| Plan Review Notes For Permit 15050043 |
| Permit Number |
15050043 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-05 11:46:52 | | | | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15050043 | | | ADD: 7200 GEORGIA AVE. | | | CONT: SOLIS ROOFING | | | TEL: (561)662-6622 | | | E-MAIL: | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUES. MAY 05/ 2015 | | | ACTION: DENIED | | | | | | 1) CONTRACTOR HAS NOT IDENTIFIED WHICH SUB-SYSTEM IS TO | | | BE INSTALLED NOR THE PRESSURES FOR THE SUB-SYSTEM AND | | | LIMITATIONS. 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY | | | THE CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, | | | DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM, | | | MATERIALS, FASTENING REQUIREMENTS, FLASHING | | | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE | | | REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND | | | INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND | | | CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT | | | BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST | | | BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|