| Date |
Text |
| 2015-07-22 14:03:08 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15050177 |
| | ADD: 1152 OKEECHOBEE RD |
| | CONT: ABACOA CONSTRUCTION |
| | TEL: (561)722-3890 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WEDNESDAY JULY 22/ 2015 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED. |
| | |
| | 4) THE PLATFORM DOES INDICATEVERTICAL ACCESSIBILITY |
| | WILL BE ACHIEVED BY A PLATFORM LIFT. , PLEASE PROVIDE |
| | COMPLIANCE WITH THE 2010 FBC-ACCESSIBILITY CODE, |
| | 201.1.1 VERTICAL ACCESSIBILITYSECTIONS 553.501-553.513, |
| | F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN DO |
| | NOT RELIEVE THE OWNER OF ANY BUILDING, STRUCTURE OR |
| | FACILITY GOVERNED BY THOSE SECTIONS FROM THE DUTY TO |
| | PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS ABOVE AND |
| | BELOW THE OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER |
| | THE STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN |
| | SUCH BUILDING, STRUCTURE OR FACILITY. PLEASE PROVIDE |
| | THE MANUFACTURERS LIFT DESIGN CRITERIA. |
| | |
| | PLATFORM LIFTS ARE TO MEET THE ASME A18.1 STANDARDS. |
| | PLEASE SHOW COMPLIANCE WITH 410 PLATFORM LIFTS: |
| | |
| | 410.1 GENERAL. |
| | PLATFORM LIFTS SHALL COMPLY WITH ASME A18.1 (1999 |
| | EDITION OR 2003 EDITION) (INCORPORATED BY REFERENCE, |
| | SEE ?REFERENCED STANDARDS? IN CHAPTER 1). PLATFORM |
| | LIFTS SHALL NOT BE ATTENDANT-OPERATED AND SHALL PROVIDE |
| | UNASSISTED ENTRY AND EXIT FROM THE LIFT. |
| | |
| | 410.2 FLOOR SURFACES. |
| | FLOOR SURFACES IN PLATFORM LIFTS SHALL COMPLY WITH 302 |
| | AND 303. |
| | |
| | 410.3 CLEAR FLOOR SPACE. |
| | CLEAR FLOOR SPACE IN PLATFORM LIFTS SHALL COMPLY WITH |
| | 305. |
| | |
| | 410.4 PLATFORM TO RUNWAY CLEARANCE. |
| | THE CLEARANCE BETWEEN THE PLATFORM SILL AND THE EDGE OF |
| | ANY RUNWAY LANDING SHALL BE 1 INCH (32 MM) MAXIMUM. |
| | |
| | 410.5 OPERABLE PARTS. |
| | CONTROLS FOR PLATFORM LIFTS SHALL COMPLY WITH 309. |
| | |
| | 410.6 DOORS AND GATES. |
| | PLATFORM LIFTS SHALL HAVE LOW-ENERGY POWER-OPERATED |
| | DOORS OR GATES COMPLYING WITH 404.3. DOORS SHALL REMAIN |
| | OPEN FOR 20 SECONDS MINIMUM. END DOORS AND GATES SHALL |
| | PROVIDE A CLEAR WIDTH 32 INCHES (815 MM) MINIMUM. SIDE |
| | DOORS AND GATES SHALL PROVIDE A CLEAR WIDTH 42 INCHES |
| | (1065 MM) MINIMUM. |
| | |
| | 5-7) COMPLIED. |
| | |
| | 8) 2ND REQUEST. SHEET LS-1 THE DOOR SCHEDULE SHOWS DOOR |
| | TYPE 1 TO BE A 2'-8" DOORS ARE TO COMPLIANCE FOR FBC-B |
| | 1008.1.1 AND ACCESS. CODE 404.2.3. |
| | |
| | 9) SHEET LS-1 THE PLANS INDICATES THE STORAGE ROOM TO |
| | BE 425 SQ. FT. THE OVERALL TOTAL SQUARE FOOTAGE GIVEN |
| | IS 4,000 SQ. FT. OR OVER 10 % OF THE FLOOR AREA THAT |
| | CREATES A MIXED USE OCCUPANCY. SEE 2010 FBC-B 508.2.1 |
| | AREA LIMITATIONS. PLEASE REVIEW THE 2010 FBC-B TABLE |
| | 508.4 DEPENDING IF THE STORAGE ROOM IS A S1 OR S2 THE |
| | ROOM WILL REQUIRE A 1 HR OR 2 HOUR FIRE SEPARATION, NO |
| | FIRE SPRINKLERS. |
| | |
| | 10) THE MECHANICAL PLANS (M1) ALSO SHOW WALL LOUVERS |
| | AND ROOF TOP A/C STANDS. PLEASE PROVIDE COMPLIANCE |
| | WITH: |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(C) WALL LOUVERS- OUTSIDE AIR |
| | |
| | |
| | 11) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC |
| | |
| | 12 ) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |