Plan Review Notes
Plan Review Notes For Permit 15050015
Permit Number 15050015
Review Stop E
Sequence Number 2
Notes
Date Text
2015-06-22 11:43:22APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) PROVIDE A VOLTAGE DROP CALCULATION TO THE INSPECTOR
 UPON 1ST INSPECTION IN THE FIELD INDICATING THE FEEDER
 CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN
 REQUIRED TO SUPPLY THE LOAD AS CALCULATED NEC 215.2
 (A)(1). MINIMUM RATING AND SIZE.
  
 2) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM,
 POS,SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND,
 COMMUNICATION AS NEEDED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  