3306.3 DIRECTIONAL BARRICADES
 5C) 2010 FBC-B CONSTRUCTION RAILINGS. 42 INCHES IN
 HEIGHT.
 5D) 2010 FBC-B 3306.5 BARRIERS
 5E) 2010 FBC-B 3309.1 FIRE EXTINGUISHERS
 5F) 2010 FBC-B 3310.1 TEMPORARY LIGHTED STAIRWAY
 5G) 2010 FBC-B 3311.1 / 905.3.1 STANDPIPES SHALL BE
 EXTENDED AS CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR
 OF THE HIGHEST POINT OF CONSTRUCTION HAVING SECURED
 DECKING OR FLOORING.
  
 6) 2ND REQUEST. THE PERMIT APPLICATION CAME IN AS A
 TBD, TO BE DETERMINED. A HOLD WILL BE PUT ON THE
 ISSUANCE OF THIS PERMIT TO VERIFY LICENSURE
 REQUIREMENTS THAT THE CONTRACTOR HOLDS THE APPROPRIATE
 LICENSURE FOR A 5 STORY BUILDING. FLORIDA S. S.
 489.113.
  
 7) SHEET A-0.01:
 7A)2ND REQUEST. THE CONSTRUCTION TYPE IS LISTED FOR
 BLDG # 1 AS II-B BUILDING, WHEREAS UNDER THE HEADING OF
 FIRE RESISTANCE RATING THE BUILDING IS LISTED AS
 CONSTRUCTION TYPE I-B. THIS DISCREPANCY IN THE PLANS
 WILL AFFECT THE REQUIREMENTS IN TABLE 601. 107.2.1.3,
 ADDITIONAL INFORMATION IS REQUIRED. IT APPEARS THAT
 FIRE RESISTANCE RATINGS AND ALLOWABLE HEIGHT AND AREA
 ARE FOR A CONSTRUCTION BLDG. TYPE I-B. FOR THE PURPOSE
 OF THIS REVIEW A BLDG. TYPE I-B WILL BE ASSUMED.
  
 7B) 2ND REQUEST. UNDER THE HEADING CONSTRUCTION TYPE IS
 FOUND A BOX CHECKED SPRINKLERS, YES . THIS IS NOT CLEAR
 SINCE THERE ARE BLDGS. 2 & 3 ON THE SAME LINE AS
 BUILDING # 1.
  
 THE REAL QUESTION IS WILL THERE BE (2) TYPES OF FIRE
 SPRINKLERS, FOR BUILDING # 1 WILL REQUIRE THE NFPA 13
 FIRE SPRINKLER IN COMPLIANCE WITH FBC-B 903.3.1.1 AND
 WILL BUILDINGS 2 & 3 HAVE THE SAME TYPE OF FIRE
 SPRINKLERS OR WILL THEY HAVE A NFPA 13-R INCOMPLIANCE
 WITH FBC-B 903.3.1.2. IF BOTH SYSTEMS ARE GOING TO BE
 INSTALLED PLEASE LIST THEM IN THE BUILDING MATRIX FOR
 EACH BUILDING TYPE.
  
 8-9) COMPLIED.
  
 10) SHEET A-200A:
 10A) THIS COMMENT WILL BE FOR THE 1ST FLOOR LS-1.01
 UNIT B NEXT TO STAIR # 2. THE FRONT ENTRY DOORS DO NOT
 INDICATE A DOOR IDENTIFICATION TAG, PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B TABLE 715.4.
  
 10B) 2ND REQUEST. BETWEEN DWELLING UNITS AND DWELLING
 UNITS AND COMMON AREAS WALL TYPE W5 HAS BEEN INDICATED
 A 6 INCH CONCRETE REINFORCED WALL WITH NO INSULATION.
 PLEASE PROVIDE DOCUMENTATION THAT COMPLIANCE WITH 2010
 FBC-B 1207.2 HAS BEEN ACHIEVED.
  
  
  
 11-19) COMPLIED.
  
 20)2ND REQUEST. SHEET A-9.04 INDICATES THE USE OF (2)
 FLOOR INSULATION PRODUCTS, EASY MAT AND KNAUF
 INSULATION, PLEASE SUBMIT THE REPORTS FOR COMPLIANCE
 WITH 20A-20C.
  
 PLEASE NOTE WITH THE DESIGNER OF RECORD SPECING OUT THE
 USE OF EASY MAT WE CANNOT APPROVE THESE CODE SECTIONS.
 TO DATE NO CONTRACTOR, SUPPLIER OR MANUFACTURER HAS
 BEEN ABLE TO PROVIDE TESTING REPORTS FOR THE SOUND
 REQUIREMENTS OF ASTM E 492 AND ASTM E 90. WE DO HAVE A
 FLAME SPREAD TEST THAT WILL PASS A BUILDING TYPE I OR
 II BUT NOT THE MORE RESTRICTIVE REQUIREMENT FOUND FOR
 BUILDING TYPE IIIB. SEE 719.2 CONCEALED INSTALLATION.
  
 20A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 20B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 20C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 21-22) COMPLIED.
  
 23)2ND REQUEST. EITHER THE DESIGNER OF RECORD OR THE
 CONTRACTOR CAN ELECT TO SUBMIT THE PRODUCT APPROVALS
 AFTER PERMIT ISSUANCE AS A DEFERRED SUBMITTAL UNDER
 107.3.4.2, THIS IS A WRITTEN REQUEST, OTHERWISE WE WILL
 NEED THE PRODUCT APPROVALS TO REVIEW FOR CODE
 COMPLIANCE. PLEASE NOTE TO IDENTIFY, OPENING SIZES,
 TYPE OF GLAZING, PRESSURES, TYPE OF FASTENERS, MULLIONS
 ETC.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 23A) 2ND REQUEST. FOR GLAZED PRODUCT APPROVALS,
 IDENTIFY THE TYPE OF GLAZING, WIDTH & HEIGHT OF GLAZED
 OPENING, IF MULLIONS ARE USED, CIRCLE THE MULLION TO BE
 INSTALLED, PRESSURES, AND FASTENERS.
  
 23B)2ND REQUEST. FOR ROOFING APPROVALS: FLAT ROOF.
 HIGHLIGHT THE SUB-SYSTEM TO BE INSTALLED, NOTE THE
 PRESSURES, IF THEY REQUIRE ENHANCED FASTENING, RAS 117
 CALCULATIONS, AND SIGNED & SEALED CALCULATIONS.
  
 23C)2ND REQUEST. FOR THE SLOPED ROOF: PROVIDE THE TYPE
 OF TILE TO BE INSTALLED, CIRCLE, TYPE OF FASTENER, IF
 FOAMED, IDENTIFY SIZE OF FOAM PATTY WITH ASSOCIATED
 PRESSURES.
  
 23D) 2ND REQUEST. EITHER THE DESIGN PROFESSIONAL OR THE
 CONTRACTOR CAN ELECT TO DEFER THE SUBMISSION OF THE
 PRODUCT APPROVALS TO AFTER PERMIT ISSUANCE IF THE
 PRESSURES FOR THE BUILDING ARE CORRECT AND A WRITTEN
 DOCUMENT ASKING FOR THE PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 24) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  