| 2015-11-13 12:02:06 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. REVISE SITE PLAN TO SHOW DISTANCE TO PROPERTY LINES |
| | AND TO OTHER STRUCTURES, FBC TABLE 602. |
| | |
| | ENGINEER'S RESPONSE LETTER STATES THAT THIS WAS |
| | ADDRESSED. I AM UNABLE TO LOCATE THE DIMENSION FROM THE |
| | PROPOSED STRUCTURE TO THE SOUTH PROPERTY LINE, THE |
| | BUILDING TO THE NORTH, OR THE PROPERTY LINE TO THE |
| | WEST. ALSO, IF THE DISTANCE TO THE EXISTING BUILDING IS |
| | LESS THAN 60', SHOW THE ASSUMED PROPERTY LINE AND |
| | DISTANCE FROM EACH STRUCTURE TO THE ASSUMED PROPERTY |
| | LINE, FBC 5TH EDITION 705.3. |
| | |
| | 2. CONFLICTING INFORMATION PREVENTS PROVIDING AN |
| | ACCURATE REVIEW AT THIS TIME. OCCUPANCY IS F3, BUT NO |
| | INFORMATION PROVIDED REGARDING THE FACTORY OPERATIONS |
| | WHICH ARE TO TAKE PLACE IN THE PROPOSED STRUCTURE. THE |
| | RESPONSE LETTER FOR FIRE STATES THAT THIS WILL BE |
| | STORAGE. |
| | |
| | THE PLAN IS THE OFFICIAL PERMIT RECORD. PROVIDE MORE |
| | INFORMATION REGARDING THE FACTORY USE OF THE SPACE, |
| | MATERIALS TO BE USED, CHEMICALS TO BE STORED, ETC. ALSO |
| | PROVIDE A PLAN WHICH SHOWS COMPLIANCE WITH FBC |
| | ACCESSIBILITY OR INCORPORATE APPLICABLE EXCEPTIONS INTO |
| | THE PLAN. |
| | |
| | SEE DESCRIPTION OF F3 - "SHALL INCLUDE, AMONG OTHERS, |
| | THE OCCUPANCIES LISTED IN THIS SECTION: STEEL MILLS, |
| | PAPER PLANTS AND GENERATING PLANTS." |
| | |
| | 3. NOT ENOUGH INFORMATION PROVIDED REGARDING THE DOOR: |
| | |
| | THE ELEVATION DIFFERENCE AT THE DOORS WAS NOT SHOWN. DO |
| | THE DOORS HAVE A THRESHOLD, OR IS IT A VERTICAL PIECE |
| | OF METAL AT THE BOTTOM? 1008.1.7 |
| | REVISE PLAN TO SHOW COMPLIANCE WITH SEE FBC 1003.3, |
| | 1003.5, 1008.1.3, 1008.1.1 (4' MAX DOOR WIDTH), |
| | 1008.1.9. |
| | PROVIDE DOOR HEIGHT, 1008. |
| | PROVIDE HARDWARE INFORMATION - 1008.1.9. ALSO PROVIDE |
| | INFORMATION ON HOW DOES THE DOOR OPEN FROM THE INSIDE? |
| | |
| | ANY EXCEPTIONS USED ARE TO BE INCORPORATED INTO THE |
| | PLAN. |
| | |
| | 4. REVISE PLAN TO INCLUDE OCCUPANT LOAD, FBC 1004. |
| | |
| | 5. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED. |
| | CONTACT 561-233-5025 FOR MORE INFORMATION. |
| | |
| | |
| | |