2015-06-09 17:18:48PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE
 REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH
 RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN
 CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE
 DIGITAL PLANS.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 PG. E-1.00 ELECTRICAL SITE PLAN
 1. BEING THAT THE PROPOSED POOL WILL BE UNDER A
 SEPARATE PERMIT. A NOTE AS TO THE NEC 680.10
 REQUIREMENT FOR NO UNDERGROUND RACEWAYS WITHIN 5? OF
 THE WATER?S EDGE SHOULD BE MADE TO KEEP THE AREA CLEAR
 OF NON-POOL RELATED CONDUIT.
  
 PG. E1.10 PHOTOMETRIC PLAN
 1. AN AMENDMENT TO NOTE 4 IN IRRIGATION PUMP SYSTEMS TO
 INCLUDE THE CODE REQUIREMENT THAT THE DEVICES ALSO BE
 RATED ?WR? WEATHER RESISTANT.
  
 PG. E2.02A, E2.02B, E2.03A, E2.03B, E2.04A, E2.04B,
 E2.08, E2.09, E.2.13 & E2.14
 1. THE ABOVE PAGES ARE MISSING AN EXIT LIGHT IN THE
 CORNER WHERE THE TWO CORRIDORS INTERSECT. THIS/THESE
 LIGHTS SHALL BE VISIBLE FROM BOTH SIDES.
 2. IN ADDITION TO THE ABOVE, PGS. E2.04A, E2.09 & E2.14
 HAVE ACCESS TO THE ROOF. THERE SHALL BE AN EXIT LIGHT
 ON THE ROOF SIDE OF EACH OF THESE DOORS.
 3. THE SAME APPLIES TO PG. E2.04B. THE DOOR ON THE
 MATCH LINE HAS BEEN CLOUDED ON BOTH A & B.
  
 PG. E2.07A, E2.08A, E2.09A, E2.12A, E2.13A & E2.14A
 1. ON THESE PAGES YOU SHOW THE EMERGENCY EGRESS
 LIGHTING, AND THOUGH THE STAIRS ARE SHOWN ON THE
 INDIVIDUAL FLOOR PLANS, THEY ARE A PART OF THE
 EMERGENCY EGRESS AND THEREFORE REFLECTED AS SUCH.
  
  
  
 PG. E3.00, UNITS NOTES & LEGEND
 THIS IS PRIMARILY A NOTES PAGE AND HAS TWO ITEMS
 NEEDING CORRECTION. THESE SAME NOTES ARE TYPICAL
 THROUGHOUT THE DRAWINGS.
 1. NOTE 17 OF THE APARTMENT UNIT NOTES SHOULD BE
 AMENDED TO INCLUDE THE NEC 314.27 REQUIREMENT THAT THE
 CEILING BOXES BE RATED TO SUPPORT 50#. THIS NOTE HAS
 BEEN NOTED ELSEWHERE ON THE PLANS.
 2. I NOTICED THAT YOUR DESIGN INCLUDES CEILING FANS AND
 THEREFORE, APARTMENT SINGLE STATION SMOKE DETECTORS,
 NOTE 4 SHALL BE AMENDED TO INCLUDE 36? FROM THE TIP OF
 A CEILING FAN BLADE.
  
