| 2015-06-09 17:18:48 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE |
| | REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH |
| | RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN |
| | CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE |
| | DIGITAL PLANS. |
| | |
| | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | |
| | PG. E-1.00 ELECTRICAL SITE PLAN |
| | 1. BEING THAT THE PROPOSED POOL WILL BE UNDER A |
| | SEPARATE PERMIT. A NOTE AS TO THE NEC 680.10 |
| | REQUIREMENT FOR NO UNDERGROUND RACEWAYS WITHIN 5? OF |
| | THE WATER?S EDGE SHOULD BE MADE TO KEEP THE AREA CLEAR |
| | OF NON-POOL RELATED CONDUIT. |
| | |
| | PG. E1.10 PHOTOMETRIC PLAN |
| | 1. AN AMENDMENT TO NOTE 4 IN IRRIGATION PUMP SYSTEMS TO |
| | INCLUDE THE CODE REQUIREMENT THAT THE DEVICES ALSO BE |
| | RATED ?WR? WEATHER RESISTANT. |
| | |
| | PG. E2.02A, E2.02B, E2.03A, E2.03B, E2.04A, E2.04B, |
| | E2.08, E2.09, E.2.13 & E2.14 |
| | 1. THE ABOVE PAGES ARE MISSING AN EXIT LIGHT IN THE |
| | CORNER WHERE THE TWO CORRIDORS INTERSECT. THIS/THESE |
| | LIGHTS SHALL BE VISIBLE FROM BOTH SIDES. |
| | 2. IN ADDITION TO THE ABOVE, PGS. E2.04A, E2.09 & E2.14 |
| | HAVE ACCESS TO THE ROOF. THERE SHALL BE AN EXIT LIGHT |
| | ON THE ROOF SIDE OF EACH OF THESE DOORS. |
| | 3. THE SAME APPLIES TO PG. E2.04B. THE DOOR ON THE |
| | MATCH LINE HAS BEEN CLOUDED ON BOTH A & B. |
| | |
| | PG. E2.07A, E2.08A, E2.09A, E2.12A, E2.13A & E2.14A |
| | 1. ON THESE PAGES YOU SHOW THE EMERGENCY EGRESS |
| | LIGHTING, AND THOUGH THE STAIRS ARE SHOWN ON THE |
| | INDIVIDUAL FLOOR PLANS, THEY ARE A PART OF THE |
| | EMERGENCY EGRESS AND THEREFORE REFLECTED AS SUCH. |
| | |
| | |
| | |
| | PG. E3.00, UNITS NOTES & LEGEND |
| | THIS IS PRIMARILY A NOTES PAGE AND HAS TWO ITEMS |
| | NEEDING CORRECTION. THESE SAME NOTES ARE TYPICAL |
| | THROUGHOUT THE DRAWINGS. |
| | 1. NOTE 17 OF THE APARTMENT UNIT NOTES SHOULD BE |
| | AMENDED TO INCLUDE THE NEC 314.27 REQUIREMENT THAT THE |
| | CEILING BOXES BE RATED TO SUPPORT 50#. THIS NOTE HAS |
| | BEEN NOTED ELSEWHERE ON THE PLANS. |
| | 2. I NOTICED THAT YOUR DESIGN INCLUDES CEILING FANS AND |
| | THEREFORE, APARTMENT SINGLE STATION SMOKE DETECTORS, |
| | NOTE 4 SHALL BE AMENDED TO INCLUDE 36? FROM THE TIP OF |
| | A CEILING FAN BLADE. |
| | |
| | PGS. E3.01, E3.02 & E3.03 |
| | THE NOTES ON ALL OF THE SHEETS ARE THE SAME; THEREFORE |
| | THE FIRST THREE COMMENTS APPLY TO ALL. |
| | 1. UNIT CODED NOTES, #4 SHALL INCLUDE THE TIP OF A |
| | CEILING FAN. (THE REGULATION INVOLVING THE KITCHEN IS |
| | ONLY THAT IF THE UNIT IS WITHIN 10? OF THE RANGE IT HAS |
| | TO BE SILENCEABLE). |
| | 2. ADDITIONAL NOTES, #7 IS A REPEAT OF #4 ABOVE, & #2 |
| | SHOULD BE AMENDED TO READ?AND BE RATED WEATHER |
| | RESISTANT ?WR? AS PER NEC 406.8. |
| | THE FOLLOWING ITEMS ARE ISSUES THAT WERE CLOUDED |
| | THROUGHOUT ALL THREE MODEL UNITS. THESE CLOUDS CAN BE |
