| Plan Review Notes For Permit 15050195 |
| Permit Number |
15050195 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-07 12:50:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A VERIFIABLE COPY OF THE CONTRACT FOR THIS | | | JOB, FBC 109. | | | | | | 2. PROVIDE A COPY OF THE SPEC SHEETS/ MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS FOR PRODUCTS PROPOSED | | | (ELASTOMERIC COATING, PRIMER, ETERNAMASTIC, FABRIC), | | | FBC 107. | | | | | | 3. PROVIDE EVIDENCE THAT THE COATING PROPOSED (#901 | | | ACRYLIC ELASTOMERIC COATING) COMPLIES WITH FBC | | | 1507.15.2: | | | | | | THE INSTALLATION OF LIQUID APPLIED ROOF COATINGS SHALL | | | COMPLY WITH ASTMC 836, ASTM C 957, ASTM D 1227 OR ASTM | | | D 3468, ASTM D 6083, ASTM D 6694 OR ASTMD 6947. | | | | | | 2. PROVIDE INFORMATION REGARDING THE EXISTING. REVISE | | | THE SPEC TO STATE WHETHER THE EXISTING ROOF IS AN | | | INSULATED OR NON-INSULATED DECK. | | | | | | | | | | | | |
|