 PGS. E3.01, E3.02 & E3.03
 THE NOTES ON ALL OF THE SHEETS ARE THE SAME; THEREFORE
 THE FIRST THREE COMMENTS APPLY TO ALL.
 1. UNIT CODED NOTES, #4 SHALL INCLUDE THE TIP OF A
 CEILING FAN. (THE REGULATION INVOLVING THE KITCHEN IS
 ONLY THAT IF THE UNIT IS WITHIN 10? OF THE RANGE IT HAS
 TO BE SILENCEABLE).
 2. ADDITIONAL NOTES, #7 IS A REPEAT OF #4 ABOVE, & #2
 SHOULD BE AMENDED TO READ?AND BE RATED WEATHER
 RESISTANT ?WR? AS PER NEC 406.8.
 THE FOLLOWING ITEMS ARE ISSUES THAT WERE CLOUDED
 THROUGHOUT ALL THREE MODEL UNITS. THESE CLOUDS CAN BE
 SEEN BY VIEWING THE CHANGE MARK LAYERS.
 3. NEC 210.52 (A)(1) RECEPTACLES SHALL BE INSTALLED
 SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE
 FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FT. FROM A
 RECEPTACLE OUTLET. THIS INCLUDES THE DISTANCE FROM THE
 EDGE OF THE WALL.
 4. NEC 210.52 (A)(2) ANY WALL SPACE 2 FT. OR MORE IN
 WIDTH SHALL HAVE AN OUTLET
 5. NEC 210.52(C)(1) A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH WALL COUNTERTOP SPACE THAT IS 12 IN.
 OR WIDER. RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT
 NO POINT ALONG THE WALL LINE IS MORE THAN 24 IN.
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE.
 6. NEC 210.52(C)(3) AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED AT EACH PENINSULAR COUNTERTOP.
 7. NEC 210.520(D) IN DWELLING UNITS, AT LEAST ONE
 RECEPTACLE OUTLET SHALL BE INSTALLED IN BATHROOMS
 WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH BASIN.
 8. NEC 210.70(A)(3) AT LEAST ONE LIGHTING OUTLET
 CONTAINING A SWITCH OR CONTROLLED BY A WALL SWITCH
 SHALL BE INSTALLED WHERE THESE SPACES ARE USED FOR
 STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICING. THE
 LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE
 EQUIPMENT REQUIRING SERVICING. THE CLOSET IN WHICH SMC
 BOX/CABINET IS IN SHALL HAVE THE REQUIRED LIGHTING.
  
 PG. E4.00A
 1. SOUND SYSTEM NOTES BOX SHALL HAVE AN ADDITIONAL LINE
 ITEM STATING THAT THE AUDIO SYSTEM SHALL BE MUTED VIA
 THE FACP IN THE EVENT OF AN ALARM CONDITION.
  
 PG. E4.00B
 1. ILLUMINATION ELECTRICAL NOTES #3, SEE CORRECTION TO
 NEC 700.12(F)
  
 PG. E4.01, E4.03, E4.05, E4.06, MAIN ELECTRICAL ROOM
 ?A?, ?B? & ?C?
 1. SEE CLOUDED AREA IN ELECTRICAL ROOM NOTES WHICH HAS
 TO BE CLARIFIED.
  
 PG. E4.02 & E4.09 MACHINE ROOMS
 1. ELEVATOR ELECTRICAL NOTES BOX, NOTRE #1 SHALL BE
 CORRECTED TO READ AS FOLLOWS: NEC 620.51.
  
 PG. E4.07, E4.08 ENLARGED TRASH ROOMS
 1. BOTH, TRASH ROOM A, B, C & D, HAVE THE SAME COMMENT
 AS FOLLOWS: CHECK FOR PROPER WORKING CLEARANCE AS PER
 NEC 110.26. THERE DOES NOT APPEAR TO BE SUFFICIENT
 CLEARANCE BETWEEN THE ELECTRICAL OUTLETS AND WHATEVER
 IS IN FRONT OF THEM.
  
 PG. E5.06
 1. CORRECT INCORRECTLY QUOTED NEC SECTION TO READ
 (410.130(G))
 2. CLARIFY YOUR INTENT AT THE OUTLET STUB UP DETAIL
  
 THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008
 EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE
 APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND
 FLORIDA BUILDING CODE ENERGY CONSERVATION.
  
2015-06-09 15:45:43SEE ATTACHMENTS FOR DERTAILS OF ELECTRICAL PLAN REVIEW
 RESULTS.
 FIRE ALARM REVIEW TO FOLLOW