| Plan Review Notes For Permit 15050054 |
| Permit Number |
15050054 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-18 15:03:09 | ELECTRICAL PLAN REVIEW | | | | | | FIRST REVIEW FAILED AS INDICATED BELOW: | | | THE FOLLOWING CORRECTIONS ARE REQUIRED TO THE | | | ELECTRICAL SUBMITTAL FOR A SATISFACTORY ELECTRICAL | | | REVIEW: | | | | | | 1. IT IS CUSTOMARY TO PROVIDE THREE (3) SETS OF | | | DRAWINGS FOR APPROVAL | | | 2. VALUATION AS INDICATED ON THE SEALED DRAWINGS DOES | | | NOT MATCH THAT OF THE PERMIT APPLICATION. | | | 3. PER NOTE ON THE TITLE BLOCK, THESE DRAWINGS ARE NOT | | | TO BE ALTERED. | | | 4. THE APPLICABLE VERSION OF THE NFPA 70 CURRENTLY IN | | | USE IS THE 2008 EDITION AND NOT THE 2011 AS INDICATED | | | ON THE DRAWINGS. | | | 5. AS PER FBC 107.2.1, PLANS ARE TO BE DIMENSIONED IN A | | | SUITABLE MANNER, THE FONT ON THE TYPICAL ELEVATOR | | | WIRING DIAGRAM IS NOT LEGIBLE. | | | 6. EXPLAIN WHY THE DEVICE AT THE 2ND FLR LOBBY IS NOT | | | BEING INSTALLED, AND IF SO, CORRECT THE PLANS | | | ACCORDINGLY. | | | | | | FOR QUESTIONS, PLEASE CONTACT MIKE ALBARRAN | | | CITY OF WEST PALM BEACH ELECTRICAL PLANS EXAMINER | | | [email protected] | | | |
|