| 2015-06-22 11:43:22 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | | FEE(S). | | | | | | 1) PROVIDE A VOLTAGE DROP CALCULATION TO THE INSPECTOR | | | UPON 1ST INSPECTION IN THE FIELD INDICATING THE FEEDER | | | CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN | | | REQUIRED TO SUPPLY THE LOAD AS CALCULATED NEC 215.2 | | | (A)(1). MINIMUM RATING AND SIZE. | | | | | | 2) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM, | | | POS,SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, | | | COMMUNICATION AS NEEDED. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | | | | |
|