Plan Review Notes
Plan Review Notes For Permit 15050048
Permit Number 15050048
Review Stop P
Sequence Number 1
Notes
Date Text
2015-05-05 05:53:051) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE
 INTERCEPTOR TO BE REPLACED. PLAN CAN BE HAND DRAWN.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SUBMIT DETAIL OF THE TYPE OF INTERCEPTOR TO BE
 INSTALLED. 2010 FPC 1003.2. SEE 2010 FPC SECS.
 1003.5.2, 1003.5.3 FOR CONSTRUCTION REQUIREMENTS.
 3) SUBMIT INTERCEPTOR SIZING CALCULATIONS TO ENSURE
 THAT THE INTERCEPTOR BEING INSTALLED, ALTHOUGH AN EXACT
 REPLACEMENT, IS SIZED CORRECTLY. THE EXISTING UNIT MAY
 NOT HAVE BEEN SIZED CORRECTLY AND NOW IS THE TIME TO
 CORRECT ANY ISSUES. 2010 FPC SEC.1003.5.1 AND TABLE
 1003.5.1.
  
 PLUMBING PLAN REVIEW