| 2015-05-11 14:36:29 | PERMIT # 15050177 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PLAN APPROVED WITH COMMENTS. ALL COMMENTS MUST BE |
| | ADDRESSED AND/OR COMPLIED WITH. |
| | |
| | PROVISO: |
| | 1) SHEETS "C-1" AND "OC-1" SHOW DIFFERENT OCCUPANT |
| | LOADS. SHEET "C-1" STATES 341 OCCUPANTS AND SHEET |
| | "OC-1" SHOWS A TOTAL OF 150 OCCUPANTS. PLEASE PROVIDE |
| | THE CORRECT OCCUPANT LOAD. |
| | |
| | 2) PER NFPA 101, CHAPTER 13: EXISTING ASSEMBLY |
| | OCCUPANCIES - ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS |
| | OF 300 OR MORE SHALL BE PROVIDED WITH AN APPROVED FIRE |
| | ALARM SYSTEM AND PROTECTED BY AN APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | 4) EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | 5) PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS |
| | WITH EXIT SIGNS. |
| | |
| | 6) DJ BOOTH, PLATFORM, & STAGE: HANDRAILS ARE REQUIRED |
| | ON BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE LOCATED |
| | NOT LESS THAN 34 INCHES AND NOT MORE THAN 38 INCHES |
| | ABOVE THE SURFACE OF THE TREAD, MEASURED VERTICALLY TO |
| | THE TOP OF THE RAIL FROM THE LEADING EDGE OF THE TREAD. |
| | HANDRAIL ENDS SHALL BE RETURNED TO THE WALL OR FLOOR OR |
| | SHALL TERMINATE AT NEWEL POSTS. HANDRAIL CROSS SECTION |
| | SHALL HAVE A DIAMETER OF NOT LESS THAN 1.25 INCHES AND |
| | NOT MORE THAN 2 INCHES. |
| | |
| | 7) FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER |
| | THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE |
| | PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER |
| | LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE |
| | RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| | PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| | AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| | READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| | UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| | SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE |
| | LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED |
| | LOCK. |
| | |
| | |