| 2015-05-13 13:49:15 | DISPOSITION AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN | | | REVIEW | | | PERMIT #: 15050041 | | | DATE: 5/13/15 | | | APPLICABLE CODES:NFPA 72 2013; FBC 2010; WPB AMENDMENTS | | | TO FBC 2010 CHAPTER 1; NEC 2008 | | | REVIEW CYCLE: 1 | | | ACTION: FAILED | | | | | | THE ABOVE MENTIONED PERMIT FAILED ELECTRICAL REVIEW AS | | | FOLLOWS: | | | | | | AS PER NFPA 72, SECTION 7.4.5, THE SUBMITTED DRAWING | | | FAIL TO INDICATE: | | | 1. THE ROOM DESCRIPTION OF EVERY ROOM AND/OR AREA | | | 2. THE LOCATION OF PRIMARY POWER DISCONNECTING MEANS | | | 3. THE IDENTIFICATION OF CEILINGS OVER 10' IN HEIGHT | | | 4. INDICATION OF TYPE OF CEILING. | | | AS PER NFPA 72 SECTION 10.6.5 | | | 1. MAKE REFERENCE TO THE LABELING AND MECHANICAL | | | PROTECTION FOR THE SYSTEM DISCONNECTING MEANS. | | | THE PLANS DO NOT INDICATE THE LOCATION OF THE HVAC | | | UNITS THEREFORE, | | | AS PER NFPA 72, SECTION 23.8.5.4.6 | | | 1. THE LOCATION OF THE RESET SWITCH FOR THE DUCT | | | DETECTORS IF ANY. | | | |
|