| Notes |
| Date |
Text |
| 2015-05-05 05:53:05 | 1) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE | | | INTERCEPTOR TO BE REPLACED. PLAN CAN BE HAND DRAWN.WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 2) SUBMIT DETAIL OF THE TYPE OF INTERCEPTOR TO BE | | | INSTALLED. 2010 FPC 1003.2. SEE 2010 FPC SECS. | | | 1003.5.2, 1003.5.3 FOR CONSTRUCTION REQUIREMENTS. | | | 3) SUBMIT INTERCEPTOR SIZING CALCULATIONS TO ENSURE | | | THAT THE INTERCEPTOR BEING INSTALLED, ALTHOUGH AN EXACT | | | REPLACEMENT, IS SIZED CORRECTLY. THE EXISTING UNIT MAY | | | NOT HAVE BEEN SIZED CORRECTLY AND NOW IS THE TIME TO | | | CORRECT ANY ISSUES. 2010 FPC SEC.1003.5.1 AND TABLE | | | 1003.5.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|