| 2015-05-07 12:40:02 | 5/7/2015 |
| | PROJECT: KITCHEN REMODEL |
| | PERMIT#: 15050180 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) NEC 210.52(A) |
| | VERIFY RECEPTACLE SPACING. THERE APPEAR TO BE WALLS IN |
| | NEED OF RECEPTACLES TO MEET THIS MINIMUM REQUIREMENT. |
| | |
| | 2) WPB AMENDMENTS TO FBC 107.3.5.1.2 |
| | PROVIDE ADDITIONAL DETAIL TO SUPPORT THE RELOCATION OF |
| | THE BREAKER PANEL INCLUDING HOW ALL EXISTING BRANCH |
| | CIRCUITS WILL BE RELOCATED. PROVIDE A DESIGN DETAIL |
| | ILLUSTRATING METHODS AND MATERIALS PROPOSED. |
| | |
| | 3) NEC 210.8(6) |
| | ALL ALL OUTLETS IN THE KITCHEN SHALL HAVE GFI |
| | PROTECTION FOR PERSONELL. |
| | |
| | 4) PROVIDE DIMENSIONS FOR NEW LOCATION OF PANELBOARD TO |
| | SHOW COMPLIANCE WITH THE NEC 110.26 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |