| | PROJECT: KITCHEN REMODEL |
| | PERMIT#: 15050180 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) NEC 210.52(A) |
| | VERIFY RECEPTACLE SPACING. THERE APPEAR TO BE WALLS IN |
| | NEED OF RECEPTACLES TO MEET THIS MINIMUM REQUIREMENT. |
| | SEE THE DINING ROOM WALLS SPECIFICALLY. |
| | |
| | 2) NEC 210.7 (B) |
| | THE PANEL SCHEDULE INDICATES CIRCUITS 5 AND 7 ARE FOR |
| | THE DISHWASHER AND DISPOSAL BUT INDICATE A SINGLE |
| | RECEPTACLE FEEDING BOTH. WHERE TWO OR MORE BRANCH |
| | CIRCUITS SUPPLY DEVICES OR EQUIPMENT ON THE SAME YOKE, |
| | A MEANS TO SIMULTANEOUSLY DISCONNECT THE UNGROUNDED |
| | CONDUCTORS SUPPLYING THOSE DEVICES SHALL BE PROVIDED AT |
| | THE POINT AT WHICH THE BRANCH CIRCUITS ORIGINATE. |
| | |
| | 3) NEC 422.31 |
| | A DISCONNECT IS REQUIRED FOR THE WATER HEATER. |
| | |
| | 4) FBC-RESIDENTIAL 314 AND 315. |
| | SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED INSIDE AND |
| | OUTSIDE OF SLEEPING AREAS. WHEN ALTERATIONS, REPAIRS, |
| | OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR |
| | MORE SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING |
| | DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE |
| | EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW |
| | DWELLINGS. |
| | |
| | 5) NEC 210.12, 406.11 |
| | ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |