| Plan Review Notes For Permit 15050133 |
| Permit Number |
15050133 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-27 16:49:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) NO GENERATOR DETAIL PROVIDED, INCLUDING TYPE AND | | | SIZE, FUEL SOURCE, EXHAUST LOCATION. | | | | | | 2) PROVIDE DETAILED AND ACCURATE DIMENSIONS FROM | | | PROPERTY LINE, BUILDING LINE, ADJACENT IMPORTANT | | | STRUCTURES, NEAREST OPENINGS TO ANY BUILDINGS. | | | | | | 3) PROVIDE NOTE INDICATING IF THIS SUPPLIES EMERGENCY | | | POWER TO THE LIFE SAFETY FIRE ALARM SYSTEM. IF SO, IT | | | SHALL COMPLY WITH ALL APPROPRIATE NFPA CODES. |
|