| | SEEN BY VIEWING THE CHANGE MARK LAYERS. |
| | 3. NEC 210.52 (A)(1) RECEPTACLES SHALL BE INSTALLED |
| | SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE |
| | FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FT. FROM A |
| | RECEPTACLE OUTLET. THIS INCLUDES THE DISTANCE FROM THE |
| | EDGE OF THE WALL. |
| | 4. NEC 210.52 (A)(2) ANY WALL SPACE 2 FT. OR MORE IN |
| | WIDTH SHALL HAVE AN OUTLET |
| | 5. NEC 210.52(C)(1) A RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT EACH WALL COUNTERTOP SPACE THAT IS 12 IN. |
| | OR WIDER. RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT |
| | NO POINT ALONG THE WALL LINE IS MORE THAN 24 IN. |
| | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| | SPACE. |
| | 6. NEC 210.52(C)(3) AT LEAST ONE RECEPTACLE OUTLET |
| | SHALL BE INSTALLED AT EACH PENINSULAR COUNTERTOP. |
| | 7. NEC 210.520(D) IN DWELLING UNITS, AT LEAST ONE |
| | RECEPTACLE OUTLET SHALL BE INSTALLED IN BATHROOMS |
| | WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH BASIN. |
| | 8. NEC 210.70(A)(3) AT LEAST ONE LIGHTING OUTLET |
| | CONTAINING A SWITCH OR CONTROLLED BY A WALL SWITCH |
| | SHALL BE INSTALLED WHERE THESE SPACES ARE USED FOR |
| | STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICING. THE |
| | LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE |
| | EQUIPMENT REQUIRING SERVICING. THE CLOSET IN WHICH SMC |
| | BOX/CABINET IS IN SHALL HAVE THE REQUIRED LIGHTING. |
| | |
| | PG. E4.00A |
| | 1. SOUND SYSTEM NOTES BOX SHALL HAVE AN ADDITIONAL LINE |
| | ITEM STATING THAT THE AUDIO SYSTEM SHALL BE MUTED VIA |
| | THE FACP IN THE EVENT OF AN ALARM CONDITION. |
| | |
| | PG. E4.00B |
| | 1. ILLUMINATION ELECTRICAL NOTES #3, SEE CORRECTION TO |
| | NEC 700.12(F) |
| | |
| | PG. E4.01, E4.03, E4.05, E4.06, MAIN ELECTRICAL ROOM |
| | ?A?, ?B? & ?C? |
| | 1. SEE CLOUDED AREA IN ELECTRICAL ROOM NOTES WHICH HAS |
| | TO BE CLARIFIED. |
| | |
| | PG. E4.02 & E4.09 MACHINE ROOMS |
| | 1. ELEVATOR ELECTRICAL NOTES BOX, NOTRE #1 SHALL BE |
| | CORRECTED TO READ AS FOLLOWS: NEC 620.51. |
| | |
| | PG. E4.07, E4.08 ENLARGED TRASH ROOMS |
| | 1. BOTH, TRASH ROOM A, B, C & D, HAVE THE SAME COMMENT |
| | AS FOLLOWS: CHECK FOR PROPER WORKING CLEARANCE AS PER |
| | NEC 110.26. THERE DOES NOT APPEAR TO BE SUFFICIENT |
| | CLEARANCE BETWEEN THE ELECTRICAL OUTLETS AND WHATEVER |
| | IS IN FRONT OF THEM. |
| | |
| | PG. E5.06 |
| | 1. CORRECT INCORRECTLY QUOTED NEC SECTION TO READ |
| | (410.130(G)) |
| | 2. CLARIFY YOUR INTENT AT THE OUTLET STUB UP DETAIL |
| | |
| | THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008 |
| | EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE |
| | APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA |
| | BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION. |
| | |
| 2015-06-09 15:45:43 | SEE ATTACHMENTS FOR DERTAILS OF ELECTRICAL PLAN REVIEW |
| | RESULTS. |
| | FIRE ALARM REVIEW TO FOLLOW |