Plan Review Notes
Plan Review Notes For Permit 15050054
Permit Number 15050054
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-18 15:03:09ELECTRICAL PLAN REVIEW
  
 FIRST REVIEW FAILED AS INDICATED BELOW:
 THE FOLLOWING CORRECTIONS ARE REQUIRED TO THE
 ELECTRICAL SUBMITTAL FOR A SATISFACTORY ELECTRICAL
 REVIEW:
  
 1. IT IS CUSTOMARY TO PROVIDE THREE (3) SETS OF
 DRAWINGS FOR APPROVAL
 2. VALUATION AS INDICATED ON THE SEALED DRAWINGS DOES
 NOT MATCH THAT OF THE PERMIT APPLICATION.
 3. PER NOTE ON THE TITLE BLOCK, THESE DRAWINGS ARE NOT
 TO BE ALTERED.
 4. THE APPLICABLE VERSION OF THE NFPA 70 CURRENTLY IN
 USE IS THE 2008 EDITION AND NOT THE 2011 AS INDICATED
 ON THE DRAWINGS.
 5. AS PER FBC 107.2.1, PLANS ARE TO BE DIMENSIONED IN A
 SUITABLE MANNER, THE FONT ON THE TYPICAL ELEVATOR
 WIRING DIAGRAM IS NOT LEGIBLE.
 6. EXPLAIN WHY THE DEVICE AT THE 2ND FLR LOBBY IS NOT
 BEING INSTALLED, AND IF SO, CORRECT THE PLANS
 ACCORDINGLY.
  
 FOR QUESTIONS, PLEASE CONTACT MIKE ALBARRAN
 CITY OF WEST PALM BEACH ELECTRICAL PLANS EXAMINER
 [email protected]
  